Fig. 19 — Ventilation Rated Based on
CO2 Set Point
Indoor Air Quality Sensor Wiring — To wire the sensors after they are mounted in the conditioned air space and return air duct, see Fig. 20 and the instructions shipped with the sen- sors. For each sensor, use two
HUMIDITY SENSOR
The use of a standard 2- x
If the sensor is installed directly on a wall surface, install the humidity sensor using 2 screws and 2 hollow wall anchors
Do NOT clean or touch the sensing element with chemical solvents; they can permanently damage the sensor.
The sensor must be mounted vertically on the wall. The Carrier logo should be oriented correctly when the sensor is properly mounted.
DO NOT mount the sensor in drafty areas such as near heat- ing or
Avoid corner locations. Allow at least 4 ft between the sen- sor and any corner. Airflow near corners tends to be reduced, resulting in erratic sensor readings.
Sensor should be vertically mounted approximately 5 ft up from the floor, beside the space temperature sensor.
For distances up to 500 feet, use a
The power for the sensor is provided by the control board. The board provides 24 vdc for the sensor. No additional power source is required.
To wire the sensor, perform the following:
1.At the sensor, remove
2.Connect the RED wire to the sensor screw terminal marked (+).
3.Install one lead from the resistor (supplied with the sensor) and the WHITE wire, into the sensor screw ter- minal marked
4.Connect the remaining lead from the resistor to the BLACK wire and secure using a closed end type crimp connector or wire nut.
5.Using electrical tape, insulate any exposed resistor lead to prevent shorting.
6.At the control box, remove the jacket from the cable and route the RED conductor over to the left side of the control board. Route the remaining conductors to the right side of the control board.
0
H F 2 3 B J 0 4 2
M a d e i n S w i t z e r l a n d b y B e l i m o A u t o m a t i o n
L R 9 2 8 0 0
NEMA 2
LISTED
94D5 U TEMP. IND. & L REG. EQUIP.
Class 2 Supply
5K
WIP
yel blu ora
|
| RH/IAQ |
|
| GND |
|
| 1 |
35 | ||
80...110s |
| |
24VAC/DC |
| |
50/60Hz |
| |
3VA | 2W |
|
COM |
|
|
1 | 2 | 3 |
blk | red | wht |
21 |
| 87 |
24 VAC | LINE | |
VOLTAGE | ||
|
SEPARATE
ISOLATED
POWER
SUPPLY
REQUIRED
(24 VAC, 25 VA
MINIMUM)
*Do not connect to the same transformer that supplies power to the zone controller.
→Fig. 20 — Indoor Air Quality Sensor Wiring
25 | 303 |