Defrost Control Timing Pins
Each timing pin selection provides a different accumulated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. The defrost timing jumper is factory installed to provide a 60 minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90 minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5 second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5 second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and reapplied.
Compressor Delay
The defrost board has a
NOTE: The
Time Delay
The
Pressure Switch Circuit
The defrost control includes two pressure switch circuits. A high pressure switch is connected to the board’s
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by an pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a
locked out until power to the board is interrupted, then re- established, or until the jumper is applied to the TEST pins for 0.5 seconds.
NOTE: The defrost control board ignores input from the low pressure switch terminals as follows:
•During the TEST mode
•During the defrost cycle
•During the 90 seconds
•For the first 90 seconds each time the reversing valve switches heat/cool modes
If the TEST pins are jumpered and the 5 minute delay is being bypassed, the
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition as shown in Table 9.
Defrost Control Board
Diagnostic LEDs
Table 9
Issue 1007 | Page 19 |