Raypak 514-824 manual Troubleshooting Honeywell S8600, Electrical, Highvoltage

Page 25

ELECTRICAL

WARNING

HIGHVOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24VNOMINAL)

YES

SPARK ACROSS

IGNITER/SENSORGAP

YES

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAINBURNERLIGHTS?

YES

SYSTEMRUNS UNTIL

CALL FOR HEAT ENDS?

YES

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

 

 

 

NOTE:Before troubleshooting, familiarize yourself with the startup and checkout

 

 

 

procedure.

 

 

 

 

 

 

 

 

Check line voltage power, low voltage transformer, limit controller, thermostat (control-

NO

 

 

ler) and wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pull ignition lead and check spark at module.

 

 

 

NO

 

 

 

 

Spark Okay?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

 

 

 

• Check boot of the ignition cable for signs of melting or buckling. Take protective

 

 

 

action to shield cable and boot from excessive temperatures.

 

 

 

 

 

NO

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

 

 

 

 

and pilot burner orifice is not blocked.

 

 

 

 

 

 

• Check electrical connections between module and pilot operator on gas control.

 

 

 

• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,

 

 

 

replace gas control; if not, replace module.

 

 

 

 

 

 

 

 

NOTE:If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.

 

 

 

 

 

 

 

 

 

NO

 

• Check continuity of ignition cable and ground wire.

 

 

 

 

• Clean flame rod.

 

 

 

• Check electrical connections between flame rod and module.

 

 

 

• Check for cracked ceramic flame rod insulator.

 

 

 

• Check that pilot flame covers flame rod and is steady and blue.

 

 

 

• Adjust pilot flame.

 

 

 

• If problem persists, replace module.

 

 

 

 

 

 

 

 

• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

• Check electrical connections between module and gas control. If okay, replace

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

 

 

 

NO

 

 

 

• Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though

 

 

 

operation is normal at the time of checkout.

 

 

 

• Check that pilot flame covers flame rod and is steady and blue.

 

 

 

• If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

Check for proper thermostat (controller) operation.

Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

25

Image 25
Contents What to do if YOU Smell GAS Installation Operating Instructions CommercialWaterchemistry Contents For Your Safety Read Before Operating START-UP Procedures Before START-UPBurners WaterTo Turn OFF GAS to Appliance Operating InstructionsWater Pressure Switch Maintenance and Care ProceduresAfter START-UP Visual InspectionPool & SPA Water Chemistry Basic Tips if Heater will not FireCalifornia Proposition 65 Warning Important NoticeClearances Base InstallationStep #2 Indoor HeaterVenting Connections Vent PipingAnsi Z Gaspressureregulator GAS Supply ConnectionsPlumbing for Water Connections Location Pipe Sizing for GAS ConnectionsFlow Rates Model Pipe Size MIN. GPM MAX. GPM CompanionflangeconnectionsAuxiliary Bypass Valve Adjustmentinlet Pressure Relief Valve InstallationAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS UnithermgovernoroperationS8600 Ignition Control Electrical WiringPage 151965 152141 152142 Typical Comfortable SPA Temperature Range CONTROLS/ADJUSTMENTS/REPLACEMENTSKnobstopadjustment Servicing InsructionsPressure Switch Adjustment Pressure SwitchPressure Switch Adjustment Range Pilot SafetyRaypak Tube Cleaning KIT UNITHERMGOVERNORU.G.REPLACEMENT Desootingprocedure Combustionchamberremoval Important Notice Liming Electrical Troubleshooting Honeywell S8600Highvoltage Raypak, Inc Agoura Road Westlake Village, CA Replacement Parts ListThis page is empty Pilot ASSEMBLY- Electronic Ignition Page Page
Related manuals
Manual 32 pages 49.67 Kb