Raypak 0180B Type H manual Combustion/Ventilation Air, Model No Sq. in. of Free Area

Page 8

3.Except for carpeted flooring, boilers are certified for installation on combustible floors.

4.For un-insulated hot water pipes, maintain a 2" clearance, or consult local authority having juris- diction.

Combustion/Ventilation Air

WARNING: Air supply to the boiler room must not be affected by mechanical exhaust vents located in other parts of the house, such as kitchen or bathroom fans, or attic blowers. Mechanical exhaust vents may create a negative pressure condition in the boiler room that can become a hazard of asphyxiation, explosion or fire.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler. Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants, drycleaning fluids, degreasers, and paint removers. Other harmful elements may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive acid compounds when burned in a gas flame. The resulting acid condensate can damage or substantially reduce the life of the heater. It may be necessary to provide outside air directly to the heater in order to avoid this problem.

1.The boiler must be provided with adequate supply of air for proper combustion and ventilation in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provi- sions of the local building codes.

2.Models 0042 and 0066 only: When the boiler is installed in a confined space such as a utility room or closet where all air is supplied from inside the building, the boiler room must be provided with two openings, each one having a minimum net free area, in square inches as shown in Table C.

Model No.

Sq. in. of Free Area

 

 

0042

70

0066

 

 

 

 

Table C: Minimum Net Free Area

 

 

One opening shall be within 12" of the top, and the other opening within 12" of the floor. If additional gas appliances are installed in the same space, the total input of all gas appliances installed in the same space, must be considered in the calculation. Refer to Sec.

5.3.5of the latest edition of the National Fuel Gas Code for additional requirements.

Fig. 3: Location of Openings for

Combustion/Ventilation Air

NOTE: If louvers, grills or screens are used on the openings, obtain the net free area requirements from their supplier or manufacturer. If the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have 20-25 percent free area and metal louvers will have 60-75 percent free area as shown in Sec. 5.3.5 National Fuel Gas Code.

3.If the boiler room is located against an outside wall and air openings can communicate directly with the outdoors, the two openings on the outside wall must each have a net free area as shown in Table D.

Model No.

Sq. in. of Free Area

 

 

0042

12

 

 

0066

18

 

 

0090

24

 

 

0135

35

 

 

0180

45

 

 

Table D: Minimum Net Free Area

8

Image 8
Contents Raytherm Residential Boilers Page Contents Pay Attention to These Terms General Specifications Receiving EquipmentRating Gas NPT Heating Net Piping ConnectionsInput Capacity Installation Code RequirementsMounting Base Clearance RequirementsCombustion/Ventilation Air Model No Sq. in. of Free AreaVent Max Model No Connector Horizontal Diameter Length ft Venting ConnectionsCommon Vents Roof Pitch X/12 Min. ftVent Damper Installation Location Vent Damper LocationMounting Vent Damper OperationFlair Damper Abbreviation DescriptionVent Damper Water Connections & System Piping Gas Supply ConnectionsGas Pressure Model No System Flow Max. System Gpm Head ft/WC Piping Diagrams Single-Zone PipingElectrical Wiring Wiring Diagrams Page Page Single-Zone Taco Valve System with Three 3 Zone Pumps Primary/Secondary Pumping System Honeywell Zone Valve IID Units with Low Water Cut-off Device Servicing Procedures Sequence OperationGeneral Location of Controls Intermittent Ignition Device IIDSTART-UP Procedures Lighting the BoilerFor Standing Pilot Models Filling the SystemTo Turn Off Gas to the Boiler Models 90, 135 For Automatic Ignition ModelsShut-down Procedure To Turn Off Gas to the BoilerFor Honeywell valve Turn gas control knob For Honeywell valveTesting the Ignition Safety Shut-off Safe Shut-down TestsInspection Procedures Low Water Cut-Off When InstalledProcedure for Cleaning Flue Gas Passageways BurnersRepair Procedures Tube Cleaning Procedure TypicalHeat Exchanger Removal Burner Tray RemovalHeat Exchanger Re-assembly Combustion Chamber RemovalTroubleshooting CausesPiping Adjustment & Replacement of Components Replacement Parts List Fast-Response Temperature Sensor Module ReplacementFast-Response Temperature Sensor Probe Replacement Circulator ReplacementLimited Parts Warranty

0180B Type H specifications

The Raypak 0180B Type H is a standout model in the realm of heating solutions, offering a unique blend of efficiency and reliability for both residential and commercial applications. Known for its robust design and advanced technologies, the 0180B Type H is specifically engineered to provide exceptional performance while ensuring energy savings.

One of the key features of the Raypak 0180B Type H is its compact design, which makes it ideal for installation in tight spaces without sacrificing performance. The unit incorporates a patented heat exchanger that enhances thermal efficiency, ensuring that a higher percentage of energy is converted into usable heat. This design not only maximizes performance but also minimizes waste, contributing to lower operating costs and reduced environmental impact.

Equipped with Raypak's state-of-the-art digital control system, the 0180B Type H provides precise temperature regulation and monitoring. Users can easily set desired temperature parameters, while the system automatically adjusts to maintain optimal heating levels. This technology not only enhances user convenience but also ensures that the system operates at peak efficiency, further extending the lifespan of the unit.

The 0180B Type H features a durable construction that includes corrosion-resistant materials, ensuring longevity even in challenging environments. Its design is tailored to withstand extreme weather conditions, making it a reliable choice for various applications, including pool heating, spa heating, and process heating. Additionally, the unit is equipped with advanced safety features, such as built-in pressure relief valves and automatic shut-off mechanisms, providing peace of mind for users.

Another notable characteristic of the Raypak 0180B Type H is its compatibility with alternative energy sources. The unit can be easily integrated with solar heating systems, enhancing energy efficiency and sustainability. This flexibility makes it an attractive option for eco-conscious consumers looking to reduce their carbon footprint.

In summary, the Raypak 0180B Type H combines advanced technology with a user-friendly interface, robust construction, and energy-efficient design. Its unique features cater to a variety of heating needs, establishing it as a premier choice for individuals and businesses alike. Whether for residential or commercial use, the 0180B Type H is designed to deliver consistent, reliable heating solutions that stand the test of time.