Lennox International Inc 06/11 50672801 Line Set Requirements, Using Existing Line SET

Page 10

Line Set Requirements

This section provides information on: installation of new or replacement line set.

SAdding Polyol ester oil requirements

SNew or replacement line set installation

SUsing existing line set.

ADDING POLYOL ESTER OIL REQUIREMENTS

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol Ester oil.

The compressor is charged with sufficient Polyol Ester oil (POE) for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. Systems with 20 pounds or less of refrigerant required no oil to be added.

For systems over 20 pounds − add one ounce for every five

(5) pounds of HFC−410A refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

NEW OR REPLACEMENT LINE SET INSTALLATION

Field refrigerant piping consists of both liquid and vapor lines from the outdoor unit to the indoor coil. Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as specified in table 2.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended installation practices.

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XP13) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

USING EXISTING LINE SET

Things to consider:

SLiquid line that meter the refrigerant, such as RFC1 liquid line, must not be used in this application.

SExisting line set of proper size as listed in table 2 may be reused.

SIf system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page 15).

If existing line set is being used, then proceed to Brazing Connections on page 11.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing Line Set and Indoor Coil on page 13.

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

Table 2. Refrigerant Line Set

 

Field Connections

 

Recommended Line Set

Model

 

 

 

 

 

 

Liquid Line

Suction Line

Liquid Line

Suction Line

L15 Line Set

 

 

 

 

 

 

XP13−018−230

 

 

 

 

 

 

 

 

 

 

 

XP13−024−230

 

 

 

 

 

 

3/8" (10 mm)

3/4" (19 mm)

3/8" (10 mm)

3/4" (19 mm)

L15−41

XP13−030−230

 

 

 

 

 

 

 

 

 

 

 

XP13−036−230

 

 

 

 

 

 

 

 

 

 

 

XP13−042−230

 

 

 

 

 

 

3/8" (10 mm)

7/8" (22 mm)

3/8" (10 mm)

7/8" (22 mm)

L15−65

XP13−048−230

 

 

 

 

 

 

 

 

 

 

 

XP13−060−230

3/8" (10 mm)

1−1/8" (29 mm)

3/8" (10 mm)

1−1/8" (29 mm)

Field Fabricated

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

506728−01

Page 10

Image 10
Contents Shipping and Packing List Table of ContentsGeneral Side View Unit Dimensions − Inches mmModel Number Identification 13 −036 − 230 −08 TOP ViewTypical Unit Parts Arrangement PLUMBING, Switches Sensor ComponentsControl Panel Using Manifold Gauge SET Operating Gauge Set and Service ValvesOperating Service Valves Caps and Fasteners Torque RequirementsOperating Ball−Type Service Valve Operating Angle−Type Service ValveReinstall Stem Cap 3RECOVERING Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal Line Set Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections 1CUT and Debur 2CAP and Core Removal6BRAZE Line SET Wrap Service ValvesFlow Nitrogen Preparation for Next Step2CONNECT Gauges and Equipment for Flushing Procedure 3FLUSHING Line SETSensing Bulb Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Equalizer Line InstallationConnect Gauge SET Leak Test Line Set and Indoor CoilTest for Leaks Evacuating Line Set and Indoor Coil 2EVACUATE the SystemElectrical Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC TransformerTypical Unit Wiring Diagram Unit Start−Up Unit START−UPConnect Manifold Gauge SET and WEIGH−IN Charge Leak CHECK, Repair and EvacuateConnections for Optimizing System Charge Using HFC−410A Weigh In Method Calculating System Charge for Outdoor Unit Void of ChargeOptimizing System Refrigerant Charge Optimizing ProcedureAdjusting Indoor Airflow CFM =If subcooling value is SATº LIQºSCº RefrigerantNormal Operating Pressures − Liquid +10 and Vapor +5 Psig HFC−410A Temperature F − Pressure Psig Defrost System System OperationDefrost Control CMC1 OFF Indoor Unit MaintenanceDealer Indoor CoilXP13 Series Job Name Job no Date Job Location City Start−Up and Performance ChecklistInstaller City Sequence of Operation Thermostat

LENNOX Elite Series XP13 Units HEAT PUMPS, 06/11 50672801 specifications

Lennox International Inc., a leading name in the HVAC (heating, ventilation, and air conditioning) industry, has a reputation for delivering high-quality and energy-efficient systems. One of the standout products in their lineup is the Lennox Elite Series XP13 heat pump, model number 50672801. This heat pump is designed to provide exceptional comfort throughout the year while offering efficiency and reliability that homeowners can depend on.

The Lennox Elite Series XP13 heat pump features a compact design that makes it suitable for various outdoor spaces. One of its main characteristics is its efficiency, boasting a SEER (Seasonal Energy Efficiency Ratio) rating of up to 16 and an HSPF (Heating Seasonal Performance Factor) of up to 9. This means that the XP13 can help reduce energy bills, making it an eco-friendly choice for homeowners looking to minimize their carbon footprint.

This heat pump utilizes advanced technology to ensure optimal performance. The XP13 is equipped with a scroll compressor, which operates quietly and efficiently compared to traditional compressors. This feature ensures a more reliable and consistent temperature control, which translates to enhanced comfort levels in the home. Moreover, the XP13 is designed with a sound-dampening system that reduces operational noise, making it one of the quieter options in the market.

Another key aspect of the XP13 heat pump is its innovative use of advanced coil technology. The unit's coils are made from high-grade aluminum, which promotes superior heat exchange and improves overall efficiency. In addition, the XP13 is designed with a built-in filter drier that helps remove moisture and contaminants from the refrigerant, protecting the system from potential damage and enhancing its lifespan.

The XP13 model is compatible with the iComfort S30 smart thermostat, allowing users to control their home’s temperature remotely. This smart technology provides energy-saving options and real-time updates, ensuring that homeowners can optimize their HVAC systems for both comfort and efficiency.

Overall, the Lennox Elite Series XP13 heat pump, model 50672801, exemplifies a commitment to delivering high-performance heating and cooling solutions. With its energy-efficient design, advanced technologies, and features aimed at enhancing user comfort and convenience, the XP13 remains a top choice among homeowners looking for a reliable and effective heat pump system.