GAS SUPPLY CONNECTIONS

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut off valve located outside the heater jacket. All gas piping should be tested after installation in accordance with local codes.

MANUAL

SHUT OFF VALVE

GAS INLET

HEATER JACKET

SEDIMENT

GAS

TRAP

UNION VALVE

Fig. #8090.0

CAUTION: the heater and its manual shut off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 Psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY. The heater and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. Do NOT use open flame.

NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant is recommended.

A minimum of 7” W.C. and a maximum of 14” W.C. upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 12” W.C. and a maximum of 14” for propane gas.

GASPRESSUREREGULATOR

The gas pressure regulator is preset and sealed at 4” W.C. for natural gas, and 11” W.C. for propane gas. Between the gas valve and the burners is a 1/8” pipe plug. The pressure at this point, taken with a manometer, should be about 3.7” W.C. natural gas and 10.5” W.C. propane gas. If an adjustment is needed, remove seal

and turn adjustment screw clockwiseto in- crease pressure or counter clockwise

to decrease pressure

GAS PRESSURE

MANOMETER

TEST UPSTREAM

 

MANUAL

SHUT-OFF

VALVE

GAS PRESSURE TEST

AT GAS VALVE

GAS PRESSURE TEST

AT HEATER

Fig. # 8149.0

11

Image 11
Contents What to do if YOU Smell GAS Installation Operating Instructions CommercialWaterchemistry Contents Water START-UP Procedures Before START-UPFor Your Safety Read Before Operating BurnersTo Turn OFF GAS to Appliance Operating InstructionsVisual Inspection Maintenance and Care ProceduresWater Pressure Switch After START-UPImportant Notice Basic Tips if Heater will not FirePool & SPA Water Chemistry California Proposition 65 WarningClearances Base InstallationVent Piping Indoor HeaterStep #2 Venting ConnectionsAnsi Z Gaspressureregulator GAS Supply ConnectionsCompanionflangeconnections Pipe Sizing for GAS ConnectionsPlumbing for Water Connections Location Flow Rates Model Pipe Size MIN. GPM MAX. GPMUnithermgovernoroperation Pressure Relief Valve InstallationAuxiliary Bypass Valve Adjustmentinlet AUTOMATICCHLORINATORSANDCHEMICALFEED- ERSS8600 Ignition Control Electrical WiringPage 151965 152141 152142 Servicing Insructions CONTROLS/ADJUSTMENTS/REPLACEMENTSTypical Comfortable SPA Temperature Range KnobstopadjustmentPilot Safety Pressure SwitchPressure Switch Adjustment Pressure Switch Adjustment RangeRaypak Tube Cleaning KIT Combustionchamberremoval DesootingprocedureUNITHERMGOVERNORU.G.REPLACEMENT Important Notice Liming Highvoltage Troubleshooting Honeywell S8600Electrical Raypak, Inc Agoura Road Westlake Village, CA Replacement Parts ListThis page is empty Pilot ASSEMBLY- Electronic Ignition Page Page
Related manuals
Manual 32 pages 49.67 Kb

514-824 specifications

The Raypak 514-824 is a leading model in the realm of heating solutions, specifically designed for outdoor residential and commercial applications. Known for its efficiency and durability, the Raypak 514-824 has gained popularity among users looking for reliable heating systems.

One of the standout features of the Raypak 514-824 is its advanced design that incorporates high-quality materials ensuring longevity. This model is constructed with a robust heat exchanger, typically made of copper or bronze, which promotes better thermal conductivity while resisting corrosion. This ensures that the unit maintains a high performance level even after prolonged use, making it an excellent choice for areas with varying weather conditions.

The technological aspects of the Raypak 514-824 are also impressive. It is equipped with an intuitive digital control system that allows for precise temperature adjustments. Users can easily set their desired temperature, which is maintained automatically, providing comfort with minimal manual control. The digital display is user-friendly, making it simple to monitor system performance and adjust settings as needed.

Efficiency is a critical characteristic of the Raypak 514-824. With a focus on energy-saving capabilities, this heater exceeds industry standards, often achieving efficiency ratings that minimize energy consumption. This not only results in cost savings on utility bills but also contributes to environmental sustainability, making it a more responsible choice for heating needs.

Safety features are paramount in the design of the Raypak 514-824. It includes various protections such as high-limit switches and pressure regulators that help prevent overheating and maintain optimal operating conditions. These safety measures ensure that the unit operates reliably and minimizes risks associated with traditional heating systems.

Furthermore, installation versatility sets the Raypak 514-824 apart. It is designed for straightforward installation, suitable for various setups whether it's integrated with a swimming pool or spa heating system. This adaptability makes it an ideal selection for anyone looking to enhance their outdoor space with effective heating solutions.

In summary, the Raypak 514-824 is a high-performing, efficient, and versatile heating model that combines modern technology with significant safety features. Its emphasis on user-friendly operation and long-lasting materials makes it a top contender in the heating market, catering to both residential and commercial applications. The Raypak 514-824 exemplifies a commitment to quality, efficiency, and reliability.