TROUBLESHOOTING

ELECTRICAL (ELECTRONIC IGNITION IID)

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

WARNING

HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

SPARK ACROSS

IGNITER/SENSOR GAP

YES

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

 

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout

 

 

 

procedure.

 

 

 

 

 

 

 

 

 

Check line voltage power, low voltage transformer, limit controller, thermostat

NO

 

 

(controller) and wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pull ignition lead and check spark at module.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Spark Okay?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

 

 

 

Check boot of the ignition cable for signs of melting or buckling. Take protective

 

 

 

 

action to shield cable and boot from excessive temperatures.

 

 

 

 

 

 

NO

 

Check that all manual gas valves are open, supply tubing and pressures are

 

 

 

 

good,

and pilot burner orifice is not blocked.

 

 

 

 

 

 

Check electrical connections between module and pilot operator on gas control.

 

 

 

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,

 

 

 

 

replace gas control; if not, replace module.

 

 

 

 

 

 

 

 

NOTE: If S8600H goes into lockout, reset system. Lockout is used on L.P.G.

 

 

 

models.

 

NO

 

• Check continuity of ignition cable and ground wire.

 

 

 

 

Clean flame rod.

 

 

 

Check electrical connections between flame rod and module.

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

Adjust pilot flame.

 

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

 

 

 

NO

 

 

 

 

 

Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though

 

 

 

 

 

operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

28

Image 28
Contents Installation and Operating Instructions For Your SafetyTable of Contents Specifications and Dimensions General SpecificationsReceiving Equipment General Safety Precautions TIME/TEMPERATURE Relationships in Scalds ScaldingCoderequirements Installation ProceduresMountingbase Outdoormodels Fig. #8280.1Fig. #9351 Vent TERMINAL/INDOOR Stack Installation Common Vents GAS Supply ConnectionsGAS Pressure Regulator GAS PRESSURE-SPECIFICATIONSWater Connections & System Piping LOW NOx WH1 Relief ValveElectricalwiring Wiring Diagram KEYWiring Diagram Standing Pilot Models 260Wiring Diagram Intermittent Ignition Device IID Model Fig. #2373Wiring Diagram Intermittent Ignition Device IID Models 330Model 261 LOW NOx Model 401 LOW NOx START-UPPROCEDURES Servicing ProceduresSequenceofoperation Intermittentignitiondeviceiid What to do if YOU Smell GAS Fig.#8083.2System Shut Down Procedure For Automatic Ignition ModelsTo Turn OFF GAS to Appliance Inspectionprocedures BurnersFor Automatic Ignition Systems START-UP Procedures S8610B Burner AdjustmentHigh GAS Pressure Switch OperationNormal Inspection Procedures Burner Drawer RemovalGAS Valve Removal Main Burner and Orifice RemovalHeat Exchanger RE-ASSEMBLY Repair SectionHeatexchangerremoval Combustion Chamber RemovalTrouble Shooting Guide Important NoticePiping Troubleshooting Troubleshooting Honeywell S8600Electrical Electronic Ignition IID High VoltageElectrical Standing Pilot High VoltageADJUSTMENTS/REPLACEMENTSOF Components Replacement Parts List RAYPAK, INCFor Units with a LOW NOx Tray Page Page Limitedpartswarrantyeconopakwaterheaters