Table 7 — Occupancy Schedule Information Screen
DESCRIPTION | DEFAULT | POINT NAME |
Manual Override Hours | 0 | OVRD |
Period 1: Day of Week | 11111111 | DOW1 |
Period 1: Occupied From | 00:00 | OCC1 |
Period 1: Occupied To | 24:00 | UNOCC1 |
Period 2: Day of Week | 00000000 | DOW2 |
Period 2: Occupied From | 00:00 | OCC2 |
Period 2: Occupied To | 24:00 | UNOCC2 |
Period 3: Day of Week | 00000000 | DOW3 |
Period 3: Occupied From | 00:00 | OCC3 |
Period 3: Occupied To | 24:00 | UNOCC3 |
Period 4: Day of Week | 00000000 | DOW4 |
Period 4: Occupied From | 00:00 | OCC4 |
Period 4: Occupied To | 24:00 | UNOCC4 |
Period 5: Day of Week | 00000000 | DOW5 |
Period 5: Occupied From | 00:00 | OCC5 |
Period 5: Occupied To | 24:00 | UNOCC5 |
Period 6: Day of Week | 00000000 | DOW6 |
Period 6: Occupied From | 00:00 | OCC6 |
Period 6: Occupied To | 24:00 | UNOCC6 |
Period 7: Day of Week | 00000000 | DOW7 |
Period 7: Occupied From | 00:00 | OCC7 |
Period 7: Occupied To | 24:00 | UNOCC7 |
Period 8: Day of Week | 00000000 | DOW8 |
Period 8: Occupied From | 00:00 | OCC8 |
Period 8: Occupied To | 24:00 | UNOCC8 |
If a 1 is configured in the corresponding place for a certain day of the week, the related “Occupied from” and “Occupied to” times for that period will take effect on that day of the week. If a 1 is placed in the holiday field the related times will take effect on a day configured as a holiday. A zero means the schedule period will not apply to that day.
Period |
|
|
Day of Week: | Range | 0 or 1 |
| Default Values | 11111111 for period 1, |
| 00000000 for periods |
Occupied From — This field is used to configure the hour and minute, in military time, when the mode for the zone controller becomes occupied.
Period |
|
Occupied from: Units | Hours: Minutes |
Range | 00:00 to 24:00 |
Default Value | 00:00 |
Occupied To — This field is used to configure the hour and minute, in military time, when the occupied mode for the zone controller becomes unoccupied.
Period |
|
Occupied from: Units | Hours: Minutes |
Range | 00:00 to 24:00 |
Default Value | 24:00 |
SET POINT SCREEN — The Set Point screen is used to modify the zone controller set points. See Table 8.
Occupied Heat — The Occupied Heat set point is used to con- figure the heating set point for the zone controller during Occu- pied mode.
Occupied Heat: Units | F (C) |
Range | 40.0 to 90.0 |
Default Value | 70.0 |
Occupied Cool — The Occupied Cool set point is used to con- figure the cooling set point for the zone controller during Occu- pied mode.
Occupied Cool: Units | F (C) |
Range | 45.0 to 99.9 |
Default Value | 74.0 |
Unoccupied Heat — The Unoccupied Heat set point is used to configure the heating set point for the zone controller during Unoccupied mode.
Unoccupied Heat: Units | F (C) |
Range | 40.0 to 90.0 |
Default Value | 55.0 |
Unoccupied Cool — The Unoccupied Cool set point is used to configure the cooling set point for the zone controller during Unoccupied mode.
Unoccupied Cool: Units | F (C) |
Range | 45.0 to 99.9 |
Default Value | 90.0 |
→Occupied High Humidity — The Occupied High Humidity set point is used to configure the humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.
Occupied High Humidity: Units | % Humidity |
Range | 0.0 to 100.0 |
Default Value | 60.0 |
→Unoccupied High Humidity — The unoccupied high humidi- ty set point is used to configure the unoccupied humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.
Unoccupied |
|
High Humidity: Units | % humidity |
Range | 0 to 100 |
Default Value | 100 |