shipped loose. The full open position is appropriate for most systems, and ensures adequate flow through the boiler.

If system flow is inadequate, (indicated by excessive temperature drop through the system) the bypass valve can be throttled slightly. Care must be taken against over-throttling which may lead to inadequate flow through the boiler and boiler harmonics (a hum- ming sound from the heat exchanger).

If adequate system flow cannot be obtained without causing harmonics, an additional pump is required. The factory-mounted circulator will provide adequate water flow for systems designed at a 20°F temperature drop, and system pressure drop or head not exceed- ing that which is shown in Table J.

Model No.

System Flow

Max. System

(gpm)

Head (ft/WC)

 

 

 

 

H-0042

3.5

8.0

 

 

 

H-0066

5.3

8.5

 

 

 

H-0090

7.3

6.5

 

 

 

H-0135

11.0

10.0

 

 

 

H-0180

14.6

7.0

 

 

 

Table J: System Pressure Drop

When the total system head exceeds the available head pressures, a primary/secondary pumping system is recommended.

The minimum boiler operating temperature should be 105°F. When operating at low temperature applica- tions, ΔT (temperature rise) must be 20°F or less.

Propylene glycol solution is commonly used in the heating system when freeze protection is required. This will affect the system design and pump perform- ance. As a rule of thumb, 50% solution of propylene glycol will require the system flow (gpm) to increase by 14%, and the system head (ft/WC) by 23% in order to maintain the same heat transfer load.

Systems with multiple zones may require an addition- al circulator. Consult manufacturer's data for valve pressure drops. When an indirect water heating sys- tem is used, it is recommended that a separate circulator be installed to meet the required flow and pressure drop conditions of the indirect water heater.

We recommend that the make-up water from the cold water line have a check valve, gate valve, and feedwa- ter regulator set at 12 psi. Install unions and gate or ball valves at inlet and outlet connections at the boiler to facilitate servicing.

The pressure relief valve is mounted on the boiler and must be piped to a drain. We recommend that all high points be vented and that purge valves be installed. A boiler installed above radiation level must be provided with a low water cut-off device. See page 27 for wiring hook-up.

The boiler, when used in connection with a refrigera- tion system, must be installed so that the chilled medium is piped in parallel with the boiler with appro- priate valves to prevent the chilled medium from entering the boiler.

The boiler piping system of a hot water heating boiler, that is connected to heating coils located in air han- dling units where they may be exposed to refrigerated air circulation, must be equipped with flow control valves or other automatic means to prevent gravity cir- culation of the boiler water during the cooling cycle.

A diaphragm expansion tank should be installed in the return line. A typical 8"-diameter expansion tank can be used on models H-0042, and H-0066, and an 11"- diameter expansion tank can be used on models H-0090, H-0135 and H-0180. Consult tank manufac- turer for correct sizing.

16

Image 16
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms General Specifications Receiving EquipmentInput Capacity Heating Net Piping ConnectionsRating Gas NPT Installation Code RequirementsMounting Base Clearance RequirementsCombustion/Ventilation Air Model No Sq. in. of Free AreaVent Max Model No Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper Abbreviation DescriptionVent Damper Gas Pressure Gas Supply ConnectionsWater Connections & System Piping Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Servicing Procedures Sequence OperationGeneral Location of Controls Intermittent Ignition Device IIDSTART-UP Procedures Lighting the BoilerFor Standing Pilot Models Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsShut-down Procedure To Turn Off Gas to the BoilerFor Honeywell valve Turn gas control knob For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsInspection Procedures Low Water Cut-Off When InstalledProcedure for Cleaning Flue Gas Passageways BurnersRepair Procedures Tube Cleaning Procedure TypicalHeat Exchanger Removal Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting CausesPiping Adjustment & Replacement of Components Replacement Parts List Fast-Response Temperature Sensor Module ReplacementFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty

0180B Type H specifications

The Raypak 0180B Type H is a standout model in the realm of heating solutions, offering a unique blend of efficiency and reliability for both residential and commercial applications. Known for its robust design and advanced technologies, the 0180B Type H is specifically engineered to provide exceptional performance while ensuring energy savings.

One of the key features of the Raypak 0180B Type H is its compact design, which makes it ideal for installation in tight spaces without sacrificing performance. The unit incorporates a patented heat exchanger that enhances thermal efficiency, ensuring that a higher percentage of energy is converted into usable heat. This design not only maximizes performance but also minimizes waste, contributing to lower operating costs and reduced environmental impact.

Equipped with Raypak's state-of-the-art digital control system, the 0180B Type H provides precise temperature regulation and monitoring. Users can easily set desired temperature parameters, while the system automatically adjusts to maintain optimal heating levels. This technology not only enhances user convenience but also ensures that the system operates at peak efficiency, further extending the lifespan of the unit.

The 0180B Type H features a durable construction that includes corrosion-resistant materials, ensuring longevity even in challenging environments. Its design is tailored to withstand extreme weather conditions, making it a reliable choice for various applications, including pool heating, spa heating, and process heating. Additionally, the unit is equipped with advanced safety features, such as built-in pressure relief valves and automatic shut-off mechanisms, providing peace of mind for users.

Another notable characteristic of the Raypak 0180B Type H is its compatibility with alternative energy sources. The unit can be easily integrated with solar heating systems, enhancing energy efficiency and sustainability. This flexibility makes it an attractive option for eco-conscious consumers looking to reduce their carbon footprint.

In summary, the Raypak 0180B Type H combines advanced technology with a user-friendly interface, robust construction, and energy-efficient design. Its unique features cater to a variety of heating needs, establishing it as a premier choice for individuals and businesses alike. Whether for residential or commercial use, the 0180B Type H is designed to deliver consistent, reliable heating solutions that stand the test of time.