Lennox International Inc 4HP18LT manual Refrigerant Line Sets Installing Horizontal Runs

Page 6

6.Braze the line set to the service valve. Quench the joints with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity.

7.Install the thermal expansion valve which is sold separately and which is approved for use with R410A refrigerant in the liquid line at the indoor coil (see Refrigerant Metering Device on page 9).

CAUTION

When flushing existing line set and/or indoor coil, be sure to empty all existing traps. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reducing system performance and capacity. Failure to properly flush system as explained in these instructions will void warranty.

Refrigerant Line Sets: Installing Horizontal Runs

To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.

8

Wire Tie

(around vapor line only)

Strapping Material

(around vapor line only)

Floor Joist or

Roof Rafter

Tape or Wire Tie

8

Strap the vapor line to the joist or rafter at 8intervals then strap the liquid line to the vapor line.

Metal Sleeve

Floor Joist or Roof Rafter

Tape or Wire Tie

Figure 6

506470-01

Issue 1007

Page 6

Image 6
Contents Save these instructions for future reference Lennox International Inc. CompanyGeneral InstallationInstallation Clearances Torque TableSlab Mounting Electrical WiringSlab Mounting Roof MountingInstalling Refrigerant Line Refrigerant PipingLine Set Isolation PlacementOutside Unit Placement & Installation Refrigerant Line Set DiametersRefrigerant Line Sets Installing Horizontal Runs Refrigerant Line Sets Transition from Vertical to Horizontal Flushing Procedure Required EuipmentRefrigerant Metering Device Expansion Valve SystemsTo Access the Schrader Port To Close Liquid or Suction Line Service ValveUsing an Electronic Leak Detector EvacuationIssue Refrigerant Charge Adjustment START-UPRefrigerant Charging Issue R410A Temperature/Pressure Chart Approach Values for TXV Systems Issue Operation Time Delay Defrost Control Timing PinsCompressor Delay Pressure Switch CircuitSystem Diagnostic Module Interpreting the Diagnostic LEDsLED Description 24VAC Power Wiring Thermostat Demand Wiring Miswired Module CodesMaintenance Inspect and clean outdoor coil Temperature Setting LeversHomeowner Information Temperature Indicator Fan SwitchSystem Switch Indicating LightStart-Up and Performance Checklist Wire Diagram Issue