GE 5100 installation instructions Diagnosis Switch, Temperature Limiting

Page 18

Installation Instructions

Temperature Limiting

 

1 2 3 4 5 6

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

Auxiliary Controls

Temperature limiting can reduce energy costs by limiting the lowest temperature that can be set on cooling and the highest tempera- ture that can be set on heating. Temperature limiting is controlled by setting the first six auxiliary switches.

The first three are used to select cooling range limits and the next three are used to select heating range limits.

COOLING LIMITS

Limit Switch

Temp Range

Up/On

F.

 

 

 

NONE

62 to 85

1

64 to 85

1 & 2

67 to 85

2

69 to 85

2 & 3

71 to 85

1 & 2 & 3

73 to 85

1 & 3

75 to 85

3

77 to 85

HEATING LIMITS

Limit Switch

Temp Range

Up/On

F.

 

 

 

NONE

60 to 85

4

60 to 80

4 & 5

60 to 76

5

60 to 74

5 & 6

60 to 73

4 & 5 & 6

60 to 71

4 & 6

60 to 69

6

60 to 67

Diagnosis Switch

13

ON

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

Auxiliary Controls

The Zoneline has a diagnosis feature. When switch 13 is moved to the ON (up) position, the unit will go through an operations check of all components which takes about two minutes. This diag- nostic tool is intended for use by a qualified technician.

18

Image 18
Contents Zoneline Before using your Zoneline 800.626.2000Write down the model and serial Read ALL Safety Information Before Using Replacing an existing unit?Mode Control Controls on your ZonelineVentilation Control Other Zoneline features About Your Heat PumpFan Switch Freeze SentinelBase Pan Care & CleaningOutdoor Coils Room Cabinet and CaseAir Filters Use the correct outdoor grille Read carefullyUse the correct wall case Replacing a ducted chassis Replacing 230/208 volt unitsImportant electrical safety-read carefully Important NotesZoneline Components How to Connect 230/208 Volt Electrical SupplyVolt Electrical Supply Power Connection Chart Install the Wall Case and Exterior GrilleInsulated Wall Case Install the Unit into the Wall Case Replace the Room Cabinet Low Voltage Connectors & Auxiliary Controls Boost Heat Option Electric Heat Option Remote Control Wall Thermostat PCSDo not use a common buss in the CDC wiring Central Desk ControlDiagnosis Switch Temperature LimitingThings that are normal NoiseExplanation Zoneline Doesn’t Start Before you call for serviceZoneline Does Not Cool or Heat as it Should What to DoHeating Operation Call SVC Indicator LightBurning Odor at Start of Heating Operation Air is Not Always Cool or Hot During OperationPage Parts and Accessories Further ServiceOn-Site Repair Service We’ll be thereWhat is Covered What is Not Covered