![Fig. 22 — Humidity Sensor Wiring](/images/new-backgrounds/33815/3381553x1.webp)
3.Connect the other end of the communication bus cable to the terminal block labeled CCN in the zone control- ler of the first air terminal. Following the color code in Table 3, connect the Red (+) wire to Terminal 1. Connect the White (ground) wire to Terminal 2. Con- nect the Black
4.Connect additional zone controllers in a daisy chain fashion, following the color coded wiring scheme in Table 3. Refer to Fig. 25.
NOTE: The communication bus drain wires (shield) must be tied together at each zone controller. If the communica- tion bus is entirely within one building, the resulting contin- uous shield must be connected to ground at only one single point. If the communication bus cable exits from one build- ing and enters another building, connect the shields to ground at a lightning suppressor in each building where the cable enters or exits (one point only).
0
H F 2 3 B J 0 4 2
M a d e i n S w i t z e r l a n d b y B e l i m o A u t o m a t i o n
L R 9 2 8 0 0
NEMA2
LISTED
94D5 U TEMP. IND. & L REG. EQUIP.
Class 2 Supply
5K
WIP
yel blu ora
|
| 3 CONDUCTOR |
|
|
| 20 AWG CABLE |
|
|
| RED |
|
|
| WHITE | + |
|
| - | |
|
|
| |
|
| BLACK | 499 |
|
|
| |
|
|
| RESISTOR |
|
|
| (SUPPLIED |
|
|
| W/SENSOR) |
|
| SHIELD |
|
|
| (IF USED) | HUMIDITY SENSOR |
|
|
| |
|
| RH/IAQ |
|
|
| GND |
|
|
|
| +24V |
|
| 1 |
|
35 |
| ||
80...110s |
|
| |
24VAC/DC |
|
| |
50/60Hz |
|
| |
3VA | 2W |
|
|
COM |
|
|
|
1 | 2 | 3 |
|
blk | red | wht |
|
Fig. 22 — Humidity Sensor Wiring
27