SECTION E: HYDRONIC HEATING PIPING

PUMP SELECTION

In order to insure proper performance of your boiler system, you must install a properly sized pump. Raypak recommends using a 20°F Delta T as design Delta T. (Delta T is the temperature difference between the inlet and outlet water when the boiler is firing at full rate). If a Delta T larger than 20°F is necessary, see Table D-1 for minimum flow rate requirements.

PRESSURE DROP IN FEET OF HEAD

FEEDWATER REGULATOR

Raypak recommends that a feedwater regulator be installed and set at 12 PSIG minimum pressure at the highest point of system. Install a check valve or back flow device upstream of the regulator, with a manual shut off valve as required by local codes.

PIPING - HEATING BOILERS

All high points should be vented. Purge valves and a bypass valve should be installed. A boiler installed above radiation level must be provided with a low water cutoff device. The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.

The boiler piping system of a hot water heating boiler connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. It is highly recommended that the piping be insulated.

AIR-SEPARATION/EXPANSION TANK

All boilers should be equipped with a properly sized expansion tank and air separator fitting as shown in the following diagrams.

THREE-WAY VALVES

Valves designed to blend water temperatures or reduce water circulation through the boiler should not be used. Raypak heaters are high recovery low mass heaters not subject to thermal shock. Raypak offers a full line of electric sequencers that produce direct reset of boiler water temperature. Refer to the Controls Section in our Complete Catalog.

Table E-1

NOTE: Basis for Minimum flow -20 gpm or 40° DT

Maximum flow -90 gpm.

Flow switch will not operate if flow is less than 20 gpm.

14

Image 14
Contents Installation Operating Instructions Table of Contents Page Section a Before Installing the Boiler Model Identification High Delta Component Location General Information Equipment Base StackingBoiler Size Boiler Side 302-902Outdoorinstallations Outdoor Installation Minimum ClearancesCombustion and Ventilation AIR Indoor Units Direct VENT-INSTALLATONSection C Combustion and Ventilation AIR Page Section D Water Piping General LOW Temperature SystemTemperature & Pressure Gauge Reliefvalve PipingSection E Hydronic Heating Piping DUALBOILERPRIMARY/SECONDARYPIPING Fig. #9223Single Domestic HOT Water Heater with ONE Storage Tank Section F Domestic HOT Water PipingPotable Water and Space Heatingapplication Section G Pool Heating BypassSpawater Chemistry Singlepoolheaterapplication Automatic Chlorinators and ChemicalfeedersWinterizingyour Heater GAS Supply Pressure Section H GAS Supply ConnectionsGAS Supply Connection GAS Pressure Regulator Check Power Source Section I Electrical Power ConnectionsCheck the Power Source FIELD-CONNECTEDCONTROLLERSField Wiring Connection Making the Electrical ConnectionsElectrical Connections Domestic HOT Water ShockhazardSection J Venting Connections Definition ofAppliance CategoriesTable J-1 Support of Vent Stack Vent Terminal Location GeneralVenting Installation Tips Venting ConfigurationsSection J-1 Natural Draft Vertical Venting Category Natural Draft VerticalventNatural Draft Vertical Venting System Installation Natural Draft Vertical Vent TerminationPage Section J-2 HORIZONTALTHRU-WALLVENTING Category III TableHI Delta Sleeve Flue Conversion Fig. #9436Horizontal Thru-wall Direct Vent Termination Section J-3 Direct Vent HORIZONTALTHRU-WALLVENTING TableHorizontal Thru-wall Direct Vent Termination Direct Vent Verticalventing TableVertical Direct Vent System Installation Vertical Direct Vent TerminationSection J-5 HideltaoutdoorventkitandinstructionsHI Delta Outdoor Vent Instructions Heater as shippedFinished assembly HI Delta Filter BOX Instructions HI Delta Filter BOX KITThiskitincludes Model Partnumber Filter Section K Controls Boiler Sequence of Operations HI-DELTAModelHI-DELTAModel HI-DELTAModel902 Ignition Control Module High Limit Manual ResetFlow Switch Operating ControlLOW Water CUT OFF Optional LOW Water Cutoff High and LOW GAS Pressure SwitchesGAS Pressure Switch Wire Diagram Model Reference Drawing Number M152470-Rev. J H3/W3 Reference Drawing Number M152464-Rev R H3/HW3 Reference Drawing Number M152465 Rev-P H3/W3 Section L General Safety Precautions TIME/TEMPERATURE Relationships in ScaldsSection M PRE-START-UP Preparation for START-UP Section N HI-DELTA Initial START-UPTools Needed Turn Off Main Gas ValveSTART-UP Your Hi-Delta is tunedLeak Test Procedure DUAL-SEAT GAS Valves Pilot Turn Down Test for Raypak HI Delta BoilersPage Section O Post START-UP Check Section P Operation Toturn OffgastoapplianceSection Q Maintenance Suggested Minimum Maintenance ScheduleSemi-Annually Preventive Maintenance ScheduleWeekly AnnuallyAppendix a InsidecombustionaircontaminationCorporate Headquarters

302-902 specifications

The Raypak 302-902 is a highly efficient, reliable, and versatile heating solution commonly used in residential and commercial pool heating applications. Known for its exceptional performance and advanced technology, the Raypak 302-902 has become a favored choice among pool owners looking to extend their swimming season and enhance comfort.

One of the main features of the Raypak 302-902 is its robust construction. Built with a copper heat exchanger, it is designed to withstand the rigors of continuous use while offering superior heat transfer capabilities. The heat exchanger is also designed for easy maintenance, enabling pool owners to keep their systems running efficiently for years.

The Raypak 302-902 employs advanced digital controls, which provide precise temperature regulation. This modern control system allows users to set their desired water temperature with accuracy and maintain it consistently, ensuring a pleasant swimming experience. Additionally, these digital controls feature self-diagnostic capabilities, alerting users to potential issues, which aids in quick troubleshooting and maintenance.

In terms of energy efficiency, the Raypak 302-902 stands out with its ability to harness energy effectively, leading to significant savings in operational costs. It is equipped with an efficient gas burner, which optimizes fuel consumption while delivering rapid heating performance. This efficiency is complemented by its ability to operate with natural gas or propane, making it adaptable to various setups and preferences.

The unit also prides itself on its environmentally friendly operation. It meets stringent regulations for emissions, ensuring that pool owners can enjoy a pool heating solution that is both effective and reduces its ecological footprint. This focus on sustainability has made it a popular choice among environmentally conscious consumers.

Moreover, the Raypak 302-902 is designed for versatility. It can be easily integrated with existing pool systems and is compatible with both in-ground and above-ground pools. This flexibility allows it to cater to a wide range of pool sizes and configurations, making it suitable for both residential and commercial applications.

In conclusion, the Raypak 302-902 offers an array of features, technologies, and characteristics that make it a top contender in the pool heating market. With its durable construction, advanced digital controls, energy efficiency, and environmentally friendly operation, it remains a reliable choice for those seeking comfort and convenience in their swimming experience. Whether for a backyard oasis or a commercial facility, the Raypak 302-902 delivers consistent performance and accessibility.