Model

1/2 in. Pipe

3/4 in. Pipe

1 in. Pipe

1 1/4 in. Pipe

No.

Nat.

Pro.

Nat.

Pro.

Nat.

Pro.

Nat.

Pro.

 

 

 

 

 

 

 

 

 

 

0042

125

350

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0066

60

160

175

460

 

 

 

 

 

 

 

 

 

 

 

 

 

0090

30

80

125

300

400

 

 

 

 

 

 

 

 

 

 

 

 

0135

15

40

60

150

200

450

 

 

 

 

 

 

 

 

 

 

 

0180

 

20

35

90

115

300

425

 

 

 

 

 

 

 

 

 

 

Table H: Maximum Equivalent Pipe Length (Feet)

Gas Supply Connections

The inlet gas connection of the boiler gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to Table H above.

Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shut-off valve locat- ed outside the jacket. All gas piping should be tested after installation in accordance with local codes.

NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant suitable for use with Natural and Propane gases is recommended.

These boilers are also certified to operate on propane gas, when equipped with the combination gas valve and orifices (pilot and main burners) sized for propane gas.

Gas Pressure

ManualUnion

Valve

Sediment Trap

Gas Valve

Must be Supplied by Installer

Fig. 14: Sediment Trap

CAUTION: The boiler and its manual shut-off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45 kPa). Dissipate test pressure in the gas supply line before reconnecting the boiler and its manual shut-off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY. The boiler and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame.

The gas valve is provided with pressure taps to meas- ure gas pressure upstream of the gas valve and downstream which is the same as the manifold pres- sure.

Gas Type

Inches

Inches

Regulator

WC Min.

WC Max.

Setting

 

 

 

 

 

Natural

7.0

10.5

3.5

 

 

 

 

Propane

12.0

13.0

11.0

 

 

 

 

Table I: Minimum and Maximum Gas Pressure

Water Connections & System Piping

The pipe size for water connections is shown on page

6.Typical piping systems are shown on pages 17 to

This boiler is supplied with a circulator and built-in bypass as standard to ensure the required minimum water flow in the boiler. The bypass on models H-0135 and H-0180 is provided with an adjustable valve that is factory-set in the full open position. The handle is

15

Image 15
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms Receiving Equipment General SpecificationsHeating Net Piping Connections Input CapacityRating Gas NPT Clearance Requirements InstallationCode Requirements Mounting BaseModel No Sq. in. of Free Area Combustion/Ventilation AirVenting Connections Vent Max Model No Connector Horizontal Diameter Length ftRoof Pitch X/12 Min. ft Common VentsVent Damper Location Vent Damper Installation LocationVent Damper Operation MountingAbbreviation Description Flair DamperVent Damper Gas Supply Connections Gas PressureWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Single-Zone Piping Piping DiagramsElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Intermittent Ignition Device IID Servicing ProceduresSequence Operation General Location of ControlsFilling the System START-UP ProceduresLighting the Boiler For Standing Pilot ModelsFor Automatic Ignition Models To Turn Off Gas to the Boiler Models 90, 135For Honeywell valve Shut-down ProcedureTo Turn Off Gas to the Boiler For Honeywell valve Turn gas control knobSafe Shut-down Tests Testing the Ignition Safety Shut-offBurners Inspection ProceduresLow Water Cut-Off When Installed Procedure for Cleaning Flue Gas PassagewaysBurner Tray Removal Repair ProceduresTube Cleaning Procedure Typical Heat Exchanger RemovalCombustion Chamber Removal Heat Exchanger Re-assemblyCauses TroubleshootingPiping Adjustment & Replacement of Components Circulator Replacement Replacement Parts ListFast-Response Temperature Sensor Module Replacement Fast-Response Temperature Sensor Probe ReplacementLimited Parts Warranty

0180B Type H specifications

The Raypak 0180B Type H is a standout model in the realm of heating solutions, offering a unique blend of efficiency and reliability for both residential and commercial applications. Known for its robust design and advanced technologies, the 0180B Type H is specifically engineered to provide exceptional performance while ensuring energy savings.

One of the key features of the Raypak 0180B Type H is its compact design, which makes it ideal for installation in tight spaces without sacrificing performance. The unit incorporates a patented heat exchanger that enhances thermal efficiency, ensuring that a higher percentage of energy is converted into usable heat. This design not only maximizes performance but also minimizes waste, contributing to lower operating costs and reduced environmental impact.

Equipped with Raypak's state-of-the-art digital control system, the 0180B Type H provides precise temperature regulation and monitoring. Users can easily set desired temperature parameters, while the system automatically adjusts to maintain optimal heating levels. This technology not only enhances user convenience but also ensures that the system operates at peak efficiency, further extending the lifespan of the unit.

The 0180B Type H features a durable construction that includes corrosion-resistant materials, ensuring longevity even in challenging environments. Its design is tailored to withstand extreme weather conditions, making it a reliable choice for various applications, including pool heating, spa heating, and process heating. Additionally, the unit is equipped with advanced safety features, such as built-in pressure relief valves and automatic shut-off mechanisms, providing peace of mind for users.

Another notable characteristic of the Raypak 0180B Type H is its compatibility with alternative energy sources. The unit can be easily integrated with solar heating systems, enhancing energy efficiency and sustainability. This flexibility makes it an attractive option for eco-conscious consumers looking to reduce their carbon footprint.

In summary, the Raypak 0180B Type H combines advanced technology with a user-friendly interface, robust construction, and energy-efficient design. Its unique features cater to a variety of heating needs, establishing it as a premier choice for individuals and businesses alike. Whether for residential or commercial use, the 0180B Type H is designed to deliver consistent, reliable heating solutions that stand the test of time.