Lennox International Inc 06/11 50672801 Optimizing System Refrigerant Charge, Cfm =, Action

Page 24
3. Determine if fan needs adjustment

Optimizing System Refrigerant Charge

This section provides instructions on optimizing the system charge. This section includes:

SOptimizing procedure

SAdjusting indoor airflow

SUsing subcooling method

SApproved matched components, targeted subcooling (SC) values and add charge values

SNormal operating pressures

STemperature pressures

OPTIMIZING PROCEDURE

1.Move the low−side manifold gauge hose from the vapor line service valve to the true suction port (see figure 17).

2.Set the thermostat for either cooling or heating demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit.

3.Allow unit to run for five minutes to allow pressures to stabilize.

4.Check the airflow as instructed under Adjusting Indoor Airflow to verify or adjust indoor airflow for maximum

efficiency. Make any air flow adjustments before continuing with the optimizing procedure.

5.Use subcooling method to optimize the system charge (see figure 21). Adjust charge as necessary.

ADJUSTING INDOOR AIRFLOW

Heating Mode Indoor Airflow Check

(Only use when indoor unit has electric heat)

Indoor blower airflow (CFM) may be calculated by energizing electric heat and measuring:

STemperature rise between the return air and supply air temperatures at the indoor coil blower unit,

SMeasuring voltage supplied to the unit,

SMeasuring amperage being drawn by the heat unit(s).

Then, apply the measurements taken in the following formula to determine CFM:

Amps x Volts x 3.41

CFM =

1.08 x Temperature rise (F)

Cooling Mode Indoor Airflow Check

Check airflow using the Delta−T (DT) process using figure 20.

ADJUSTING INDOOR AIRFLOW

 

 

 

 

 

 

 

 

 

 

 

 

DT

 

 

 

 

 

 

 

 

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of air

 

 

80

24

24

24

23

23

22

22

 

22

20

19

18

17

16

15

 

entering

Dry−bulb

78

23

23

23

22

22

21

21

 

20

19

18

17

16

15

14

 

indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

76

22

22

22

21

21

20

19

 

19

18

17

16

15

14

13

 

 

 

 

 

coil ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

21

21

21

20

19

19

18

 

17

16

16

15

14

13

12

 

 

 

 

 

 

 

A

 

 

 

72

20

20

19

18

17

17

16

 

15

15

14

13

12

11

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7019 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet−bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

1. Determine the desired DT

ature using dry bulb (A) and wet bulb (B). DT is the intersect- ing value of A and B in the table (see triangle).

2. Find temperature drop across coil

bulb entering and leaving air temperatures (A and C). Tem- perature Drop Formula: (TDrop) = A minus C.

ference between

 

 

B

 

C

TDrop

 

 

 

 

 

53º

19º

 

 

 

 

 

 

air flow

air flow

B

DRY

 

 

64º

BULB

 

 

 

All temperatures are

INDOOR

 

COIL

 

expressed in ºF

 

 

 

A 72º

DRY

BULB

WET

BULB

the measured TDrop and the desired DT (TDropDT) is within +3º, no adjustment is needed. See examples: Assume DT =

15 and A temp. = 72º, these C temperatures would necessi- tate stated actions:

TDrop

DT

=

ºF

ACTION

53º

19

15

=

4

Increase the airflow

58º

14

15

=

−1

(within +3º range) no change

62º

10

15

=

−5

Decrease the airflow

4.Adjust the fan speed crease/decrease fan speed.

Changing air flow affects all temperatures; recheck tempera- tures to confirm that the temperature drop and DT are within +3º.

Figure 20. Checking Airflow over Indoor Coil Using Delta−T Formula

506728−01

Page 24

Image 24
Contents Table of Contents Shipping and Packing ListGeneral Unit Dimensions − Inches mm Model Number Identification 13 −036 − 230 −08Side View TOP ViewPLUMBING, Switches Sensor Components Typical Unit Parts ArrangementControl Panel Operating Gauge Set and Service Valves Operating Service ValvesUsing Manifold Gauge SET Caps and Fasteners Torque RequirementsOperating Angle−Type Service Valve Operating Ball−Type Service ValveReinstall Stem Cap Recovering Refrigerant from Existing System 1DISCONNECT Power3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal NEW or Replacement Line SET Installation Using Existing Line SETLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core RemovalWrap Service Valves Flow Nitrogen6BRAZE Line SET Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure 3FLUSHING Line SETInstalling New Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Connect Gauge SETTest for Leaks Evacuating Line Set and Indoor Coil 2EVACUATE the SystemSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerTypical Unit Wiring Diagram Unit Start−Up Unit START−UPLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and WEIGH−IN ChargeConnections for Optimizing System Charge Using HFC−410A Weigh In Method Calculating System Charge for Outdoor Unit Void of ChargeOptimizing Procedure Adjusting Indoor AirflowOptimizing System Refrigerant Charge CFM =SATº LIQº SCºIf subcooling value is RefrigerantNormal Operating Pressures − Liquid +10 and Vapor +5 Psig HFC−410A Temperature F − Pressure Psig System Operation Defrost SystemDefrost Control CMC1 OFF Maintenance DealerIndoor Unit Indoor CoilXP13 Series Start−Up and Performance Checklist Installer CityJob Name Job no Date Job Location City Sequence of Operation Thermostat

LENNOX Elite Series XP13 Units HEAT PUMPS, 06/11 50672801 specifications

Lennox International Inc., a leading name in the HVAC (heating, ventilation, and air conditioning) industry, has a reputation for delivering high-quality and energy-efficient systems. One of the standout products in their lineup is the Lennox Elite Series XP13 heat pump, model number 50672801. This heat pump is designed to provide exceptional comfort throughout the year while offering efficiency and reliability that homeowners can depend on.

The Lennox Elite Series XP13 heat pump features a compact design that makes it suitable for various outdoor spaces. One of its main characteristics is its efficiency, boasting a SEER (Seasonal Energy Efficiency Ratio) rating of up to 16 and an HSPF (Heating Seasonal Performance Factor) of up to 9. This means that the XP13 can help reduce energy bills, making it an eco-friendly choice for homeowners looking to minimize their carbon footprint.

This heat pump utilizes advanced technology to ensure optimal performance. The XP13 is equipped with a scroll compressor, which operates quietly and efficiently compared to traditional compressors. This feature ensures a more reliable and consistent temperature control, which translates to enhanced comfort levels in the home. Moreover, the XP13 is designed with a sound-dampening system that reduces operational noise, making it one of the quieter options in the market.

Another key aspect of the XP13 heat pump is its innovative use of advanced coil technology. The unit's coils are made from high-grade aluminum, which promotes superior heat exchange and improves overall efficiency. In addition, the XP13 is designed with a built-in filter drier that helps remove moisture and contaminants from the refrigerant, protecting the system from potential damage and enhancing its lifespan.

The XP13 model is compatible with the iComfort S30 smart thermostat, allowing users to control their home’s temperature remotely. This smart technology provides energy-saving options and real-time updates, ensuring that homeowners can optimize their HVAC systems for both comfort and efficiency.

Overall, the Lennox Elite Series XP13 heat pump, model 50672801, exemplifies a commitment to delivering high-performance heating and cooling solutions. With its energy-efficient design, advanced technologies, and features aimed at enhancing user comfort and convenience, the XP13 remains a top choice among homeowners looking for a reliable and effective heat pump system.