Lennox International Inc 4HP18LT manual Required Euipment, Flushing Procedure

Page 8

Flushing Existing Line Set and Indoor Coil

This procedure should not be performed on systems which contain contaminants, such as compressor burn out.

Required Euipment

The following equipment is needed to flush the existing line set and indoor coil (See Figure 9). Two clean R-22 recovery bottles, an oil-less recovery machine with a “pump down” feature, and two sets of gauges (one for use with R-22 and one for use with R410A).

Flushing Procedure

IMPORTANT: The line set and/or indoor coil must be flushed with at least the same amount of refrigerant that previously charged the system. Check the charge in the flushing cylinder before flushing the unit.

1.Remove existing R-22 refrigerant using the appropriate procedure.

If the existing outdoor unit is not equipped with shutoff valves, or if the unit is not operational AND the existing R-22 refrigerant will be used to flush the system:

Disconnect all power to the existing outdoor unit. Connect the existing unit, a clean recovery cylinder, and the recovery machine according to the instructions provided with the recovery machine. Remove all R-22 refrigerant

from the existing system. Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and suction lines from the existing outdoor unit.

If the existing outdoor unit is equipped with manual shutoff valves AND new R-22 refrigerant will be used to flush the system:

Start the existing R-22 refrigerant system in cooling mode and close the liquid line valve. Pump all the existing R-22 refrigerant back into the outdoor unit.

(It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.)

When the low side system pressures reach 0 psig, close the suction line valve. Disconnect all power to the existing outdoor unit. Refer to the gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and suction lines from the existing outdoor unit.

2.Remove the existing outdoor unit. Set the new R410A unit and follow the brazing connection procedure outlined previously on this page to make line set connections. Do not install the R410A thermal expansion valve at this time.

3.Make low voltage and line voltage connections to the new outdoor unit. Do not turn on power to the unit or open the outdoor unit service valves at this time.

Flushing Connections

Figure 9

506470-01

Issue 1007

Page 8

Image 8
Contents Save these instructions for future reference Lennox International Inc. CompanyInstallation Installation ClearancesGeneral Torque TableElectrical Wiring Slab MountingSlab Mounting Roof MountingInstalling Refrigerant Line Refrigerant PipingPlacement Outside Unit Placement & InstallationLine Set Isolation Refrigerant Line Set DiametersRefrigerant Line Sets Installing Horizontal Runs Refrigerant Line Sets Transition from Vertical to Horizontal Flushing Procedure Required EuipmentRefrigerant Metering Device Expansion Valve SystemsTo Access the Schrader Port To Close Liquid or Suction Line Service ValveUsing an Electronic Leak Detector EvacuationIssue Refrigerant Charging Refrigerant Charge AdjustmentSTART-UP Issue R410A Temperature/Pressure Chart Approach Values for TXV Systems Issue Operation Defrost Control Timing Pins Compressor DelayTime Delay Pressure Switch CircuitLED Description System Diagnostic ModuleInterpreting the Diagnostic LEDs 24VAC Power Wiring Thermostat Demand Wiring Miswired Module CodesMaintenance Homeowner Information Inspect and clean outdoor coilTemperature Setting Levers Fan Switch System SwitchTemperature Indicator Indicating LightStart-Up and Performance Checklist Wire Diagram Issue