Carrier 33ZCVAVTRM, 33ZCFANTRM → - Set Point Screen, Airflow Service Configuration Screen

Models: 33ZCSECTRM 33ZCVAVTRM 33ZCFANTRM

1 52
Download 52 pages 4.39 Kb
Page 37
Image 37

Air Quality — The Air Quality set point is used to configure the IAQ set point for the zone controller if optional controlled ventilation support is used.

Air Quality

Units

none shown (ppm

(ppm):

 

implied)

 

Range

0 to 5000

 

Default Value

850

Delta Airflow — The Delta Airflow set point is used to con- figure the Delta Airflow set point for the zone controller if the zone pressure control option is used. If a negative pressure is desired, configure the value as a positive delta.

Delta Airflow:

Units

cfm

 

Range

-9999 to 9999

 

Default Value

0

Service Configuration Selection Screen — The Service Configuration Selection screen is a menu of Service screens which can be accessed by the user. The following screens are available: Airflow Service Configuration, Terminal Service Configuration, Option Service Configuration, and Sec- ondary Damper Service Configuration.

AIRFLOW SERVICE CONFIGURATION SCREEN — The Airflow Service Configuration Table is used to configure the pressure independent and backup pressure dependent set points. See Table 9.

Pressure Independent — Pressure Independent (PI) set points should be configured for pressure independent operation applications.

Cool Minimum (PI) — This configuration is the minimum airflow the terminal will control to when the equipment is in Cooling mode (or Fan Only mode) or free cooling. The space requirements for cooling must be at a minimum, or the terminal is a fan powered terminal and the space requirements are for heat.

Cool Minimum: Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)

Default Value

0

Cool Maximum (PI) — This configuration is the maximum airflow the terminal will control to when the equipment is in Cooling mode (or Fan Only mode) or free cooling and the space requirements for cooling are at a maximum.

Cool Maximum: Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)

Default Value

4000

Terminal Reheat (PI) — This configuration is for single duct units with ducted reheat. The desired airflow is configured at which the reheat will provide optimum performance. This val- ue is compared to the Minimum Cool value and the greater of the two values is used to determine the airflow set point.

Terminal Reheat: Units

CFM

Range

0 to 9999 (Limited by

the High Velocity pressure limit alarm)

Default Value

0

Table 8 — Set Point Screen

DESCRIPTION

DEFAULT

POINT NAME

Set Points

 

 

Occupied Heat

70.0 F

OHSP

Occupied Cool

74.0 F

OCSP

Unoccupied Heat

55.0 F

UHSP

Unoccupied Cool

90.0 F

UCSP

Occupied HIgh Humidity

60.0 %

ORHH

Unoccupied High Humidity

100 %

URHH

Air Quality (ppm)

850 ppm

AQSP

Delta Airflow

0 cfm

DCFM

Table 9 — Airflow Service Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

Pressure Independent

 

 

Cool Minimum

0 cfm

COOLMIN

Cool Maximum

4000 cfm

COOLMAX

Terminal Reheat

0 cfm

REHEAT

Heat Minimum

0 cfm

HEATMIN

Heat Maximum

4000 cfm

HEATMAX

Parallel Fan On

0 cfm

FNONCFM

Dual Duct CV Airflow

4000 cfm

DDCVFLOW

Pressure Dependent

 

 

Cool Minimum Position

0 %

CMINPOS

Cool Maximum Position

100 %

CMAXPOS

Reheat Minimum Position

0 %

REMINPOS

Heat Minimum Positon

0 %

HMINPOS

Heat Maximum Position

100 %

HMAXPOS

Deadband Percent

12.5 %

DB_PCT

37

1001

Page 37
Image 37