Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM procedure 1.Apply 24 vac power to the control

Models: 33ZCSECTRM 33ZCVAVTRM 33ZCFANTRM

1 52
Download 52 pages 4.39 Kb
Page 30
Image 30
procedure:

9.Check to be sure the area around the air handler(s) is clear of construction dirt and debris.

10.Check that final filters are installed in the air han- dler(s). Dust and debris can adversely affect system operation.

11.Verify that the zone controller and the air handler con- trols are properly connected to the CCN bus.

Before starting the air source fan, make sure that dampers at the system’s air terminals are not fully closed. Starting the fan with dampers closed will result in damage to the system ductwork.

12.Remember to utilize good duct design and to provide sufficient straight duct at the inlet of the box. A mini- mum of three times the inlet size is recommended.

Network Addressing — Use the following method when all the zone controllers are installed and powered, and the SPT sensors are wired and functioning properly. This method can be used if no addresses have been set previously. The ad- dress of an individual zone controller may be set by using the address search function on the Service Tool software when it is directly connected to the service port of the zone controller and the CCN bus is disconnected. This is the standard method of setting the address.

Addresses may also be set using the Service Tool Address Search Function if the zone controller is isolated from the CCN bus.

Each zone controller will default to an address of 0, 140 when its application software is initially loaded. Since multiple controllers will be on the same bus, a unique address must be assigned to each controller before the system can operate prop- erly. The assignment of controller addresses will be performed through software by using the Address Search function of the Network Service Tool, as follows:

1.The software recognizes that the Zone Controller's ad- dress, stored in the zone controller memory, has not been written yet (this will be true when the unit is first powered up on the job, or after a jumper-initiated reset).

2.Press the override button on the SPT (terminals J4-14 and J4-12 are shorted) for 1 to 10 seconds.

3.The zone controller address changes from 0, 140 to 239, 239 for a period of 15 minutes.

4. Use Network Service Tool to change the address from 239, 239 to a valid system address within 15 minutes.

NOTE: If the address is not changed from 239, 239 to a valid system address within 15 minutes, the control- ler will revert to address 0, 140 and use of the override button will cause the address function to repeat. The operator MUST actively set the address even if the final desired address is 0, 140.

Initial Operation and Test — Perform the following

procedure:

1.Apply 24 vac power to the control.

2.Connect the service tool to the phone jack service port of the controller.

3.Using the service tool, upload the controller from address assigned in Network Addressing section above.

4.From the Terminal Service Configuration screen, properly configure the damper type and inlet size. If a round inlet is used, then enter the size directly in the Inlet Diameter decision. If a square, rectangular, or

elliptical damper inlet is supplied, then enter the inlet size in square inches in the Inlet Area decision.

5.If the terminal damper closes in the CW direction, then no adjustment is required. Otherwise, locate the damper direction configuration decision (CW Rota- tion) and toggle the value to OPEN by using the space bar. This configuration decision is also located on the Terminal Service Configuration screen.

6.After entering the area and rotation direction, verify operation of the damper. From the service tool Diag- nostic, Maintenance Screen, select the Zone Air Balance/Commissioning Table and force the Commis- sioning Mode point to Enable. Then select the Damper/Transducer Cal point and force this point to Enable. The controller automatically tests the actuator by fully closing the damper.

It checks the fully closed position to determine if the control was properly mounted. It then opens the damper. The control scales the actual actuator travel range used to a 0 to 100% open value. Finally the con- trol will close the damper, test, and zero the pressure transducer. When completed, the control automatically removes the force from the Damper/Transducer Cal point. If a failure occurs at any point during the testing, the Auto-Calibration point at the bottom of the screen will indicate ALARM and the test will be aborted.

7.The actuator stroke has now been calibrated for the proper rotation.

Airflow Check — After the damper transducer calibration has been performed, the terminal is ready for an airflow check. To perform airflow check, make sure Terminal Type, Primary Inlet Size, and Probe Multiplier settings on the Terminal Ser- vice Configuration screen are configured. If all of the terminals were installed with the dampers open, it is acceptable to start the fan at this time. If it becomes difficult for the air source to provide the necessary static pressure for airflow testing, it may be necessary to calibrate the damper transducer for a majority of terminals and check temperatures and set points to be sure most will be controlling to less than maximum CFM when the air source is started.

When the system fan is running and the static pressure is fairly stable access the Zone Air Balance/Commissioning table and force the Commissioning Mode Point to Enable. The sys- tem is now ready to enable maximum CFM and check if the airflow controls correctly with the maximum CFM set point. Read the Zone Air Balance/Commissioning table section on page 47 which describes the Zone Air Balance/Commissioning table and what adjustments can be made from this screen. If the maximum airflow function is working properly, the user can stop here and leave the rest of the airflow calibration for the air balance contractor.

If working with the air balance contractor, proceed with the minimum airflow calibration at this time. If this terminal is fan powered or the terminal was installed with heat, and the heat configuration was already performed, continue with the fan and heat test while the Zone Air Balance/Commissioning table is still being displayed.

Fan and Heat Configuration and Test — Per- form the following procedure to configure and test the fan and heat:

1.Display the Terminal Service Configuration screen to make sure the proper Terminal Type and Heat Type are configured. See the Configuration section to answer questions about the individual configurations.

2.From the Diagnostics Maintenance Screen select the Zone Air Balance/Commissioning table.

3.Force the Commissioning Mode to Enable.

501

30

Page 30
Image 30
Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications procedure 1.Apply 24 vac power to the control