Table 10 — Terminal Service Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

COOLING

 

 

Terminal Type

1

TERMTYPE

Primary Inlet Size

 

 

Inlet Diameter

6.0 in.

RNDSZ

Inlet Area

0.0 in.

SQA

Probe Multiplier

2.443

PMF

Calibration Gain

1.000

CAL_GAIN

Offset

0 cfm

OFFSET

Damper

 

 

Proportional Gain

30.0

KP

Integral Gain

5.0

KI

Derivative Gain

0.0

KD

Starting Value

20 %

STARTVAL

CW Rotation

Close

DMPDIR

Pressure Independent

Yes

PRESIND

HEATING

 

 

Heat Type

0

HEATTYPE

VAV Central Heating

Yes

CENHEAT

Heating

 

 

Proportional Gain

8.0

KP

Integral Gain

3.0

KI

Derivative Gain

0.0

KD

Starting Value

80 F

STARTVAL

Ducted Heat

Yes

DUCTHEAT

Maximum Temperature

110 F

MAXTEMP

Number of Electric Heat Stages

1

STAGES

Heat On Delay

2

HONDEL

Fan Off Delay

2

FNOFFD

2-Position Heat Logic

Normal

HEATYPE

SPT Trim

0.0 F

SPTTRIM

SAT Trim

0.0 F

SATTRIM

Remote Contact Configuration

Close

RMTCFG

Probe Multiplier — This configuration is used to input a factor for the velocity pressure probe installed in the terminal inlet. Most inlet probes will have some aerodynamic characteristics that will affect the differential pressure output from the probe. The formula used by the ComfortID™ controller for calculat- ing the airflow (cfm) is based on measuring velocity with a Pitot tube probe. A PMF (Pitot measurement factor) is required in the calculation for different probes. Because various probe characteristics are different, the PMF is used to determine the correct airflow based on the type of probe installed. The PMF will compensate for the difference between Pitot-type probes and the actual probe installed.

The default PMF value of 2.273 is the correct value to use when the zone controller is used with a Carrier probe in a Carrier air terminal. For terminals and probes supplied by other manufacturers, the PMF must be calculated and entered into the zone controller configuration in order to correctly measure airflow.

To determine the correct PMF value, there are several meth- ods depending on the data supplied by the terminal manufac- turer. The manufacturer may supply a “K factor” or may sup- ply a chart of velocity pressure vs. airflow for the terminal. The K factor is the actual airflow velocity at a velocity pressure reading of 1 in. wg for the probe. This value is in ft/min and can be used to calculate the PMF. When the K factor is entered into the following equation, it is compared to the value of 4005, which is the K factor for a Pitot tube probe:

PMF = (4005/K FACTOR)2

If a chart is supplied by the manufacturer instead of the K factor, then the K factor can be calculated from the chart using the following formula:

K FACTOR = (cfm at 1-in. wg)/(duct area ft2)

As an example, an air terminal with an 8-in. round inlet is used. The terminal manufacturer has provided an airflow chart

that gives an airflow value of 820 cfm at a velocity pressure reading of 1 in. wg. To determine the PMF for the terminal:

1.Determine duct area.

radius of duct = diameter of duct/2 radius = 8-in./2-in.

radius = 4-in.

Area of circular duct = Πr2 Area = 3.14159 x 42 Area = 3.14159 x 16 Area = 50.26-in.2

Area must be in ft2

50.26-in.2/(144-ft2) = 0.34906 ft2

2.Determine K factor.

K factor = (820 cfm/0.34906 ft2) K factor = 2349 fpm

3.Determine PMF.

PMF = (4005 fpm/2349 fpm)2 PMF = 2.907

Another way to determine the probe constant for a probe without documentation is to measure the velocity pressure with a Magnahelic gage. Open the damper and adjust the static pres- sure or open the damper until you have one inch of velocity pressure on the Magnahelic gage. Measure the total CFM of air being delivered. The CFM just measured divided by the inlet area in square feet should equal the K factor for the formula. Now use the K factor that was empirically derived to determine the probe multiplier.

Probe Multiplier: Range

0.250 to 9.999

Default Value

2.443

Calibration Gain — Air terminal testing by industry standards is done with straight duct, upstream of the terminal. Since some applications do not get installed in this manner, the actual air- flow from the terminal at balancing may not equal the reading from the zone controller.

39

303

Page 39
Image 39
Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications Terminal Service Configuration Screen, Rndsz

33ZCSECTRM, 33ZCVAVTRM, 33ZCFANTRM specifications

The Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM are advanced air conditioning units designed for commercial and light industrial applications. These models represent Carrier's commitment to innovation and energy efficiency, offering unbeatable performance while ensuring minimal environmental impact.

One of the main features of the Carrier 33ZCFANTRM series is its outstanding energy efficiency. These units are designed to meet or exceed Energy Efficiency Ratio (EER) standards, which translates to reduced energy consumption and lower utility bills for users. The implementation of variable speed drive technology allows for precise control of airflow and cooling, enabling the units to adapt to varying load requirements seamlessly. This not only enhances comfort levels but also optimizes energy use.

In terms of design, the Carrier 33ZCSECTRM model stands out with its compact footprint, making it ideal for installation in tight spaces. It features a robust chassis made from high-quality materials that ensure durability and resistance to harsh outdoor conditions. Additionally, the unit is equipped with sound-dampening technology, resulting in quieter operation compared to many traditional systems.

The 33ZCVAVTRM model takes versatility to the next level by incorporating advanced Variable Air Volume (VAV) technology. This allows for customized airflow delivery, ensuring that different areas of a building can be conditioned to meet specific comfort needs. The VAV system helps maintain optimal indoor air quality by continuously monitoring and adjusting airflows based on real-time demand.

Each model also features advanced controls which integrate seamlessly with building management systems. This connectivity provides users with powerful tools for monitoring system performance, enabling predictive maintenance and improving overall operational efficiency.

Moreover, the Carrier 33ZC series employs environmentally friendly refrigerants, which aligns with global sustainability goals. The use of these refrigerants contributes to a lower carbon footprint while still delivering exceptional cooling capacity.

Overall, the Carrier 33ZCFANTRM, 33ZCSECTRM, and 33ZCVAVTRM models epitomize Carrier's innovative spirit, combining cutting-edge technology with superior performance features. These units are well-suited to meet the rigorous demands of diverse commercial applications, promoting both comfort and efficiency in today's dynamic work environments. As businesses evolve, the need for reliable, efficient, and adaptable HVAC solutions becomes paramount, and these Carrier models stand ready to meet that challenge head-on.