PRIMARY AIR INLET
UNIT WITH ELECTRIC REHEAT
2 FT. MIN.
AIR
TERMINAL
UNIT
ZC | HEAT | SAT |
UNIT WITH OCTOPUS
PRIMARY
AIR INLET
ZC — Zone Controller
|
| 2 FT. MIN. |
| AIR | OCTOPUS |
TERMINAL | ||
| UNIT |
|
ZC | HEAT | SAT |
→ Fig. 17 — Supply Air Temperature Probe (Part No. 33ZCSENSAT) Locations
The CO2 sensors (33ZCSENCO2) factory set for a range of 0 to 2000 ppm and a linear voltage output of 0 to 10 vdc. Figure 19 shows ventilation rates for various CO2 set points when outside air with a typical CO2 level of 350 ppm is used. Refer to the instructions supplied with the CO2 sensor for elec- trical requirements and terminal locations. The zone controller requires 24 vac 25 va transformer to provide power to the sensor.
To convert the CO2 sensor into a
To accurately monitor the quality of the air in the condi- tioned air space, locate the sensor near the return air grille so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact.
Do not mount the space sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return air stream.
5.625
(14.3)
3.25
(8.3)
1.125
(2.9)
5
(12.7)
0.25
(0.8)
To accurately monitor the quality of the air in the return air duct, locate the sensor at least 6 in. upstream or 15 in. down- stream of a 90 degree turn in the duct. The downstream loca- tion is preferred. Mount the sensor in the center of the duct.
IMPORTANT: If the sensor is mounted in the return air duct, readjust the
Fig. 18 — Indoor Air Quality (CO2) Sensor
(33ZCSENCO2)
303 | 24 |