Nordyne M3RL installation instructions Cooling Mode, Furnace Fails to Operate

Page 31

Initial Power up: After 30 seconds of igniter warm-up the gas valve (24 VAC) will then open. The igniter circuit will stay ener- gized for 3 seconds after the gas valve opens.

After Initial Power up: The control has a programmed adaptive ignition feature which varies the warm-up period as fol- lows: If ignition is successful the warm-up is reduced by 3-seconds on each subsequent call for heat until ignition failure occurs. Upon ignition failure, the warm-up is in- creased by 3-seconds on the next try. If successful, the timing remains fixed at this level. In general, whenever ignition failure occurs the warm-up interval is increased by 3-seconds on the next try. And if success- ful, it remains there. Minimum and maxi- mum warm-up time limits are set at 6 and 54-seconds, respectively.

7.The furnace control must prove flame via the flame sensor 5 seconds after the gas valve opens. If flame is sensed, all burn- ers are on and the ignitor cools off. If no flame is sensed, the gas valve closes immediately and the inducer continues to run. A second trial for ignition (step 6) begins if no flame is sensed. On the fifth try for ignition, the furnace control is locked out and the red LED will blink 4 times repetitively. The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out. Oth- erwise, the furnace will attempt another ignition sequence in 1 hour.

8.The furnace control energizes the cir- culating air blower on the heating speed 30 seconds after the gas valve circuit is energized .

9.When the thermostat has been satisfied,

gas valve is de-energized.

10.The inducer is de-energized after a 30- second postpurge.

11.The furnace control keeps the circulating air blower energized for 120 seconds (factory set) or 60, 90, or 180 seconds (field adjustable). (See Figure 27.)

12.Abnormal conditions: If a limit opens during operation, the inducer and circulating air blower continue to operate. The gas valve is de-energized immediately. The blowers continue to operate until the limit closes. When the limit closes the inducer blower is de-energized immediately. The circulating air blower continues to operate for the speci- fied delay (factory set at 120 seconds).

Cooling Mode:

1.On a call for cooling the thermostat closes, applying 24 VAC to the G and Y terminals on the furnace control. This closes the compressor contactor.

2.The furnace control energizes the circu- lating blower (115 VAC) on the cooling speed.

3.When the thermostat is satisfied, the G and Y terminals on the control board are de-energized opening the compressor contactor.

4.The circulating air blower is de-energized after a 90-second delay.

Fan Mode:

1.On a call for fan operation, the thermostat applies 24 VAC to the G terminal on the furnace control board.

2.The circulating air blower is energized immediately on the heating speed.

3.If the furnace is operated in the continu- ous ON position at the thermostat and is then switched to AUTO, the circulating blower will operate for a specified delay (factory set at 120 seconds).

Furnace Fails to Operate

If the furnace does not operate check the following:

1.Is the thermostat operating properly?

2.Is the front door in place?

3.Is the furnace disconnect closed?

4.Has the circuit breaker tripped or the control board fuse burned open?

5.Is the gas turned on?

6.Are any manual reset switches open?

7.Is the filter dirty or plugged?

8.Is the flame sensor coated? (Remove and clean with emery cloth.)

9.Is the deck switch open?

If the furnace locks out after 5 attempts for ignition, it will try again every hour if a call for heat remains. If the inducer and circulating air blowers are operating, and items 1 through 8 have been checked, press the red reset but- ton on the vent safety switch. (See Figure 29.) If the furnace operates after depressing the reset button, contact a qualified service tech- nician to identify and repair the problem.

If furnace still fails to operate, depress the red reset buttons on the flame roll-out switch. If the furnace operates after depressing the reset button, contact a qualified service tech- nician to identify and repair the problem.

31

Image 31
Contents Installation Instructions Page L 060 a a W Table of ContentsTop View Shipping WeightFurnace Specifications/Airflow Data GeneralGeneral Description Owner InformationManufacturer WARRANTY, OWNER’S Responsibilities Installation StandardsCirculating AIR Supply LocationMinimum Clearances Return AIR Provisions Duct ConnectorsDucted Return AIR Closet or AlcoveDuct Installation Duct Connector SelectionAIR Distribution Systems Screw Down Platinum Series Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector CUT Duct Opening Finger Tabbed onlyAlternate Attachment Methods Installing Finger Tabbed Duct CON- NectorsVenting and Combustion AIR Requirements Install FurnaceGeneral Furnace Must not be Common Vented with Other Appliances Venting RequirementsVent Termination Clearances for Direct Vent Furnaces Vent TableVent Pipe Material Vent Pipe InstallationHorizontal Venting Downflow FurnaceHorizontal Venting Drainage of Condensate from Furnace Alternate Horizontal Vent InstallationGAS Supply and Piping Furnace with Condensate Drain Trap AssemblyTo Turn Off Fuel Supply to the Appliance ConversionLeak Check High Altitude DerateApproximate Orifice Size for Natural and LP Gases To Remove the Burner AssemblyTo Remove the Burner Orifices To Convert the Unit to the Alternate GasConvertible Pressure Regulator Cap Lighting and Adjustment of the ApplianceCompleting the Conversion Electrical WiringLine Voltage Wiring Type of Fuel Manifold PressureElectrical Data Low Voltage WiringStart-Up Procedure START-UP and AdjustmentsVentilation Sequence of Operation Shut Down ProcedureVerifying Firing Rate Verifying Burner Operation Verifying Operation of the Supply Air Limit SwitchDescription of Components Gas Flow RateAir Filter MaintenanceAccessory Kits Combustion Air and Vent SystemBlower Compartment Condensate Drain AssemblySystem Operation Information LubricationFurnace Fails to Operate Cooling ModeM3 Downflow Furnace Downflow Furnace Wiring Diagram Page Fuel Type INSTALLATION/PERFORMANCE Check List¢7082197¤

M3RL specifications

The Nordyne M3RL is a high-efficiency gas furnace designed for residential heating applications, characterized by its robust performance and advanced technologies. It is part of Nordyne's distinguished lineup, which emphasizes reliability and comfort in home heating systems. The M3RL model is particularly notable for its focus on energy efficiency, making it an attractive option for homeowners looking to reduce their energy expenses while maintaining optimal heating levels.

One of the standout features of the Nordyne M3RL is its high Annual Fuel Utilization Efficiency (AFUE) rating, which often exceeds 80%. This efficient design ensures that more of the fuel consumed is converted into usable heat for the home. By employing a variable-speed blower, the M3RL enhances comfort by allowing for more precise control over air circulation, contributing to better temperature consistency throughout the living space.

The M3RL utilizes advanced multi-stage heating technology, allowing the system to operate at different capacities depending on the heating demand. This means it can run at lower settings during milder weather, which not only saves energy but also reduces wear and tear on the equipment, extending its lifespan. The furnace also includes a reliable ignition system that ensures quick and safe starts, eliminating the inefficiencies associated with older pilot light systems.

Another important characteristic of the Nordyne M3RL is its acoustical insulation, which minimizes operational noise. The quiet operation is particularly valued in residential settings, where noise pollution can be disruptive. Additionally, the furnace features a compact design, making it easy to install in a variety of spaces, including tight basements or utility rooms.

The M3RL model is also equipped with a smart control system that interfaces seamlessly with modern thermostats, offering homeowners the ability to program their heating schedules and optimize energy usage. This integration with smart home technology positions the M3RL not just as a heating solution, but as a component of a more comprehensive home energy management system.

In conclusion, the Nordyne M3RL gas furnace represents a blend of efficiency, advanced technology, and user-friendly features. Its high AFUE rating, multi-stage heating capability, quiet operation, and smart technology integration make it a reliable choice for homeowners aiming to enhance their comfort while minimizing energy costs. This furnace is a testament to Nordyne's commitment to innovation in the HVAC industry.