Johnson Controls R-410A manual Altitude/Temperature Correction Factors, Air Temperature ºF

Page 68

505430-BTG-A-0309

Altitude/Temperature Correction Factors

Air

 

 

 

 

 

Altitude (Ft.)

 

 

 

 

 

Temp.

0

1000

2000

3000

4000

 

5000

 

6000

7000

8000

9000

10000

40

1.060

1.022

0.986

0.950

0.916

 

0.882

 

0.849

0.818

0.788

0.758

0.729

50

1.039

1.002

0.966

0.931

0.898

 

0.864

 

0.832

0.802

0.772

0.743

0.715

60

1.019

0.982

0.948

0.913

0.880

 

0.848

 

0.816

0.787

0.757

0.729

0.701

70

1.000

0.964

0.930

0.896

0.864

 

0.832

 

0.801

0.772

0.743

0.715

0.688

80

0.982

0.947

0.913

0.880

0.848

 

0.817

 

0.787

0.758

0.730

0.702

0.676

90

0.964

0.929

0.897

0.864

0.833

 

0.802

 

0.772

0.744

0.716

0.689

0.663

100

0.946

0.912

0.880

0.848

0.817

 

0.787

 

0.758

0.730

0.703

0.676

0.651

 

1.100

 

 

 

 

 

 

 

1.050

 

 

 

 

 

 

 

1.000

 

 

 

 

 

 

Factor

0.950

 

 

 

 

 

Sea Level

 

 

 

 

 

 

0.900

 

 

 

 

 

1000 ft

 

 

 

 

 

2000 ft

Correction

 

 

 

 

 

 

0.850

 

 

 

 

 

3000 ft

 

 

 

 

 

4000 ft

 

 

 

 

 

 

0.800

 

 

 

 

 

5000 ft

0.750

 

 

 

 

 

6000 ft

 

 

 

 

 

 

 

 

 

 

 

 

7000 ft

 

 

 

 

 

 

 

 

0.700

 

 

 

 

 

8000 ft

 

 

 

 

 

 

9000 ft

 

 

 

 

 

 

 

 

0.650

 

 

 

 

 

10000 ft

 

 

 

 

 

 

 

 

0.600

 

 

 

 

 

 

 

40

50

60

70

80

90

100

 

 

 

Air Temperature (ºF)

 

 

Figure 1: Altitude/Temperature Correction Factors

The examples below will assist in determining the airflow performance of the product at altitude.

Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: At an elevation of 5,000 ft. the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, the Altitude/Temperature Correction Factors table must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. The table shows the correction factor to be 0.832.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC

Corrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

blower tables to select the blower speed and the BHP requirement.

Solution: As in the example above, no temperature information is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.

Sea level static pressure = 1.5 / .832 = 1.80"

Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation.

BHP at 5,000 ft. = 3.2 x .832 = 2.66

68

Johnson Controls Unitary Products

Image 68
Contents Description Table of Contents C00 NomenclatureCondensing Unit Features and Benefits Outdoor Unit AccessoriesFeatures BenefitsAir Handling Unit Features and Benefits Unit InstallationAccessories Factory-Mounted ComponentsGuide Specifications Non-fused Disconnect Switch Refrigerant PipingElectrical Requirements Unit ControlsBlower Wheels Shall Evaporator Coil ShallBlower Motor Shall Physical Data YH-07 Thru -20 and YJ-10 Thru -20 Physical DataPH-07 Thru -20 and PJ-15 Thru -20 Physical Data Physical Data Indoor Unit Indoor CoilUnit Limitations Condenser Unit limitationsAir Handling Unit Limitations DB/WBCooling and Heating Ratings Cooling And Heating RatingCapacity Performance Condenser and Air Handling Cooling Capacities YH-07 / NH-07115F 125F YH-07 / NH-10 75FYH-07 / NH-10 YH-10 / NH-10 YH-10 / NH-10 YJ-10 / NJ-10 YJ-10 / NJ-10 YH-12 / NH-15 MBh YJ-12 / NJ-15 YJ-12 / NJ-15 YH-15 / NH-15 YH-15 / NH-15 YH-15 / NH-20 YH-15 / NH-20 YJ-15 / Two NH-07 YJ-15 / Two NH-07 YJ-15 / Two NH-10 Sensible Capacity MBhSensible Capacity MBh1 YJ-15 / NJ-15 115F 125F YJ-15 / NJ-20 Sensible Capacity MBh1 YH-20 / NH-20 115F 125F YJ-20 / Two NH-10 Total Sensible Capacity MBh1 YJ-20 / NJ-20 Capacity1 Input Condenser Only Cooling Capacities Condenser Only Ratings MBH EER75F 85F 115F 125F PH-10 / NH-10 PH-10 / NH-10 PH-15 / NH-15 PH-15 / NH-15 PJ-15 / NJ-15 PJ-15 / NJ-15 PH-20 / NH-20 PH-20 / NH-20 PJ-20 / NJ-20 PJ-20 / NJ-20 Heat Pump And Air Handler Heating Capacities PH-07 / NH-07 CFM68.2 80.0 93.8 84.3 98.8 Airflow Performance NH-07 Upflow and Horizontal Airflow PerformanceNH-07 Upflow NH-07 HorizontalNH/NJ-10 Horizontal NH/NJ-10 Upflow and Horizontal Airflow PerformanceNH/NJ-10 Upflow NH/NJ-15 Horizontal NH/NJ-15 Upflow and Horizontal Airflow PerformanceNH/NJ-15 Upflow NH/NJ-20 Horizontal NH/NJ-20 Upflow and Horizontal Airflow PerformanceNH/NJ-20 Upflow RPM Selection Additional Static Resistance BTG-A-0309 Altitude/Temperature Correction Factors Air Temperature ºFFactor CorrectionAirflow Performance Example Supply Air Blower PerformanceOutdoor Sound Power Levels dB, 60 Hz Sound PerformanceElectrical Data FLAAmpacity1 BTG-A-0309 Electrical Data For Indoor Models Electrical Data Indoor UnitsElectric Heat Option Electrical Data Indoor Units Air Conditioning Condensing Units Typical Wiring DiagramsTypical YH-07 Wiring Diagram Typical YH-10 / YH-12 Wiring Diagram Typical YJ-10 / YJ-12 Wiring Diagram Typical YH-15 / YH-20 Wiring Diagram Typical YJ-15 / YJ-20 Wiring Diagram Typical PH-07 Wiring Diagram Heat Pump UnitsTypical PH-10 Wiring Diagram Typical PH-15 / PH-20 Wiring Diagram Typical PJ-15 / PJ-20 Wiring Diagram Typical NH-07 Wiring Diagram Air Handling UnitsTypical NH/NJ-10 Thru NH/NJ-20 Wiring Diagram Weights And Dimensions Corner Weights & Center of Gravity AC/HP UnitsUnit Dimensions Unit Dimensions PH-07, PH-10, YH-07, YH/YJ-10, YH/YJ-12Unit Dimensions PH/PJ-15, PH/PJ-20, YH/YJ-15, YH/YJ-20 Location Dimensions Piping And Electrical Connection Sizes InchesCorner Weights & Center of Gravity NH/NJ Units LbsUnit Dimensions NH-07 / NH/NJ-10 and NJ-10 TOP ViewUnit Dimensions NH/NJ-15 Unit Dimensions NH/NJ-20 TOP ViewMinimum Clearances PIPING, Electrical and Duct Opening Connection SizesMounting Typical Suspension of AHU’s From CeilingTypical Field Wiring Diagram NH-07 Unit S1 G1 S2 G2 C Johnson Controls Unitary Products York Drive Norman, OK
Related manuals
Manual 16 pages 31.86 Kb

R-410A specifications

Johnson Controls R-410A is a widely recognized refrigerant in the HVAC industry, primarily used in air conditioning and heat pump applications. Known for its environmental benefits and efficiency, R-410A has risen to prominence as a reliable replacement for older refrigerants such as R-22, which are being phased out due to their harmful impact on the ozone layer.

One of the standout features of R-410A is its low impact on global warming potential, making it an environmentally-friendly choice. It is composed of a mixture of hydrofluorocarbons (HFCs), specifically difluoromethane (R-32) and pentafluoroethane (R-125). This blend allows for efficient heat transfer while minimizing harmful emissions, addressing the growing concerns over climate change.

Johnson Controls emphasizes the efficiency of R-410A systems, which can provide a highly effective cooling performance. They are designed to operate at higher pressures compared to R-22, allowing for more efficient heat exchange and better overall system performance. This results in greater energy efficiency ratings, contributing to lower electricity bills for consumers.

In terms of technology, R-410A systems often feature advanced compressor designs and enhanced coil configurations, which optimize the system’s performance. Johnson Controls integrates state-of-the-art variable speed technologies and smart controls that enhance responsiveness and adaptability to changing environmental conditions. These innovations not only improve thermal comfort but also reduce energy consumption, leading to a smaller carbon footprint.

Another significant characteristic of R-410A is its compatibility with various lubricants, which is crucial for maintaining system performance and longevity. Johnson Controls often utilizes specially formulated lubricants that work optimally with R-410A, ensuring reliable operation and reducing the risk of issues related to lubrication.

In summary, Johnson Controls R-410A is an important refrigerant characterized by its efficient, environmentally friendly properties and advanced technologies. Its application in modern HVAC systems provides users with excellent performance, substantial energy savings, and an effective solution for climate-conscious cooling. As the industry continues to evolve, R-410A remains a central player in the push toward more sustainable and efficient heating and cooling solutions.