Lennox International Inc 4HP18LT Installation, General, Torque Table, Inspection of Shipment

Page 2

INSTALLATION

General

Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation. Observe and follow all warnings, cautions, instructional labels, and tags. Failure to comply with these instructions could result in an unsafe condition and/or premature component failure.

These instructions are intended as a general guide only for use by qualified personnel and do not supersede any national or local codes in any way. The installation must comply with all provincial, state, and local codes as well as the National Electrical Code (U.S.) or Canadian Electrical Code (Canada). Compliance should be determined prior to installation.

4HP18LT condensing units use R410A which is an ozone- friendly HFC refrigerant. The unit must be installed with a matching indoor coil and line set. A filter drier approved for use with R410A is installed in the unit.

IMPORTANT: This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to confirm proper charge and airflow may reduce energy efficiency and shorten equipment life.

When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.

Torque Table

Fastener

Torque

 

 

Stem Caps

8 ft. lbs.

 

 

Service Port Caps

8 ft. lbs.

 

 

Sheet Metal Screws

16 in. lbs.

 

 

#8 Machine Screws

16 in. lbs.

 

 

#10 Machine Screws

28 in. lbs.

 

 

Compressor Bolts

90 in. lbs.

 

 

Table 1

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier immediately, preferably in writing, and should include a request for inspection by the carrier’s agent.

If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied.

Check the unit rating plate to confirm specifications are as ordered.

Location of Unit

Outdoor units operate under a wide range of weather conditions; therefore, multiple factors must be considered when positioning the unit. The unit must be positioned to give adequate clearances for sufficient airflow and servicing. Refer to Figure 1 for installation clearances.

Installation Clearances

36”

36” *36”

36” *

*A service clearance of 30" must be maintained on one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36". Clearance to one of the remaining two sides may be 12" and the final side may be 6".

A clearance of 24" must be maintained between units.

48" clearance required on top of unit. Maximum soffit overhang is 36".

Figure 1

Place a sound-absorbing material, such as Isomode under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings..

506470-01

Issue 1007

Page 2

Image 2
Contents Save these instructions for future reference Lennox International Inc. CompanyGeneral InstallationInstallation Clearances Torque TableSlab Mounting Electrical WiringSlab Mounting Roof MountingInstalling Refrigerant Line Refrigerant PipingLine Set Isolation PlacementOutside Unit Placement & Installation Refrigerant Line Set DiametersRefrigerant Line Sets Installing Horizontal Runs Refrigerant Line Sets Transition from Vertical to Horizontal Flushing Procedure Required EuipmentRefrigerant Metering Device Expansion Valve SystemsTo Access the Schrader Port To Close Liquid or Suction Line Service ValveUsing an Electronic Leak Detector EvacuationIssue Refrigerant Charging Refrigerant Charge AdjustmentSTART-UP Issue R410A Temperature/Pressure Chart Approach Values for TXV Systems Issue Operation Time Delay Defrost Control Timing PinsCompressor Delay Pressure Switch CircuitLED Description System Diagnostic ModuleInterpreting the Diagnostic LEDs 24VAC Power Wiring Thermostat Demand Wiring Miswired Module CodesMaintenance Homeowner Information Inspect and clean outdoor coilTemperature Setting Levers Temperature Indicator Fan SwitchSystem Switch Indicating LightStart-Up and Performance Checklist Wire Diagram Issue