GE 8500 Series installation instructions Build and Install the Zoneline Base Platform

Page 18

Installation Instructions

WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION

Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions provided with the plenum.

IMPORTANT: The wall plenum is not designed to carry structural loads. Proper wall header construction is required. The plenum requires proper flashing, shim and caulk for a weather resistant installation.

Proper header for structural support. Apply proper caulking and flashing.

Properly square and level plenum.

Architectural

Louver—RAVAL1

Exterior/Outside Wall

Wall Plenum

 

RAVWP6 – 6D x 1934W x 32H

 

RAVWP8 – 8D x 1934W x 32H

 

RAVWP12 – 12D x 1934W x 32H

Case

RAVWP15 – 15D x 1934W x 32H

 

1BUILD AND INSTALL THE ZONELINE BASE PLATFORM

1.Construct a 2314” min. x 2314” min. square platform with legs to raise the platform a minimum of 8”.

NOTE: The platform must have a load-bearing capacity of 175 lbs. minimum.

2. Make drain hole cutout(s):

• Primary Drain – Centerline of drain is

approximately 514” from left platform edge

and 812” from back platform edge.

• Secondary Drain – Centerline of drain

is approximately 612” from left platform edge

and 514” from back platform edge.

Left side of platform 2314min.

8”min.

for drain access

NOTE: Specific cutout size for drain connections needs

to be determined by the installer for the given installation situation.

Back of platform 2314min.

Cutout for drain

514 connection(s) (see NOTE below)

514612 812

3. Place the platform in the utility closet

with the following clearance between it

and the interior surface of the walls/door/panel:

• 4” min. from front of the case –

Unit to be installed through FRONT of case

• 5” min. from front of the case –

Unit to be installed through SIDE of case

• 3” min. from two sides of the case (5” for side

installation).

4. Align the platform with the opening of

the wall plenum and secure to the floor

using appropriate brackets and bolts.

18

Image 18
Contents Preparation WarrantyAir Filters Model # Serial #Safety Precautions Troubleshooting Controls-dip switchesControls-Dip Switches All Electric Heat Heat pump models onlyDuct Constant on FanOccupancy Sensor Field Supplied Freeze Sentinel Requires room air sensor kit-RAVRMSTemperature Limiting Requires room air sensor kit-RAVRMS Temperature limiting during Cool modeGEAppliances.com Room Air Sensor Requires room air sensor kit Ravrms Controls-terminal connectionsControls-Terminal Connections Also be connected to the remote thermostatMotion Sensor Obtained locally Central Desk ControlRemote Thermostat Door Sensor Obtained locallyVentilation Control Other features of your ZonelineOn/Off Switch About Heat Pumps on some modelsBase Pan Care and cleaningDrain Air FiltersInstallation Recommended branch circuit wire sizes For 230/208 Volt Cord Connections onlyAttach Conduit For 230/208 Volt Direct Connect Applications onlyRemove Junction BOX Cover Important Connection of a 265V AC productMake Wire Lead Connections Inside the Junction BOX Power Connection ChartModel Type Required AccessoriesZoneline Components Electronic ThermostatTypical Utility Closet and Dimensions Top ViewUtility Closet Connection Locations Air grille and access door/panel OptionUnit-mounted filter with a field-supplied return Build and Install the Zoneline Base Platform 000 BTU 12,000 BTU 18,000 BTU Install the DrainsDuctwork 390 415 440 465 490 435 485 535Adjust all four leveling legs until the case is level Install and Connect the CaseInstall and Ground Unit to the Case Unit to the CaseMaximum Wiring Length for Thermostat Connection to the Unit Make Unit Electrical ConnectionsConnect the TOP Duct Connect Power Final CheckServicing Unit is unplugged Before You Call For Service…Power failure Indoor airflow is restricted Air filter is dirtyNormal Operating Sounds Minute delayThings that are normal Compressor. You may also hear a fan noise stop and startGEAppliances.com Page What GE Will Not Cover Vertical Zoneline WarrantyFor The Period GE Will Replace Model numberConsumer Support GE Appliances Website Schedule ServiceParts and Accessories Real Life Design Studio

8500 Series specifications

The GE 8500 Series represents a remarkable advancement in the realm of industrial gas turbines, combining efficiency, reliability, and flexibility. Designed to meet the demands of current energy markets, this series of turbines is engineered for both baseload and peak-load applications, making it an ideal choice for operators seeking to optimize their energy production.

One of the standout features of the GE 8500 Series is its exceptional thermal efficiency. With a capability of achieving efficiency levels exceeding 60%, these turbines significantly reduce fuel consumption and lower greenhouse gas emissions. This feature not only makes them environmentally friendly but also helps operators reduce operational costs in the long run, positioning them favorably in a competitive energy landscape.

The GE 8500 Series incorporates advanced airfoil technologies that enhance performance. Featuring an innovative blade design, these turbines are capable of operating efficiently across a wide range of operating conditions. The materials used in the construction of the blades are engineered for durability, allowing them to withstand the harsh environments often encountered in power generation. This greatly extends the service life of the turbine and reduces downtime for maintenance.

Another important aspect of the GE 8500 Series is its adaptability. These turbines can utilize various fuels, including natural gas, hydrogen, and biofuels, offering flexibility to operators in terms of resource management. This feature allows utilities to adjust to changing fuel availability and price fluctuations, ensuring consistent energy generation.

The control and monitoring systems integrated into the GE 8500 Series are state-of-the-art, featuring advanced digital control technologies that provide real-time performance data. This allows operators to make informed decisions regarding maintenance and operational adjustments, ultimately enhancing the overall reliability of the power generation system.

In addition to these advancements, the GE 8500 Series is designed with a focus on reduced emissions without compromising performance. The turbines incorporate advanced combustion technologies that facilitate ultra-low emissions, aligning with the global movement toward cleaner energy solutions.

In conclusion, the GE 8500 Series is an exceptional line of gas turbines that combines high efficiency, flexibility, and low emissions. With advanced technologies and robust features, these turbines are positioned to meet the evolving needs of the energy sector while supporting the transition to a more sustainable future.