Raypak 302-902 manual Section C Combustion and Ventilation AIR, Direct VENT-INSTALLATON

Page 11

SECTION C: COMBUSTION AND VENTILATION AIR

COMBUSTION AND VENTILATION AIR (Indoor Units)

The boiler must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be supplied via conventional venting, where combustion air is drawn from the area immedi- ately surrounding the boiler, or via direct vent, where combustion air is drawn directly from outside. All installations must comply with the requirements of NFGC for U.S., CAN/CGA B 149.1 and .2 for Canada, and all local codes.

CAUTION:

NOTICE:

Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler and void the warranty. See appendix A.

It is recommended that the intake vent be insulated to minimize sweating.

DIRECT VENT-INSTALLATON

If outside air is drawn through the intake pipe directly to the unit for combustion:

1.Install combustion air direct vent in accordance with Section J-3 and Section J-4 of this manual.

2.Provide adequate ventilation.

3.In cold climates, and to mitigate potential freeze-up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circulation of cold air through the boiler during the non-operating hours.

CONVENTIONAL COMBUSTION AIR SUPPLY (FOR U.S. INSTALLATION ONLY)

(a)All Air from Inside the Building. The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour (22 cm2 per kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (30 cm) of the top, and one opening shall commence within 12 inches (30 cm) of the bottom, of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (8 cm).

(b)All Air from Outdoors. The confined space shall communicate with the outdoors in accordance with methods 1 or 2. The minimum dimension of air openings shall not be less than 3 in. (8cm). Where ducts are used, they shall be of the same cross- sectional area as the free area of the openings to which they connect.

1.Two permanent openings, one commencing within 12in. (30cm) of the top, and one commencing within 12in. (30cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

a. Where directly communicating with the outdoors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 sq in. per 4000 Btu per hr (5.5cm2 per kW) of total input rating of all equipment in the enclosure.

b. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 sq in. per 2000 Btu per hr (11 cm2 per kW) of total input rating of all equipment in the enclosure.

2.One permanent opening, commencing within 12 in. (30cm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16cm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:

a. 1 sq in. per 3000 Btu per hr (7 cm2 per kW) of the total input rating of all equipment located in the enclosure, and b. Not less than the sum of the areas of all vent connectors in the confined space.

WARNING:

Do not use one permanent opening method if the equipment room is under negative pressure condition or the equipment is common vented with other gas-fired appliances.

11

Image 11
Contents Installation Operating Instructions Table of Contents Page Section a Before Installing the Boiler Model Identification High Delta Component Location General Information Stacking Equipment BaseBoiler Side 302-902 Boiler SizeOutdoor Installation Minimum Clearances OutdoorinstallationsCombustion and Ventilation AIR Indoor Units Direct VENT-INSTALLATONSection C Combustion and Ventilation AIR Page Reliefvalve Piping LOW Temperature SystemTemperature & Pressure Gauge Section D Water Piping GeneralSection E Hydronic Heating Piping Fig. #9223 DUALBOILERPRIMARY/SECONDARYPIPINGSingle Domestic HOT Water Heater with ONE Storage Tank Section F Domestic HOT Water PipingPotable Water and Space Heatingapplication Bypass Section G Pool HeatingSpawater Chemistry Singlepoolheaterapplication Automatic Chlorinators and ChemicalfeedersWinterizingyour Heater GAS Supply Pressure Section H GAS Supply ConnectionsGAS Supply Connection GAS Pressure Regulator FIELD-CONNECTEDCONTROLLERS Section I Electrical Power ConnectionsCheck the Power Source Check Power SourceMaking the Electrical Connections Field Wiring ConnectionShockhazard Electrical Connections Domestic HOT WaterDefinition ofAppliance Categories Section J Venting ConnectionsTable J-1 Vent Terminal Location General Support of Vent StackVenting Configurations Venting Installation TipsNatural Draft Verticalvent Section J-1 Natural Draft Vertical Venting CategoryNatural Draft Vertical Vent Termination Natural Draft Vertical Venting System InstallationPage HORIZONTALTHRU-WALLVENTING Category III Table Section J-2Fig. #9436 HI Delta Sleeve Flue ConversionHorizontal Thru-wall Direct Vent Termination HORIZONTALTHRU-WALLVENTING Table Section J-3 Direct VentHorizontal Thru-wall Direct Vent Termination Verticalventing Table Direct VentVertical Direct Vent Termination Vertical Direct Vent System InstallationHideltaoutdoorventkitandinstructions Section J-5Heater as shipped HI Delta Outdoor Vent InstructionsFinished assembly HI Delta Filter BOX Instructions HI Delta Filter BOX KITThiskitincludes Model Partnumber Filter Section K Controls HI-DELTAModel Boiler Sequence of OperationsHI-DELTAModel HI-DELTAModel902 Operating Control High Limit Manual ResetFlow Switch Ignition Control ModuleLOW Water CUT OFF Optional LOW Water Cutoff High and LOW GAS Pressure SwitchesGAS Pressure Switch Wire Diagram Model Reference Drawing Number M152470-Rev. J H3/W3 Reference Drawing Number M152464-Rev R H3/HW3 Reference Drawing Number M152465 Rev-P H3/W3 TIME/TEMPERATURE Relationships in Scalds Section L General Safety PrecautionsSection M PRE-START-UP Turn Off Main Gas Valve Section N HI-DELTA Initial START-UPTools Needed Preparation for START-UPYour Hi-Delta is tuned START-UPPilot Turn Down Test for Raypak HI Delta Boilers Leak Test Procedure DUAL-SEAT GAS ValvesPage Section O Post START-UP Check Toturn Offgastoappliance Section P OperationSuggested Minimum Maintenance Schedule Section Q MaintenanceAnnually Preventive Maintenance ScheduleWeekly Semi-AnnuallyInsidecombustionaircontamination Appendix aCorporate Headquarters

302-902 specifications

The Raypak 302-902 is a highly efficient, reliable, and versatile heating solution commonly used in residential and commercial pool heating applications. Known for its exceptional performance and advanced technology, the Raypak 302-902 has become a favored choice among pool owners looking to extend their swimming season and enhance comfort.

One of the main features of the Raypak 302-902 is its robust construction. Built with a copper heat exchanger, it is designed to withstand the rigors of continuous use while offering superior heat transfer capabilities. The heat exchanger is also designed for easy maintenance, enabling pool owners to keep their systems running efficiently for years.

The Raypak 302-902 employs advanced digital controls, which provide precise temperature regulation. This modern control system allows users to set their desired water temperature with accuracy and maintain it consistently, ensuring a pleasant swimming experience. Additionally, these digital controls feature self-diagnostic capabilities, alerting users to potential issues, which aids in quick troubleshooting and maintenance.

In terms of energy efficiency, the Raypak 302-902 stands out with its ability to harness energy effectively, leading to significant savings in operational costs. It is equipped with an efficient gas burner, which optimizes fuel consumption while delivering rapid heating performance. This efficiency is complemented by its ability to operate with natural gas or propane, making it adaptable to various setups and preferences.

The unit also prides itself on its environmentally friendly operation. It meets stringent regulations for emissions, ensuring that pool owners can enjoy a pool heating solution that is both effective and reduces its ecological footprint. This focus on sustainability has made it a popular choice among environmentally conscious consumers.

Moreover, the Raypak 302-902 is designed for versatility. It can be easily integrated with existing pool systems and is compatible with both in-ground and above-ground pools. This flexibility allows it to cater to a wide range of pool sizes and configurations, making it suitable for both residential and commercial applications.

In conclusion, the Raypak 302-902 offers an array of features, technologies, and characteristics that make it a top contender in the pool heating market. With its durable construction, advanced digital controls, energy efficiency, and environmentally friendly operation, it remains a reliable choice for those seeking comfort and convenience in their swimming experience. Whether for a backyard oasis or a commercial facility, the Raypak 302-902 delivers consistent performance and accessibility.