Carrier 33ZCSECTRM, 33ZCFANTRM Start-Up, Perform System Check-Out, Communication Bus Wiring

Models: 33ZCSECTRM 33ZCVAVTRM 33ZCFANTRM

1 52
Download 52 pages 4.39 Kb
Page 29
Image 29
Fig. 25 — Communication Bus Wiring

33ZCSENCHG

(SENSOR)

FLOW

1/2” TUBE 3/4” TUBE 1” TUBE

Fig. 24 — Typical Water Valve and Sensor Installation

1000 FT. MAXIMUM

DRAIN WIRE (TYP)

BLK (TYP)

GND

WHT (TYP)

RED (TYP)

1 2 3

CCN

ZC (TYP)

AIR TERMINAL

UNIT (TYP)

1 2 3

CCN

1 2 3

CCN

1

2

3

CCN

BRIDGE (RECOMMENDED)

1 2 3 4

COMM 2

LEGEND

CCN — Carrier Comfort Network

ZC — Zone Controller

Fig. 25 — Communication Bus Wiring

START-UP

Use the Carrier network communication software to start up and configure the zone controller.

All set-up and set point configurations are factory-set and field-adjustable.

Changes can be made using the ComfortWORKS® soft- ware, ComfortVIEW™ software, or Network Service Tool. The Network Service Tool is a portable interface device that al- lows the user to change system set-up and set points from a zone sensor or terminal control module. During start-up, the Carrier software can also be used to verify communication with each zone controller.

For specific operating instructions, refer to the literature provided with the software.

Perform System Check-Out

1.Check correctness and tightness of all power and com- munication connections.

2.Check that all air terminals, ductwork, and zone con- trollers are properly installed and set according to installation instructions and job requirements.

3.Check that all air duct connections are tight.

4.At the air terminals, check fan and system controls for proper operation. Verify that actuator screws are prop- erly tightened.

5.At the air terminals, check electrical system and con- nections of any optional electric reheat coil. If hot water reheat is used, check piping and valves against job drawings.

6.At the air terminals, make sure that all balancing dampers at box outlets are in the fully open position.

7.If using an air handler with field-installed controls, make sure controls and sensors have been installed and wired per manufacturer installation instructions.

8.At air handlers, verify that the motor starter and, if applicable, the Hand/Off/Auto (HOA) switch are installed and wired.

NOTE: The HOA switch must be in the Off position.

29

800

Page 29
Image 29
Carrier 33ZCSECTRM, 33ZCFANTRM, 33ZCVAVTRM specifications Start-Up, Perform System Check-Out, Communication Bus Wiring