Lennox International Inc 506945-01 Checking and Adding System Refrigerant, Homeowners Information

Page 14

CHECKING AND ADDING SYSTEM REFRIGERANT

The 13ACX unit is factory-charged with enough HFC-410A refrigerant to accommodate a 15-foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker located on the unit access panel. Detailed information is provided in the 13ACX Installation and Service Procedures manual (Corp0625-L5), which is available on DaveNet.

Homeowners Information

CAUTION

Before attempting to perform any service or mainte­ nance, turn the electrical power to unit OFF at discon­ nect switch.

Cleaning of the outdoor unit's coil should be performed by a licensed professional service technician (or equivalent). Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.

Outdoor Coil

The outdoor unit must be properly maintained to ensure its proper operation.

SPlease contact your dealer to schedule proper inspection and maintenance for your equipment.

SMake sure no obstructions restrict airflow to the outdoor unit.

SGrass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy.

SKeep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.

SKeep snow level below the louvered panels to ensure proper performance.

IMPORTANT !

Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soak­ ers, waste water, etc.) will corrode the surface of steel and aluminum parts, diminish performance and af­ fect longevity of the unit.

Routine Maintenance

In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.

NOTE The filter and all access panels must be in place any time the unit is in operation. If you are unsure about the filter required for your system, call your Lennox dealer for assistance.

1.Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.

2.Disposable filters should be replaced with a filter of the same type and size.

3.The indoor evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)

Thermostat Operation

See the ComfortSense® 7000 thermostat homeowner manual for instructions on how to operate your thermostat.

Preservice Check

If your system fails to operate, check the following before calling for service:

SVerify room thermostat settings are correct.

SVerify that all electrical disconnect switches are ON.

SCheck for any blown fuses or tripped circuit breakers.

SVerify unit access panels are in place.

SVerify air filter is clean.

SIf service is needed, locate and write down the unit model number and have it handy before calling.

Page 14

Image 14
Contents Minimum Clearance Between TWO Units Setting the Unit -- ClearancesGeneral Unit Dimensions Setting the Unit CONTIN­ UED -- Unit PlacementUnit Dimensions Inches MM PlacementRefrigerant Line SET Installing Horizontal Runs InstallationRefrigerant Line SET Installing Vertical Runs NEW Construction ShownRefrigerant Line SET Inches MM Liquid Line Filter Drier InstallationTypical Liquid Line Filter Drier Installation 2CONNECT Gauges and Equipment for Flushing Procedure Refrigerant Piping -- Brazing Procedures 1CUT and Debur6BRAZE Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next StepSensing Bulb Installation Refrigerant Piping -- Installing Indoor Expansion ValveIndoor Expansion Valve Installation Equalizer Line InstallationLeak Test and Evacuation Leak TestEvacuation Open both manifold valves and start the vacuum pumpInstall Thermostat Electrical -- Circuit Sizing and Wire RoutingSize Circuit and Install Service Disconnect Switch 24VAC TransformerHigh Voltage / Ground Wires Field Control Wiring Electrical -- High Voltage and Field Control WiringRouting High VOLTAGE, Ground and Control Wiring Operating Manifold Gauge SET and Service ValvesTorque Requirements Checking and Adding System Refrigerant Homeowners InformationStart UP Checks 13ACX Start-Up and Performance ChecklistCooling Mode