STEP 3 -- LEAK TEST AND EVACUATION
LEAK TEST
LOWHIGH
MANIFOLD GAUGE SET
B
A
TO VAPOR
SERVICE VALVE (ANGLE OR BALL TYPE)
| NITROGEN | OUTDOOR UNIT |
|
| |
CONNECT GAUGE SET |
|
1A Connect the high pressure hose of an
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
BWith both manifold valves closed, connect the cylinder of
NOTE — Later in the procedure, the
2After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:
TEST FOR LEAKS
AWith both manifold valves closed, connect the cylinder of
BOpen the high pressure side of the manifold to allow
CConnect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
DAdjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
EAfter a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
FAfter leak testing, disconnect gauges from service ports.
FIGURE 11
Page 9
13ACX SERIES