Table 7 — Occupancy Schedule Information Screen

DESCRIPTION

DEFAULT

POINT NAME

Manual Override Hours

0

OVRD

Period 1: Day of Week

11111111

DOW1

Period 1: Occupied From

00:00

OCC1

Period 1: Occupied To

24:00

UNOCC1

Period 2: Day of Week

00000000

DOW2

Period 2: Occupied From

00:00

OCC2

Period 2: Occupied To

24:00

UNOCC2

Period 3: Day of Week

00000000

DOW3

Period 3: Occupied From

00:00

OCC3

Period 3: Occupied To

24:00

UNOCC3

Period 4: Day of Week

00000000

DOW4

Period 4: Occupied From

00:00

OCC4

Period 4: Occupied To

24:00

UNOCC4

Period 5: Day of Week

00000000

DOW5

Period 5: Occupied From

00:00

OCC5

Period 5: Occupied To

24:00

UNOCC5

Period 6: Day of Week

00000000

DOW6

Period 6: Occupied From

00:00

OCC6

Period 6: Occupied To

24:00

UNOCC6

Period 7: Day of Week

00000000

DOW7

Period 7: Occupied From

00:00

OCC7

Period 7: Occupied To

24:00

UNOCC7

Period 8: Day of Week

00000000

DOW8

Period 8: Occupied From

00:00

OCC8

Period 8: Occupied To

24:00

UNOCC8

If a 1 is configured in the corresponding place for a certain day of the week, the related “Occupied from” and “Occupied to” times for that period will take effect on that day of the week. If a 1 is placed in the holiday field the related times will take effect on a day configured as a holiday. A zero means the schedule period will not apply to that day.

Period (1-8):

 

 

Day of Week:

Range

0 or 1

 

Default Values

11111111 for period 1,

 

00000000 for periods 2-8.

Occupied From — This field is used to configure the hour and minute, in military time, when the mode for the zone controller becomes occupied.

Period (1-8):

 

Occupied from: Units

Hours: Minutes

Range

00:00 to 24:00

Default Value

00:00

Occupied To — This field is used to configure the hour and minute, in military time, when the occupied mode for the zone controller becomes unoccupied.

Period (1-8):

 

Occupied from: Units

Hours: Minutes

Range

00:00 to 24:00

Default Value

24:00

SET POINT SCREEN — The Set Point screen is used to modify the zone controller set points. See Table 8.

Occupied Heat — The Occupied Heat set point is used to con- figure the heating set point for the zone controller during Occu- pied mode.

Occupied Heat: Units

F (C)

Range

40.0 to 90.0

Default Value

70.0

Occupied Cool — The Occupied Cool set point is used to con- figure the cooling set point for the zone controller during Occu- pied mode.

Occupied Cool: Units

F (C)

Range

45.0 to 99.9

Default Value

74.0

Unoccupied Heat — The Unoccupied Heat set point is used to configure the heating set point for the zone controller during Unoccupied mode.

Unoccupied Heat: Units

F (C)

Range

40.0 to 90.0

Default Value

55.0

Unoccupied Cool — The Unoccupied Cool set point is used to configure the cooling set point for the zone controller during Unoccupied mode.

Unoccupied Cool: Units

F (C)

Range

45.0 to 99.9

Default Value

90.0

Occupied High Humidity — The Occupied High Humidity set point is used to configure the humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.

Occupied High Humidity: Units

% Humidity

Range

0.0 to 100.0

Default Value

60.0

Unoccupied High Humidity — The unoccupied high humidi- ty set point is used to configure the unoccupied humidity set point for the zone controller if optional zone humidity control (dehumidification) is used.

Unoccupied

 

High Humidity: Units

% humidity

Range

0 to 100

Default Value

100

1001

36