Nordyne M3RL Venting Requirements, Furnace Must not be Common Vented with Other Appliances

Page 14

!CAUTION:

Do not allow debris to fall into the fur- nace. This could cause unsafe opera- tion and voids the furnace warranty.

VENTING REQUIREMENTS

!WARNING:

FURNACE MUST NOT BE COMMON VENTED WITH OTHER APPLIANCES.

General

This section specifies installation requirements for 2-pipe combustion air piping. The capacity table provided in this section applies to the maximum equivalent lengths of vent and combustion air intake pipe.

These condensing furnaces are classified as "Category IV" appliances, which require special venting materials and installation procedures. Category IV appliances operate with positive vent pressure and therefore require vent systems which are thoroughly sealed. They also produce combustion condensate, which is slightly acidic and can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping. Therefore, vent and combustion air piping lengths must conform completely to the requirements of Table 6.

The furnace must be vented to the outdoors.

!WARNING:

CARBON MONOXIDE POISONING

HAZARD

1.Seal any unused openings in the venting system

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 or the CAN/CGA B149 Installation Codes and these instructions. Determine

that there is no blockage or re- striction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.So far as is practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4.Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall operate continuously.

5.Turn on clothes dryers and any other appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan.

6.Close fireplace dampers.

7.Test for spillage from draft hood equipped appliance at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.

8.If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.

9.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

It must not be vented in common with any other appliance, even if that appliance is of the condensing type. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to

14

Image 14
Contents Installation Instructions Page Table of Contents L 060 a a WGeneral Shipping WeightFurnace Specifications/Airflow Data Top ViewOwner Information General DescriptionInstallation Standards Manufacturer WARRANTY, OWNER’S ResponsibilitiesMinimum Clearances LocationCirculating AIR Supply Duct Connectors Return AIR ProvisionsCloset or Alcove Ducted Return AIRAIR Distribution Systems Duct Connector SelectionDuct Installation CUT Duct Opening Finger Tabbed only Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector Screw Down Platinum SeriesInstalling Finger Tabbed Duct CON- Nectors Alternate Attachment MethodsGeneral Install FurnaceVenting and Combustion AIR Requirements Venting Requirements Furnace Must not be Common Vented with Other AppliancesVent Table Vent Termination Clearances for Direct Vent FurnacesVent Pipe Installation Vent Pipe MaterialDownflow Furnace Horizontal VentingHorizontal Venting Alternate Horizontal Vent Installation Drainage of Condensate from FurnaceFurnace with Condensate Drain Trap Assembly GAS Supply and PipingHigh Altitude Derate ConversionLeak Check To Turn Off Fuel Supply to the ApplianceTo Convert the Unit to the Alternate Gas To Remove the Burner AssemblyTo Remove the Burner Orifices Approximate Orifice Size for Natural and LP GasesLighting and Adjustment of the Appliance Convertible Pressure Regulator CapType of Fuel Manifold Pressure Electrical WiringLine Voltage Wiring Completing the ConversionLow Voltage Wiring Electrical DataVentilation START-UP and AdjustmentsStart-Up Procedure Verifying Firing Rate Shut Down ProcedureSequence of Operation Gas Flow Rate Verifying Operation of the Supply Air Limit SwitchDescription of Components Verifying Burner OperationCombustion Air and Vent System MaintenanceAccessory Kits Air FilterLubrication Condensate Drain AssemblySystem Operation Information Blower CompartmentCooling Mode Furnace Fails to OperateM3 Downflow Furnace Downflow Furnace Wiring Diagram Page INSTALLATION/PERFORMANCE Check List Fuel Type¢7082197¤

M3RL specifications

The Nordyne M3RL is a high-efficiency gas furnace designed for residential heating applications, characterized by its robust performance and advanced technologies. It is part of Nordyne's distinguished lineup, which emphasizes reliability and comfort in home heating systems. The M3RL model is particularly notable for its focus on energy efficiency, making it an attractive option for homeowners looking to reduce their energy expenses while maintaining optimal heating levels.

One of the standout features of the Nordyne M3RL is its high Annual Fuel Utilization Efficiency (AFUE) rating, which often exceeds 80%. This efficient design ensures that more of the fuel consumed is converted into usable heat for the home. By employing a variable-speed blower, the M3RL enhances comfort by allowing for more precise control over air circulation, contributing to better temperature consistency throughout the living space.

The M3RL utilizes advanced multi-stage heating technology, allowing the system to operate at different capacities depending on the heating demand. This means it can run at lower settings during milder weather, which not only saves energy but also reduces wear and tear on the equipment, extending its lifespan. The furnace also includes a reliable ignition system that ensures quick and safe starts, eliminating the inefficiencies associated with older pilot light systems.

Another important characteristic of the Nordyne M3RL is its acoustical insulation, which minimizes operational noise. The quiet operation is particularly valued in residential settings, where noise pollution can be disruptive. Additionally, the furnace features a compact design, making it easy to install in a variety of spaces, including tight basements or utility rooms.

The M3RL model is also equipped with a smart control system that interfaces seamlessly with modern thermostats, offering homeowners the ability to program their heating schedules and optimize energy usage. This integration with smart home technology positions the M3RL not just as a heating solution, but as a component of a more comprehensive home energy management system.

In conclusion, the Nordyne M3RL gas furnace represents a blend of efficiency, advanced technology, and user-friendly features. Its high AFUE rating, multi-stage heating capability, quiet operation, and smart technology integration make it a reliable choice for homeowners aiming to enhance their comfort while minimizing energy costs. This furnace is a testament to Nordyne's commitment to innovation in the HVAC industry.