Nordyne M3RL Electrical Wiring, Type of Fuel Manifold Pressure, Completing the Conversion

Page 24

7.After the flame ignites, visually inspect the burner assembly to ensure that the flame is drawn directly into the center of the heat exchanger tube, as shown in Figure 23. The end of the flame will be out of sight around the bend of the heat exchanger tube. In a properly adjusted burner assem- bly, the flame color should be blue with some light yellow streaks near the outer portions of the flame.

NOTE: Until all of the air is bled out of the gas line, the hot surface ignitor may not ignite the gas. If the ignition control locks out, turn the thermostat to its lowest setting and wait one minute then turn the thermostat to a point above room temperature and the ignitor will try again to ignite the main burners. This process may have to be repeated several times before the burners will ignite. Once the burners are lit, check all gas connections for leaks again with the soap and water solution. If the solution bubbles there is a gas leak which must be corrected. Do not use an open flame to check for gas leaks.

Manifold Pressure

The gas valve for the M3 furnace series is equipped with a special conversion pres- sure regulator cap. The pressure regulator cap is factory set. If the gas valve is con- verted from natural gas to propane gas or vise versa, the manifold pressure of the gas valve will be set to pressure listed in Table 9.

Type of Fuel

Manifold Pressure

 

In. WC

 

 

Natural Gas:

3.5

Propane (LP) Gas:

10.0

 

 

Table 9. Manifold Pressure

COMPLETING THE CONVERSION

1.Affix the gas valve conversion label found in the package with the orifices to the unit rating plate.

2.Run the appliance through a complete cycle to assure proper operation.

!CAUTION:

To avoid electric shock, personal injury, or death, turn off the power at the disconnect or the main service panel before making any electrical connections.

ELECTRICAL WIRING

General

Electrical connections must be made in accor- dance with all applicable local codes and ordi- nances, and with the current revision of the National Electric Code (ANSI/NFPA 70).

For Canadian installations electrical connec- tions and grounding must be done in accor- dance with the current Canadian Electrical Code (CSA C22.1 Part 1) and/or local codes. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wire having a minimum temperature rating of 105°C. Refer to the furnace nameplate and Table 8 for electrical requirements.

Line Voltage Wiring

The line voltage (115 volt) to the furnace must be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the furnace. See Table 10. An electrical switch should be readily accessible from and within sight of the furnace. See the Wiring Diagram label in the furnace for more details.

The furnace cabinet must have an uninter- rupted, unbroken ground to minimize injury should an electrical fault condition occur. The controls used in this furnace require an earth ground to operate properly. Acceptable meth- ods for grounding are electrical wire or conduit approved for electrical ground service. Do not use gas piping as an electrical ground.

NOTE: Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify that the incoming neu-

24

Image 24
Contents Installation Instructions Page Table of Contents L 060 a a WShipping Weight Furnace Specifications/Airflow DataGeneral Top ViewOwner Information General DescriptionInstallation Standards Manufacturer WARRANTY, OWNER’S ResponsibilitiesLocation Circulating AIR SupplyMinimum Clearances Duct Connectors Return AIR ProvisionsCloset or Alcove Ducted Return AIRDuct Connector Selection Duct InstallationAIR Distribution Systems Installing Platinum Series 14 Round Duct Connector Installing Screw Down Duct CON- NectorCUT Duct Opening Finger Tabbed only Screw Down Platinum SeriesInstalling Finger Tabbed Duct CON- Nectors Alternate Attachment MethodsInstall Furnace Venting and Combustion AIR RequirementsGeneral Venting Requirements Furnace Must not be Common Vented with Other AppliancesVent Table Vent Termination Clearances for Direct Vent FurnacesVent Pipe Installation Vent Pipe MaterialDownflow Furnace Horizontal VentingHorizontal Venting Alternate Horizontal Vent Installation Drainage of Condensate from FurnaceFurnace with Condensate Drain Trap Assembly GAS Supply and PipingConversion Leak CheckHigh Altitude Derate To Turn Off Fuel Supply to the ApplianceTo Remove the Burner Assembly To Remove the Burner OrificesTo Convert the Unit to the Alternate Gas Approximate Orifice Size for Natural and LP GasesLighting and Adjustment of the Appliance Convertible Pressure Regulator CapElectrical Wiring Line Voltage WiringType of Fuel Manifold Pressure Completing the ConversionLow Voltage Wiring Electrical DataSTART-UP and Adjustments Start-Up ProcedureVentilation Shut Down Procedure Sequence of OperationVerifying Firing Rate Verifying Operation of the Supply Air Limit Switch Description of ComponentsGas Flow Rate Verifying Burner OperationMaintenance Accessory KitsCombustion Air and Vent System Air FilterCondensate Drain Assembly System Operation InformationLubrication Blower CompartmentCooling Mode Furnace Fails to OperateM3 Downflow Furnace Downflow Furnace Wiring Diagram Page INSTALLATION/PERFORMANCE Check List Fuel Type¢7082197¤

M3RL specifications

The Nordyne M3RL is a high-efficiency gas furnace designed for residential heating applications, characterized by its robust performance and advanced technologies. It is part of Nordyne's distinguished lineup, which emphasizes reliability and comfort in home heating systems. The M3RL model is particularly notable for its focus on energy efficiency, making it an attractive option for homeowners looking to reduce their energy expenses while maintaining optimal heating levels.

One of the standout features of the Nordyne M3RL is its high Annual Fuel Utilization Efficiency (AFUE) rating, which often exceeds 80%. This efficient design ensures that more of the fuel consumed is converted into usable heat for the home. By employing a variable-speed blower, the M3RL enhances comfort by allowing for more precise control over air circulation, contributing to better temperature consistency throughout the living space.

The M3RL utilizes advanced multi-stage heating technology, allowing the system to operate at different capacities depending on the heating demand. This means it can run at lower settings during milder weather, which not only saves energy but also reduces wear and tear on the equipment, extending its lifespan. The furnace also includes a reliable ignition system that ensures quick and safe starts, eliminating the inefficiencies associated with older pilot light systems.

Another important characteristic of the Nordyne M3RL is its acoustical insulation, which minimizes operational noise. The quiet operation is particularly valued in residential settings, where noise pollution can be disruptive. Additionally, the furnace features a compact design, making it easy to install in a variety of spaces, including tight basements or utility rooms.

The M3RL model is also equipped with a smart control system that interfaces seamlessly with modern thermostats, offering homeowners the ability to program their heating schedules and optimize energy usage. This integration with smart home technology positions the M3RL not just as a heating solution, but as a component of a more comprehensive home energy management system.

In conclusion, the Nordyne M3RL gas furnace represents a blend of efficiency, advanced technology, and user-friendly features. Its high AFUE rating, multi-stage heating capability, quiet operation, and smart technology integration make it a reliable choice for homeowners aiming to enhance their comfort while minimizing energy costs. This furnace is a testament to Nordyne's commitment to innovation in the HVAC industry.