Lennox International Inc 51M32 operation manual Thermostat Output Table

Page 6

Equipment Protection Override

Both the minimum compressor OFF timer and the mini- mum equipment cycle timer can be over−ridden by press- ing and holding either the HEAT or COOL button down for 4 seconds.

Over−Temperature Protection

Thermal mechanical switch opens W1 at 93°F+/−6°F.

Filter Reminder

Settings of 0 (Off), 1, 3, 6 or 12 months are available. When programmed time has elapsed, a FILTER indicator is dis- played.

Service Reminder

The SERVICE indicator is displayed only under the follow- ing conditions:

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;

OR

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of programmed temperature setpoint, heat/cool and fan mode settings, fil- ter reminder status, and equipment protection timers). Af- ter 24 hours of power loss, programmed settings will be lost and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.

LCD Backlight

Activated for 8 seconds when any key is pressed.

NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is normal and will no longer occur after the electrical disturbance has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Thermostat Output Table

The following table depicts the 51M32 thermostat output states for various input conditions. See table 2.

Table 2

Thermostat Outputs

Condition

 

W1

Y1

G

 

 

 

 

 

 

 

 

 

Gas Heat, Auto Fan

 

 

 

 

 

 

 

heat demand

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

 

 

 

 

 

no demand

 

 

 

 

 

 

 

 

 

Gas Heat, Continuous Fan

 

 

 

 

 

 

 

heat demand

 

X

 

X

 

 

 

 

 

cool demand

 

 

X

X

 

 

 

 

 

no demand

 

 

 

X

 

 

 

 

 

Electric Heat, Auto Fan

 

 

 

 

 

 

 

heat demand

 

X

 

X

 

 

 

 

 

cool demand

 

 

X

X

 

 

 

 

 

no demand

 

 

 

 

 

 

 

 

 

Electric Heat, Continuous Fan

 

 

 

 

 

 

 

heat demand

 

X

 

X

 

 

 

 

 

cool demand

 

 

X

X

 

 

 

 

 

no demand

 

 

 

X

 

 

 

 

 

NOTE −

 

 

 

X = output is activated with 24VAC.

 

 

 

Page 6

Image 6
Contents MeritR Series Thermostat Table of ContentsInitial Thermostat Power-up GeneralHeating Control Heat Mode EnabledHeat Mode Disabled Display − Home ScreenSetpoint Display and Adjustment Adjusting Temperature SetpointEnabling and Disabling Cool Mode Cooling ControlFan Control Filter ReminderDefault Thermostat Settings Service IndicatorThermostat Reset Technical SpecificationsThermostat Output Table Controls 51M33 Normal Heat Mode Enabled Additional Thermostat Buttons Normal Heat ModeEmergency Heat Mode Emergency Heat Mode EnabledCooling Control Fan Control Balance Point Setting Service Indicator Flashing RoomBalance Point Backup Heat Source Selection 51M33 Terminal DesignationsBalance Point Thermostat Output Table Electric Heat Backup − Outdoor Sensor Attached Electric Heat Backup − No Outdoor SensorGas Heat Backup Dual Fuel − No Outdoor Sensor Gas Heat Backup Dual Fuel − Outdoor Sensor Attached