At the time of removal of an existing heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain- ing connected to the common venting system are not in operation.

(a)Seal any unused openings in the common venting system.

(b)Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

(c)Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com- mon venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

(d)Place in operation the appliance being inspected. Follow the lighting instructions. Adjust tankstat so appliance will operate continuously.

(e)Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe to visually check spillage.

(f)After it has been determined that each appliance remaining connected to the common venting sys- tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

(g)Any improper operation of the common venting system should be corrected so the installation conforms with the latest edition of the National Fuel Gas Code, ANSI Z 223.1. When resizing any portion of the common venting system, the com- mon venting system should be resized to approach the minimum size as determined using the appropriate tables in Chapter 10 and in Appendix G of the National Fuel Gas Code, ANSI Z 223.1 and CAN/CGA - B149.1 -B149.2.

GAS SUPPLY CONNECTIONS

The inlet gas connection of the heater gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to the chart below:

Maximum Equivalent Pipe Length (Feet)

 

 

1/2" Pipe

3/4" Pipe

1" Pipe

1-1/4" Pipe

MODEL

NAT

PROP

NAT

PROP

NAT

PROP

NAT

PROP

0090

 

30

80

125

300

400

-

-

-

0135

 

15

40

60

150

200

500

-

 

0195

 

-

20

35

70

100

250

400

-

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shutoff valve located outside the jacket. All gas piping should be tested after installation in accordance with local codes.

ManualUnion

Valve

Sediment Trap

Gas Valve

 

Fig. # 8192.0

CAUTION: The heater and its manual shut off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/ 2 psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COV- ERED BY WARRANTY. The heater and its gas connec- tions shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame.

NOTE: Do not use teflon tape on gas line pipe thread.

Aflexible sealant suitable for use with Natural and Propane gases is recommended.

NOTE: These boilers are also certified to operate on Propane gas, when equipped with the combination gas valve and orifices (pilot and main burners) sized for Propane gas.

GASPRESSURE-SPECIFICATIONS

 

Inches

W.C.

Regulator

 

Min.

Max.

Setting

Natural

4.5

10.5

3.5

Propane

12.0

13.0

11.0

Note: Do not exceed maximum inlet gas pressure. The minimum value shown is for input adjustment.

9

Image 9
Contents For Your Safety Installation Operating InstructionsContents General Specifications Specifications and DimensionsReceiving Equipment General Safety Precautions General Safety Precautions Coderequirements Installation ProceduresMountingbase ClearancerequirementsAnsi Z VentingconnectionsFig.# Common VentsGAS Supply Connections GASPRESSURE-SPECIFICATIONSRelief Valve Water Connections & System PipingFig.# Electrical WiringWiring Diagram Standing Pilot Wiring Diagram Intermittent Ignition Device IIDModels 90, 135 Servicing Procedures General Location of ControlsSequence of Operation START-UPPROCEDURES Filling the SystemChecking the Circulator For Automatic Ignition Models Lighting the Heater For Standing Pilot ModelsTo Turn OFF GAS to Heater For Honeywell ValveFor Robertshaw Valve Inspectionprocedures Burners For Automatic Ignition SystemsFlamefailure Burnerdrawerremoval Raypak Tube Cleaning KITMain Burner and Orifice Removal RepairsectionHeat Exchanger RE-ASSEMBLY Important Notice Trouble Shooting Guide3Pilot Outage Too low or too high gas pressures ADJUSTMENTS/REPLACEMENTSOF Components Replacement Parts List RAYPAK, INCEastman Avenue Oxnard, CA Fig. # Page Page Limitedpartswarrantyeconopakwaterheaters

090A, 135A, 195A specifications

Raypak, a leading manufacturer in the pool and spa heating industry, presents its advanced line of heaters, specifically the Raypak 195A, 090A, and 135A models. These heaters are renowned for their high performance, durability, and energy efficiency, making them ideal for a variety of applications, including residential and commercial pools and spas.

The Raypak 195A heater stands out with its powerful heating capacity, which is designed to quickly raise water temperatures, ensuring comfortable swimming conditions even in cooler climates. Its compact design allows for easy installation in tight spaces, and it operates quietly, enhancing the user experience. The 090A, meanwhile, is exceptional for smaller pools or spas, delivering reliable heating performance with energy-saving features. This model is particularly popular among homeowners looking to maintain a comfortable temperature without inflating their energy bills.

In contrast, the 135A model offers an impressive balance of power and efficiency, making it suitable for medium-sized pools. It incorporates advanced technologies to minimize energy consumption while maximizing output, allowing users to enjoy their pools while being environmentally conscious.

All three models boast Raypak's innovative digital control system, which provides precise temperature management and easy programming. Users can easily set desired temperatures and schedules, minimizing manual adjustments and enhancing convenience. The built-in diagnostic capabilities alert users to any potential maintenance needs, assuring long-term reliability and performance.

Furthermore, the heaters utilize a copper heat exchanger, known for its exceptional thermal conductivity, which ensures rapid heating and corrosion resistance. The specially designed rust-resistant cabinet protects the internal components from the elements, prolonging the lifespan of the heaters.

In addition to their robust features, these Raypak models are designed for easy maintenance. The streamlined layouts make it simple for service technicians to access vital components, reducing downtime and ensuring efficiency when repairs are necessary.

With their combination of advanced technology, energy efficiency, and user-friendly features, the Raypak 195A, 090A, and 135A models stand as top choices for pool and spa heating solutions. Their reliability and performance make them a valuable addition to any backyard oasis, allowing users to enjoy warm water year-round, regardless of the climate.