Raypak 0180B Type H manual Troubleshooting, Causes

Page 34

TROUBLESHOOTING

These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service per- sonnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these instructions.

PROBLEM

1)When room thermostat is turned on, boiler does not operate.

CAUSES

1)No power to the boiler.

2)Defective room thermostat or discon- nected wire in thermostat circuit.

3)Defective transformer.

4)Defective pump relay.

5)Defective pump.

SOLUTIONS

1)Check circuit breakers, disconnect switch. Make sure power is on.

2)Check continuity on thermostat and wiring circuit. Replace thermostat, or repair wiring connections.

3)Check secondary voltage. If no 24V, replace transformer.

4)Check relay coil or contacts. Replace as required.

5)Replace pump.

2)When room thermostat is calling for heat, pump is on, but burners will not turn on.

1)For standing pilot models, pilot burner not lighted.

2)If pilot burner will not stay lighted, thermocouple or gas valve may be defective.

3)Gas knob in "Pilot" position. 4)For automatic ignition models,

gas valve knob is in "OFF" position.

5)Vent switch is open.

6)Roll-out switch is open.

7)High limit is open.

8)Fast Response Temperature Sensor probe is defective.

9)Fast Response Temperature sensor board is defective.

1)Light pilot burner. (Follow lighting instructions on rating plate.)

2)Check thermocouple MV generation. If less than 25MV (open circuit), re- place thermocouple. If between 25- 35 MV, replace gas valve.

3)Turn knob to "ON" position. 4)Turn gas knob to "ON". If ignition

module locks out, reset by interrupt- ing power to boiler.

5)Check for blockage of venting system or disconnected vent piping. After problem is corrected push button to reset, or replace single-use type vent

switch.

6)Check for blockage of flue or sooted heat exchanger. After problem is corrected push button to reset or re- place single use type roll-out switch. 7)Setting may be too low. Check water flow and adjust setting to obtain 20-

30°F temperature rise.

8)Red LED on circuit board will be ON to indicate a loose sensor connection or a shorted sensor. Check terminal connectors or replace sensor as re- quired.

NOTE: Red LED will also be ON if sensor temperature exceeds 300°F or drops below - 20°F. It will turn OFF when sensor temperature returns to the proper range. Yellow LED will be ON if temperature exceeds 240°F. It will turn off when sensor temperature falls below 180°F. When either Red or Yel- low LED is ON, boiler will be shut down. 9)Check voltage across output and

common terminals. If no 24V is pres- ent, replace board.

34

Image 34
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms General Specifications Receiving EquipmentInput Capacity Heating Net Piping ConnectionsRating Gas NPT Mounting Base InstallationCode Requirements Clearance RequirementsCombustion/Ventilation Air Model No Sq. in. of Free AreaVent Max Model No Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper Abbreviation DescriptionVent Damper Gas Pressure Gas Supply ConnectionsWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device General Location of Controls Servicing ProceduresSequence Operation Intermittent Ignition Device IIDFor Standing Pilot Models START-UP ProceduresLighting the Boiler Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsFor Honeywell valve Turn gas control knob Shut-down ProcedureTo Turn Off Gas to the Boiler For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsProcedure for Cleaning Flue Gas Passageways Inspection ProceduresLow Water Cut-Off When Installed BurnersHeat Exchanger Removal Repair ProceduresTube Cleaning Procedure Typical Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting CausesPiping Adjustment & Replacement of Components Fast-Response Temperature Sensor Probe Replacement Replacement Parts ListFast-Response Temperature Sensor Module Replacement Circulator ReplacementLimited Parts Warranty

0180B Type H specifications

The Raypak 0180B Type H is a standout model in the realm of heating solutions, offering a unique blend of efficiency and reliability for both residential and commercial applications. Known for its robust design and advanced technologies, the 0180B Type H is specifically engineered to provide exceptional performance while ensuring energy savings.

One of the key features of the Raypak 0180B Type H is its compact design, which makes it ideal for installation in tight spaces without sacrificing performance. The unit incorporates a patented heat exchanger that enhances thermal efficiency, ensuring that a higher percentage of energy is converted into usable heat. This design not only maximizes performance but also minimizes waste, contributing to lower operating costs and reduced environmental impact.

Equipped with Raypak's state-of-the-art digital control system, the 0180B Type H provides precise temperature regulation and monitoring. Users can easily set desired temperature parameters, while the system automatically adjusts to maintain optimal heating levels. This technology not only enhances user convenience but also ensures that the system operates at peak efficiency, further extending the lifespan of the unit.

The 0180B Type H features a durable construction that includes corrosion-resistant materials, ensuring longevity even in challenging environments. Its design is tailored to withstand extreme weather conditions, making it a reliable choice for various applications, including pool heating, spa heating, and process heating. Additionally, the unit is equipped with advanced safety features, such as built-in pressure relief valves and automatic shut-off mechanisms, providing peace of mind for users.

Another notable characteristic of the Raypak 0180B Type H is its compatibility with alternative energy sources. The unit can be easily integrated with solar heating systems, enhancing energy efficiency and sustainability. This flexibility makes it an attractive option for eco-conscious consumers looking to reduce their carbon footprint.

In summary, the Raypak 0180B Type H combines advanced technology with a user-friendly interface, robust construction, and energy-efficient design. Its unique features cater to a variety of heating needs, establishing it as a premier choice for individuals and businesses alike. Whether for residential or commercial use, the 0180B Type H is designed to deliver consistent, reliable heating solutions that stand the test of time.