Carrier 33ZCSECTRM, 33ZCFANTRM, 33ZCVAVTRM specifications Heat Master

Models: 33ZCSECTRM 33ZCVAVTRM 33ZCFANTRM

1 52
Download 52 pages 4.39 Kb
Page 50
Image 50

Heat Master Reference — This point displays the occupied heat set point if occupied, or the unoccupied heat set point if unoccupied. This variable will display any space temperature sensor slidebar offset that is being applied.

Heat Master

 

 

Reference:

Display Units

F (C)

 

Display Range

40.0 to 90.0

 

Default Value

55.0

 

Network Access

Read/Write

Heat Submaster Reference — If heat is enabled, this variable displays the desired supply air temperature calculated to heat the space. This is a result of the heating PID loop calculation.

Heat Submaster

 

 

Reference:

Display Units

F (C)

 

Display Range

0 to 240

 

Default Value

0

 

Network Access

Read/Write

Temperature Control Airflow — This variable displays the airflow set point determined from the temperature loop calcula- tion. The zone controller compares the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary damper airflow reference.

Temperature

 

Control Airflow: Display Units

%

Display Range

0 to 100

Default Value

100

Network Access

Read Only

Relative Humidity Control Airflow — This variable dis- plays the airflow set point determined from the relative humidity loop calculation. The zone controller compares the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary damper airflow reference.

Relative Humidity

 

Control Airflow: Display Units

%

Display Range

0 to 100

Default Value

0

Network Access

Read Only

Air Quality Control Airflow — This variable displays the air- flow set point determined from the air quality loop calculation. The zone controller compares the Temperature, Relative Humidity, and Air Quality loop. The greatest of the three will become the primary damper airflow reference.

Air Quality

 

Control Airflow: Display Units

%

Display Range

0 to 100

Default Value

0

Network Access

Read Only

Cooling in Effect — This variable displays if the air source is in the Cooling mode and if the terminal is using the cooling air- flow set points.

Cooling In Effect: Display Range

No/Yes

Default Value

Yes

Network Access

Read Only

Heating in Effect — This variable displays if the air source is in the Heat mode and if the terminal is using the heating air- flow set points.

Heating In Effect: Display Range

No/Yes

Default Value

No

Network Access

Read Only

Relative Humidity Control in Effect — This variable indi- cates if the relative humidity control is active.

Relative Humidity

 

Control In Effect: Display Range

No/Yes

Default Value

No

Network Access

Read Only

Air Quality Control in Effect — This variable indicates if the air quality control is active.

Air Quality

 

Control In Effect: Display Range

No/Yes

Default Value

No

Network Access

Read Only

Unoccupied Dehumidification — This variable indicates if unoccupied dehumidification control is in effect.

Unoccupied

 

Dehumidification: Display Range

Yes/No

Default Value

No

Network Access

Read Only

Cooling Energy — This variable displays the amount of pri- mary air source cooling BTUs being provided to the space by the terminal. A CCN compatible air source or PAT sensor on a linkage master is required.

Cooling Energy: Display Units

Btu

Display Range

0 to 999999

Default Value

0

Network Access

Read Only

Heating Energy — This point displays the amount of primary air source heating BTUs being provided to the space by the ter- minal. This value will not include zone level heating. A CCN compatible air source or PAT sensor on a linkage master is required.

Heating Energy: Display Units

Btu

Display Range

0 to 999999

Default Value

0

Network Access

Read Only

801

50

Page 50
Image 50