SUPPLY AIR TEMPERATURE — Temperature of the air leaving the zone controller downstream of any ducted heat source. Measured by a 10 kthermistor (Type III). This tem- perature is used to control the maximum discharge air to the space when local heat is active. The sensor is not required or recommended for cooling only terminals. If supply air temper- ature display is required by specification, on a cooling only box, a heat type other than zero must be configured. This will have no adverse affect on the operation of a cooling only terminal.

Supply

 

Air Temperature: Display Units

F (C)

Default Value

0.0

Display Range

-40.0 to 245.0

Network Access

Read/Write

LOCAL HEATING CAPACITY — When local heat at the terminal is enabled the percent of heat being delivered is deter- mined by the following formula for modulating (floating point) type heat:

% Capacity = [(SAT - SPT)/(Maximum Duct Temp – SPT )]

The percent of heat delivered is determined by the follow- ing for two-position hot water or staged electric heat:

% Output Capacity = (# of active stages/Total stages) * 100

Local Heating

 

 

Capacity:

Display Units

% output capacity

 

Default Value

0

 

Display range

0 to 100

 

Network Access

Read only

TERMINAL FAN — The commanded output for the terminal fan on a fan powered terminal.

Terminal Fan:

Display Units

Discrete ASCII

 

Default Value

Off

 

Display Range

Off/On

 

Network Access

Read/Write

RELATIVE HUMIDITY — Space Relative Humidity read- ing from the optional relative humidity sensor. Used by Hu- midity control function if configured.

Relative

 

 

Humidity:

Display Units

% RH

 

Default Value

0

 

Display Range

0 to 100

 

Network Access

Read/Write

AIR QUALITY — Indoor air quality reading from a CO2 sen- sor installed in the space. Used by Air Quality control function if configured.

Air Quality (ppm):Display units

None shown (parts per

 

million implied)

Default Value

0

Display range

0 to 5000

Network Access

Read/Write

SECONDARY AIRFLOW — Airflow reading from the sec- ondary pressure transducer, supplied with the secondary actua- tor, intended for dual duct and pressure control applications.

Secondary

 

 

Airflow:

Display Units

cfm

 

Default Value

0

 

Display Range

0 to 9999

 

Network Access

Read/Write

PRIMARY AIR TEMPERATURE — Primary air tempera- ture from sensor (10 k, Type III), located in main trunk of ductwork for supply air provided by the air-handling equip- ment. Used for linkage coordination.

Primary Air

 

 

Temperature:

Display Units

F (C)

 

Default Value

0.0

 

Display Range

-40.0 to 245.0

 

Network Access

Read/Write

HEAT ENABLE/DISABLE — Provides enable/disable function for local heat at the terminal. When enabled the Local heat capacity function will run to operate the terminal heat.

Heat Display:

Display Units

Discrete ASCII

 

Default Value

Dsable

 

Display Range

Dsabe/Enable

 

Network Access

Read/Write

Modify Controller Configuration — In Service Tool software, select the desired zone controller and access the Modify Controller Configuration Menu screen. This configura- tion screen is also displayed under CONFIGURE when using ComfortWORKS® and ComfortVIEW™ software.

The Modify Controller Configuration Menu screen is used to access the Alarm Limit Configuration screen, Controller Identification screen, Holiday Configuration screen, Linkage Coordinator Configuration screen, Occupancy Configuration screen, and Set Point screen.

ALARM LIMIT CONFIGURATION SCREEN — The Alarm Limit Configuration screen is used to configure the alarm settings for the zone controller. See Table 5.

Table 5 — Alarm Limit Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

Alarm Routing Control

00000000

ROUTING

Re-Alarm Time

0

RETIME

SPT Occupied Hysteresis

5.0 F

SPTHYS

Unoccupied SPT

 

 

Low Limit

40 F

LOWLIM

High Limit

99 F

HIGHLIM

Occupied RH

 

 

Low Limit

10 %

LOWLIM

High Limit

99 %

HIGHLIM

Unoccupied RH

 

 

Low Limit

0 %

LOWLIM

High Limit

100 %

HIGHLIM

Air Quality

 

 

Low Limit

250 ppm

LOWLIM

High limit

1200 ppm

HIGHLIM

High Velocity Pressure

1.2 in. wg

HIGHVP

801