3)Pilot Outage.

1) Too low or too high gas

1)

Adjust inlet gas pressure as

 

(Standing pilot models)

 

pressures.

 

shown on rating plate.

 

 

2)

Restricted pilot.

2)

Clean pilot orifice.

 

 

3)

Weak thermocouple.

3)

Replace thermocouple.

 

 

 

 

 

4)Yellow lazy flame.

1) Too low gas pressure.

1) Adjust manifold pressure as

 

 

2)

Restricted burner intake ports.

 

shown on rating plate.

 

 

2) Clean burners free of debris or

 

 

3)

Restricted gas line.

 

insects.

 

 

3) Clean gas line or increase gas line

 

 

 

 

 

piping.

 

 

 

 

 

 

5)Sooting

1) Insufficient combustion air.

1)

Refer to installation instructions

 

 

 

 

 

regarding combustion air

 

 

 

 

 

requirements.

 

 

2)

Improper venting.

2)

Refer to installations instructions.

 

 

3) Severe yellow burner flames.

3)

See yellow flame section above.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

Image 27
Contents For Your Safety Installation and Operating InstructionsTable of Contents General Specifications Specifications and DimensionsReceiving Equipment General Safety Precautions Scalding TIME/TEMPERATURE Relationships in ScaldsInstallation Procedures CoderequirementsMountingbase Fig. #8280.1 OutdoormodelsFig. #9351 Vent TERMINAL/INDOOR Stack Installation GAS Supply Connections Common VentsGAS PRESSURE-SPECIFICATIONS GAS Pressure RegulatorWater Connections & System Piping Relief Valve LOW NOx WH1Wiring Diagram KEY ElectricalwiringModels 260 Wiring Diagram Standing PilotFig. #2373 Wiring Diagram Intermittent Ignition Device IID ModelModels 330 Wiring Diagram Intermittent Ignition Device IIDModel 261 LOW NOx Model 401 LOW NOx Servicing Procedures START-UPPROCEDURESSequenceofoperation Intermittentignitiondeviceiid Fig.#8083.2 What to do if YOU Smell GASFor Automatic Ignition Models System Shut Down ProcedureInspectionprocedures Burners To Turn OFF GAS to ApplianceFor Automatic Ignition Systems Operation START-UP Procedures S8610BBurner Adjustment High GAS Pressure SwitchMain Burner and Orifice Removal Normal Inspection ProceduresBurner Drawer Removal GAS Valve RemovalCombustion Chamber Removal Heat Exchanger RE-ASSEMBLYRepair Section HeatexchangerremovalImportant Notice Trouble Shooting GuidePiping High Voltage TroubleshootingTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDHigh Voltage Electrical Standing PilotADJUSTMENTS/REPLACEMENTSOF Components RAYPAK, INC Replacement Parts ListFor Units with a LOW NOx Tray Page Page Limitedpartswarrantyeconopakwaterheaters