SUPPLY AIR TEMPERATURE — Temperature of the air leaving the zone controller downstream of any ducted heat source. Measured by a 10 kΩ thermistor (Type III). This tem- perature is used to control the maximum discharge air to the space when local heat is active. The sensor is not required or recommended for cooling only terminals. If supply air temper- ature display is required by specification, on a cooling only box, a heat type other than zero must be configured. This will have no adverse affect on the operation of a cooling only terminal.
Supply |
|
Air Temperature: Display Units | F (C) |
Default Value | 0.0 |
Display Range | |
Network Access | Read/Write |
LOCAL HEATING CAPACITY — When local heat at the terminal is enabled the percent of heat being delivered is deter- mined by the following formula for modulating (floating point) type heat:
% Capacity = [(SAT - SPT)/(Maximum Duct Temp – SPT )]
The percent of heat delivered is determined by the follow- ing for
% Output Capacity = (# of active stages/Total stages) * 100
Local Heating |
|
|
Capacity: | Display Units | % output capacity |
| Default Value | 0 |
| Display range | 0 to 100 |
| Network Access | Read only |
TERMINAL FAN — The commanded output for the terminal fan on a fan powered terminal.
Terminal Fan: | Display Units | Discrete ASCII |
| Default Value | Off |
| Display Range | Off/On |
| Network Access | Read/Write |
RELATIVE HUMIDITY — Space Relative Humidity read- ing from the optional relative humidity sensor. Used by Hu- midity control function if configured.
Relative |
|
|
Humidity: | Display Units | % RH |
| Default Value | 0 |
| Display Range | 0 to 100 |
| Network Access | Read/Write |
AIR QUALITY — Indoor air quality reading from a CO2 sen- sor installed in the space. Used by Air Quality control function if configured.
Air Quality (ppm):Display units | None shown (parts per |
| million implied) |
Default Value | 0 |
Display range | 0 to 5000 |
Network Access | Read/Write |
SECONDARY AIRFLOW — Airflow reading from the sec- ondary pressure transducer, supplied with the secondary actua- tor, intended for dual duct and pressure control applications.
Secondary |
|
|
Airflow: | Display Units | cfm |
| Default Value | 0 |
| Display Range | 0 to 9999 |
| Network Access | Read/Write |
PRIMARY AIR TEMPERATURE — Primary air tempera- ture from sensor (10 kΩ, Type III), located in main trunk of ductwork for supply air provided by the
Primary Air |
|
|
Temperature: | Display Units | F (C) |
| Default Value | 0.0 |
| Display Range | |
| Network Access | Read/Write |
HEAT ENABLE/DISABLE — Provides enable/disable function for local heat at the terminal. When enabled the Local heat capacity function will run to operate the terminal heat.
Heat Display: | Display Units | Discrete ASCII |
| Default Value | Dsable |
| Display Range | Dsabe/Enable |
| Network Access | Read/Write |
Modify Controller Configuration — In Service Tool software, select the desired zone controller and access the Modify Controller Configuration Menu screen. This configura- tion screen is also displayed under CONFIGURE when using ComfortWORKS® and ComfortVIEW™ software.
The Modify Controller Configuration Menu screen is used to access the Alarm Limit Configuration screen, Controller Identification screen, Holiday Configuration screen, Linkage Coordinator Configuration screen, Occupancy Configuration screen, and Set Point screen.
ALARM LIMIT CONFIGURATION SCREEN — The Alarm Limit Configuration screen is used to configure the alarm settings for the zone controller. See Table 5.
→ Table 5 — Alarm Limit Configuration Screen
DESCRIPTION | DEFAULT | POINT NAME |
Alarm Routing Control | 00000000 | ROUTING |
0 | RETIME | |
SPT Occupied Hysteresis | 5.0 F | SPTHYS |
Unoccupied SPT |
|
|
Low Limit | 40 F | LOWLIM |
High Limit | 99 F | HIGHLIM |
Occupied RH |
|
|
Low Limit | 10 % | LOWLIM |
High Limit | 99 % | HIGHLIM |
Unoccupied RH |
|
|
Low Limit | 0 % | LOWLIM |
High Limit | 100 % | HIGHLIM |
Air Quality |
|
|
Low Limit | 250 ppm | LOWLIM |
High limit | 1200 ppm | HIGHLIM |
High Velocity Pressure | 1.2 in. wg | HIGHVP |
801 | 32 |