Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications → - Zone Air Balance/Commissioning Table

Models: 33ZCSECTRM 33ZCVAVTRM 33ZCFANTRM

1 52
Download 52 pages 4.39 Kb
Page 48
Image 48

Table 15 — Zone Air Balance/Commissioning Table

DESCRIPTION

DEFAULT

POINT NAME

Commissioning Mode

Dsable

CMODE

Damper/Transducer Calibration

Dsable

CALIBRAT

Maximum Cooling

Dsable

MAXCOOL

Minimum Cooling

Dsable

MINCOOL

Heating Override

Dsable

HEATOVER

Fan Override

Dsable

FANOVER

CFM Set Point

0 cfm

COMCFM

Actual Airflow

0 cfm

AIRFLOW

Primary Damper Position

100 %

DMPPOS

Measured Velocity Pressure

0.000 in. wg

MVP

Supply Air Temperature

0.0 F

SAT

Auto-Calibration

Normal

CAL

Calibration Gain

1.000

CAL_GAIN

Heating Override — This variable can be used to test the heat outputs. Enabling this variable will cause the heat to be modu- lated or staged to full heat until this point is disabled or the force released. Ducted reheat operation will be controlled so as not to exceed the configured maximum duct temperature. The supply-air temperature is included on this screen to verify that the heat is operating.

Heating Override: Display Range

Dsable/Enable

Default Value

Dsable

Network Access

Read /Write

Airflow CFM Set Point — This variable displays the current airflow set point that the zone controller is controlling to. Dur- ing the calibration tests this value can be forced, which will change the set point configuration for the value being tested.

Airflow CFM

 

 

Set Point:

Display Units

CFM

 

Display Range

0 to 9999 (Limited by

 

velocity pressure transducer high alarm

 

limit)

 

 

Default Value

0

 

Network Access

Read /Write

Actual Airflow Display — This variable shows the actual air- flow being measured, based on the inlet size configured. Dur- ing the Maximum and Minimum Cooling Airflow calibration tests this value can be forced, which will correct the multiplier or offset used to calculate the airflow.

Actual Airflow: Display Units

CFM

Display Range

0 to 9999 (Limited by

velocity pressure transducer high alarm

limit)

 

Default Value

0

Network Access

Read /Write

Primary Damper Position — This variable displays the cur- rent damper position. During CFM Balancing, this variable is used to display the position of the damper. This value can be used to see if the damper is fully open and the system air is sufficient.

Primary Damper

 

 

Position:

Display Units

% (open)

 

Display Range

0 to 100

 

Default Value

100

 

Network Access

Read Only

Measured Velocity Pressure — This variable displays the measured velocity pressure, which is used to check accuracy during test and balancing of the terminal. If the pressure appears to be much different than that measured with a Magna- helic gage, the transducer can be forced to recalibrate its zero by enabling the Damper/Transducer Calibration.

Measured Velocity

 

 

Pressure:

Display Units

in. wg

Display Range 0.000 to 2.000 (Limited by velocity pressure transducer high alarm limit)

Default Value

0.000

Network Access

Read Only

Supply-Air Temperature — This variable displays the supply- air temperature for ease of verifying the heat operation during the heat test.

Supply-Air

 

 

Temperature:

Display Units

F (C)

 

Display Range

-40.0 to 245.0

 

Default Value

0.0

 

Network Access

Read /Write

Auto-Calibration — This variable will display “Normal” if the actuator and airflow transducer calibrations are successful. If damper or transducer calibration was not successful, this point will display “Alarm” and the zone controller will broadcast the appropriate alarm (if configured to transmit alarms).

Auto-Calibration: Display Range

Normal/Alarm

Default Value

Normal

Network Access

Read Only

Calibration Gain — Air terminal testing by industry standards is done with straight duct, upstream of the terminal. Since most applications are not installed in this manner, the actual airflow from the terminal, at balancing, may not equal the reading from the zone controller.

The Calibration Gain is used for making fine tuning adjust- ments to the airflow calculation. This number is calculated au- tomatically by the zone controller after input to the air balance maintenance screen. The Calibration Gain can also be entered manually in the service configuration CONFIG screen.

A number of .95 entered into the Calibration Gain variable will cause the maximum airflow to be reduced to 95% of the calculated value. A number of 1.05 would cause readings to become 5% higher. The Calibration Gain is adjusted on the Air Balance maintenance screen when performing the Maximum Airflow Calibration and will have the greatest affect on the air- flow at maximum CFM.

After performing the air balance procedure using the air bal- ance maintenance screen, it is recommended to upload and save the Airflow Configuration, Calibration Gain, and Offset settings.

Calibration Gain: Display Range

0.000 to 9.999

Default Value

1.000

Network Access

Read Only

501

48

Page 48
Image 48
Carrier 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM specifications → - Zone Air Balance/Commissioning Table