STEP 2
| TYPICAL EXISTING FIXED ORIFICE |
| TYPICAL EXISTING EXPANSION VALVE REMOVAL | |||
1A | REMOVAL PROCEDURE | OR | 1BPROCEDURE (UNCASED COIL SHOWN) | |||
(UNCASED COIL SHOWN) | ||||||
|
|
|
| STUB END |
| |
| DISTRIBUTOR TUBES |
| LIQUID LINE |
|
| |
|
| (UNCASED COIL ONLY) |
|
| ||
|
| ORIFICE |
|
| ||
|
|
| EXPANSION |
| ||
|
|
|
|
| ||
| LIQUID LINE ORIFICE HOUSING |
|
| HOUSING |
| |
|
| DISTRIBUTOR | VALVE |
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
| TEFLON® RING |
| TUBES |
|
| TEFLON® |
|
|
|
|
| RING | |
| FIXED ORIFICE |
|
|
|
|
|
| BRASS NUT |
|
| TEFLON® |
| |
|
|
|
|
| SENSING | |
|
|
|
|
| RING | |
|
|
|
|
|
| LINE |
DISTRIBUTOR ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON® SEAL
(IF PRESENT) LIQUID LINE ASSEMBLY (INCLUDES STRAINER)
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps from the liquid line and distributor as sembly.
CUsing two wrenches, disconnect liquid line from liquid line orifice hous ing. Take care not to twist or damage distributor tubes during this pro cess.
DRemove and discard fixed orifice, valve stem assembly (if present) and Teflon® washer as illustrated above.
EUse a
2CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
DISTRIBUTOR EQUALIZER
ASSEMBLY LINE
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
MALE EQUALIZER |
|
| |
LINE FITTING | VAPOR |
| |
| LIQUID | ||
SENSING BULB | LINE | ||
LINE | |||
| |||
|
|
AOn fully cased coils, remove the coil access and plumbing panels.
BRemove any shipping clamps from the liquid line and distributor assembly.
CDisconnect the equalizer line from the expansion valve equalizer line fitting on the vapor line.
DRemove the vapor line sensing bulb.
EDisconnect the liquid line from the expansion valve at the liquid line assembly.
A
VAPOR LINE SERVICE VALVE
CYLINDER CONTAINING |
| GAUGE |
CLEAN |
| MANIFOLD |
USED FOR FLUSHING |
|
|
(Positioned to deliver liquid |
| |
refrigerant) |
|
|
1 | LOW | HIGH |
NEW
OUTDOOR
UNIT
FDisconnect the expansion valve from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
GRemove and discard expansion valve and the two Teflon® rings.
HUse a
3FLUSHING LINE SET
OPENED CLOSED
EXISTING
INDOOR
UNITB
LIQUID LINE SERVICE
VALVE
RECOVERY |
|
CYLINDER | TANK |
| RETURN |
| VAPOR LIQUID | C | DISCHARGE |
D |
|
| INLET |
|
|
| |
|
|
| RECOVERY MACHINE |
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
ASet the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
BPosition the cylinder of clean
A
B
C
DConnect recovery tank to recovery machine per machine instructions.
CAfter all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the
DClose the valve on the inverted
FIGURE 7
Page 5