Lennox International Inc 51M32 Thermostat Output States, Electric Heat Backup − No Outdoor Sensor

Page 14

Table 3

Thermostat Output States

Condition

W1

 

Y1

G

O

E

 

 

 

 

 

 

 

Electric Heat Backup − No Outdoor Sensor

 

 

 

 

 

 

 

 

 

 

 

small heat demand

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand

X

 

X

X

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

X

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

Gas Heat Backup (Dual Fuel) − No Outdoor Sensor

 

 

 

 

 

 

 

 

 

 

small heat demand

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand

X

 

 

 

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

 

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

 

Electric Heat Backup − Outdoor Sensor Attached

 

 

 

 

 

 

 

 

 

 

 

small heat demand (BBP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (BBP)

X

 

X

X

 

 

 

 

 

 

 

 

 

small heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

X

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached

 

 

 

 

 

 

 

 

 

small heat demand (BBP)

X

 

 

 

 

 

 

 

 

 

 

 

 

large heat demand (BBP)

X

 

 

 

 

 

 

 

 

 

 

 

 

small heat demand (ABP)

 

 

X

X

 

 

 

 

 

 

 

 

 

large heat demand (ABP)

X

 

 

 

 

 

 

 

 

 

 

 

 

emergency heat demand

 

 

 

 

 

X

 

 

 

 

 

 

 

cool demand

 

 

X

X

X

 

 

 

 

 

 

 

 

no demand

 

 

 

 

dc

 

 

 

 

 

 

 

 

NOTE −

 

 

 

 

 

 

S X = output is activated with 24VAC

S dc: does not care (output can be in either state, i.e., either active or inactive)

S BBP: outdoor temperature is below balance point

S ABP: outdoor temperature is above balance point

S small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage timer has not expired (see Normal Heat Mode graph)

S large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor- mal Heat Mode graph)

S the state of the B terminal is opposite the state of the O terminal.

S data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.

Page 8

Image 14
Contents MeritR Series Thermostat Table of ContentsInitial Thermostat Power-up GeneralHeating Control Heat Mode EnabledHeat Mode Disabled Display − Home ScreenSetpoint Display and Adjustment Adjusting Temperature SetpointEnabling and Disabling Cool Mode Cooling ControlFan Control Filter ReminderDefault Thermostat Settings Service IndicatorThermostat Reset Technical SpecificationsThermostat Output Table Controls 51M33 Normal Heat Mode Enabled Additional Thermostat Buttons Normal Heat ModeEmergency Heat Mode Emergency Heat Mode EnabledCooling Control Fan Control Balance Point Balance Point SettingService Indicator Flashing Room Balance Point Backup Heat Source Selection51M33 Terminal Designations Thermostat Output Table Electric Heat Backup − Outdoor Sensor Attached Electric Heat Backup − No Outdoor SensorGas Heat Backup Dual Fuel − No Outdoor Sensor Gas Heat Backup Dual Fuel − Outdoor Sensor Attached