Fig. 22 — Humidity Sensor Wiring

3.Connect the other end of the communication bus cable to the terminal block labeled CCN in the zone control- ler of the first air terminal. Following the color code in Table 3, connect the Red (+) wire to Terminal 1. Connect the White (ground) wire to Terminal 2. Con- nect the Black (–) wire to Terminal 3.

4.Connect additional zone controllers in a daisy chain fashion, following the color coded wiring scheme in Table 3. Refer to Fig. 25.

NOTE: The communication bus drain wires (shield) must be tied together at each zone controller. If the communica- tion bus is entirely within one building, the resulting contin- uous shield must be connected to ground at only one single point. If the communication bus cable exits from one build- ing and enters another building, connect the shields to ground at a lightning suppressor in each building where the cable enters or exits (one point only).

0

H F 2 3 B J 0 4 2

M a d e i n S w i t z e r l a n d b y B e l i m o A u t o m a t i o n

L R 9 2 8 0 0

NEMA2

LISTED

94D5 U TEMP. IND. & L REG. EQUIP.

Class 2 Supply

5K

WIP

yel blu ora

 

 

3 CONDUCTOR

 

 

 

20 AWG CABLE

 

 

 

RED

 

 

 

WHITE

+

 

 

-

 

 

 

 

 

BLACK

499

 

 

 

 

 

 

RESISTOR

 

 

 

(SUPPLIED

 

 

 

W/SENSOR)

 

 

SHIELD

 

 

 

(IF USED)

HUMIDITY SENSOR

 

 

 

 

 

RH/IAQ

 

 

 

GND

 

 

 

 

+24V

 

 

1

 

35 in-lb (4 Nm)

 

80...110s

 

 

24VAC/DC

 

 

50/60Hz

 

 

3VA

2W

 

 

COM

 

 

 

1

2

3

 

blk

red

wht

 

Fig. 22 — Humidity Sensor Wiring

27