Table 13 — Linkage Maintenance Screen

DESCRIPTION

DEFAULT

POINT NAME

Air Source Bus Number

0

ASBUSNUM

Air Source Element Number

0

ASDEVADR

Master Zone Element Number

0

MZDEVADR

Operating Mode

OFF

ASOPMODE

Air Source Supply Temperature

0 F

ASTEMP

Start Bias Time

0 minutes

STRTBIAS

Average Occupied Heat Set Point

0.0 F

AOHS

Average Occupied Cool Set Point

0.0 F

AOCS

Average Unoccupied Heat Set Point

0.0 F

AUHS

Average Unoccupied Cool Set Point

0.0 F

AUCS

Average Zone Temperature

0.0 F

AZT

Average Occupied Zone Temperature

0.0 F

AOZT

Composite CCN Value

0

CCCNVAL

Occupancy Status

0

OCCSTAT

Next Occupied Day

(blank)

NXTOCCD

Next Occupied Time

00:00

NXTOCCT

Next Unoccupied Day

(blank)

NXTUNOD

Next Unoccupied Time

00:00

NXTUNOT

Previous Unoccupied Day

(blank)

PREVUNOD

Previous Unoccupied Time

00:00

PRVUNOT

Maximum Damper Position

0.0 %

MAXDMPOS

Static Pressure Reset

0.0 in. wg

PRESVAL

Pressure Decrease Value

0.000 in. wg

PRESDECR

Pressure Increase Value

0.000 in. wg

PRESINCR

Next Unoccupied Day — This variable displays the day when the next associated zone is scheduled to change from occupied to unoccupied mode. This point is read in conjunction with the next unoccupied time to allow the user to know the next time and day when a zone will become unoccupied.

Next Unoccupied

 

 

Day:

Display Range

MON, TUE, WED,

 

 

THU, FRI, SAT, SUN

 

Default Value

No display (Blank)

 

Network Access

None

Next Unoccupied Time — This variable displays the time of day when the next associated zone is scheduled to change from occupied to unoccupied mode. This point is read in conjunction with the next unoccupied day to allow the user to know the next time and day when a zone will become unoccupied.

Next Unoccupied

 

 

Time:

Display Range

00:00 to 24:00

 

Default Value

0:00

 

Network Access

None

Previous Unoccupied Day — This variable displays the day when the last associated zone changed from occupied to unoc- cupied mode. This point is read in conjunction with the previ- ous unoccupied time to allow the user to know the last time and day when a zone became unoccupied.

Previous Unoccupied

 

Day:

Display Range

MON, TUE, WED,

 

 

THU, FRI, SAT, SUN

 

Default Value

No display (Blank)

 

Network Access

None

Previous Unoccupied Time — This variable displays the time of day when the last associated zone changed from occupied to unoccupied mode. This point is read in conjunction with the previous unoccupied day to allow the user to know the last time and day when a zone became unoccupied.

Previous Unoccupied

 

Time:

Display Range

00:00 to 24:00

 

Default Value

0:00

 

Network Access

None

Maximum Damper Position — This variable displays the damper position of the zone controller in the system with the damper in the most open position. This is used by the linkage coordinator to calculate the static pressure reset.

Maximum Damper

 

Position:

Display Units

% (open)

 

Display Range

0.0 to 100.0

 

Default Value

0.0

 

Network Access

Read/Write

Static Pressure Reset — This variable displays the current static pressure reset calculated, using the maximum damper po- sition and the configuration information from the linkage con- figuration table.

Static Pressure

 

 

Reset:

Display Units

in. wg

 

Display Range

0.0 to 5.0

 

Default Value

0.0

 

Network Access

Read/Write

Pressure Decrease Value — If the maximum damper position in the system goes below the minimum configuration setting, the linkage coordinator will calculate an amount that the static pressure should be decreased. This is used to open the system dampers more so that they will modulate between their mini- mum and maximum settings.

This number is rounded to the nearest tenth of an inch and will be added to the static pressure reset value unless the static pressure reset value has reached maximum reset.

Pressure Decrease

 

 

Value:

Display Units

in. wg

 

Display Range

0.000 to 5.000

 

Default Value

0.000

 

Network Access

Read/Write

Pressure Increase Value — If the maximum damper position in the system goes above the maximum configuration setting, the linkage coordinator will calculate an amount that the static pressure should be increased. This is used to close the system dampers more so that they will modulate between their mini- mum and maximum settings.

45