Raypak 260-401 manual TIME/TEMPERATURE Relationships in Scalds, Scalding

Page 5

General Safety Precautions

To meet commercial hot water requirements, the tankstat is adjustable up to 190°F. However, water temperatures over 125°F. can cause severe burns instantly or death from scalds. This is the preferred starting point for setting the control for supplying gen- eral purpose hot water.

Safety and energy conservation are factors to be considered when setting the water temperature on the tankstat. The most energy efficient operation will result when the temperature setting is the lowest that satis- fies the needs consistent with the application.

Water temperature over 125°F can cause severe burns instantly or death from scalds.

Children, disabled and elderly are at high- est risk of being scalded.

See instruction manual before setting temperature at tankstat.

Feel water before bathing or showering.

Temperature limiting valves are available, see manual.

Maximum water temperatures occur just after burner has shut off. To find hot water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.

The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.

Temperature

Time to Produce Serious Burn

120°F.

More than 5 minutes

 

 

125°F.

1-1/2 to 2 minutes

130°F.

About 30 seconds

135°F.

About 10 Seconds

140°F.

Less than 5 seconds

145°F.

Less than 3 seconds

150°F.

About 1-1/2 seconds

155°F.

About 1 second

Table courtesy of Shiners Burn Institute

TIME/TEMPERATURE RELATIONSHIPS IN SCALDS

The temperature of the water in the storage tank boiler can be regulated by setting the temperature dial on front of the tankstat. To comply with safety regulations, the tankstat was set at its lowest setting before ship- ment from the factory. The illustration below illustrates the tankstat and how to adjust the water temperature.

To adjust the water temperature, insert a small straight screwdriver into slotted screw in hole in front of tankstat and turn wheel to desired setting. Thermostat is adjustable up to 190°F.

CAUTION!! - Hotter water increases the risk of

SCALDING!

There is a Hot Water SCALD Potential if the tankstat is set too high.

NOTE: When this water is supplying general purpose hot water requirements for use by individuals, a ther- mostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.

5

Image 5
Contents For Your Safety Installation and Operating InstructionsTable of Contents Receiving Equipment General SpecificationsSpecifications and Dimensions General Safety Precautions Scalding TIME/TEMPERATURE Relationships in ScaldsMountingbase Installation ProceduresCoderequirements Fig. #8280.1 OutdoormodelsFig. #9351 Vent TERMINAL/INDOOR Stack Installation GAS Supply Connections Common VentsWater Connections & System Piping GAS PRESSURE-SPECIFICATIONSGAS Pressure Regulator Relief Valve LOW NOx WH1Wiring Diagram KEY ElectricalwiringModels 260 Wiring Diagram Standing PilotFig. #2373 Wiring Diagram Intermittent Ignition Device IID ModelModels 330 Wiring Diagram Intermittent Ignition Device IIDModel 261 LOW NOx Model 401 LOW NOx Sequenceofoperation Intermittentignitiondeviceiid Servicing ProceduresSTART-UPPROCEDURES Fig.#8083.2 What to do if YOU Smell GASFor Automatic Ignition Models System Shut Down ProcedureFor Automatic Ignition Systems Inspectionprocedures BurnersTo Turn OFF GAS to Appliance Burner Adjustment START-UP Procedures S8610BHigh GAS Pressure Switch OperationBurner Drawer Removal Normal Inspection ProceduresGAS Valve Removal Main Burner and Orifice RemovalRepair Section Heat Exchanger RE-ASSEMBLYHeatexchangerremoval Combustion Chamber RemovalImportant Notice Trouble Shooting GuidePiping Troubleshooting Honeywell S8600 TroubleshootingElectrical Electronic Ignition IID High VoltageHigh Voltage Electrical Standing PilotADJUSTMENTS/REPLACEMENTSOF Components RAYPAK, INC Replacement Parts ListFor Units with a LOW NOx Tray Page Page Limitedpartswarrantyeconopakwaterheaters