GENERAL
The zone controller is a single duct, fan powered, Variable Air Volume (VAV) terminal control with a
The VAV Fan Terminal Zone Controller (33ZCFANTRM) provides dedicated control functions for series fan or parallel fan powered terminals, single duct terminals with 3 stages of heat, or as a primary controller for dual duct or zone pressure control applications.
The Single Duct Air Terminal Zone Controller (33ZCVAVTRM) provides dedicated control functions for sin- gle duct terminals with modulating heat or up to 2 stages of heat.
When the VAV Fan Terminal Zone Controller is used in conjunction with a secondary terminal and the 33ZCSECTRM secondary terminal zone controller, either dual duct or zone pressurization applications can be supported.
Carrier’s Linkage system is an integrated combination of Carrier Comfort Network (CCN) controllers for use with Sin- gle Duct air terminals and VAV Fan Powered terminals. The Single Duct air terminal and VAV Fan terminal zone control- lers are part of the Carrier ComfortID system.
Devices manufactured by Carrier which have Product Inte- grated Controls on the same communication bus as the zone controller, air handlers (such as the 39L,T), or large rooftop units do not require an external controller to function as part of a Carrier linkage system. These air handlers or large rooftop units feature
INSTALLATION
General — The zone controller is a
Each zone controller has the ability to function as a linkage coordinator for systems with up to 128 zones. As a linkage co- ordinator, a zone controller will retrieve and provide system in- formation to the air handling equipment and other zone con- trollers. A zone controller can function as a stand alone device by installing a primary supply air sensor.
The zone controller monitors differential pressure from an airflow pickup (or a pair of pickups) mounted on the terminal box. It compares the resulting signal to an airflow set point in order to provide
The zone controller is connected to a
On
Carrier’s Network Service Tool can be connected to the sys- tem at the SPT sensor if CCN communication wiring is run to
the SPT sensor. The Network Service Tool can be used to ad- just set points, set operating parameters, and fully configure the zone controller or any device on the system.
Zone Controller Hardware — The zone controller
consists of the following hardware:
•terminal control module
•
•airflow transducer (velocity sensor)
•plastic enclosure
•one no. 8 x
NOTE: A filter is not provided for the airflow transducer. For installations on systems with a high degree of impuri- ties, an air filter can be purchased and installed on the trans- ducer high pressure pickup.
Figure 2 shows the zone controller physical details. Figures
•air terminal unit
•space temperature sensor
•transformer — 24 vac, 40 va
•two no. 10 x
•two no.
•contactors (if required for fan or electric heat)
•supply air temperature sensor (required for terminal with ducted heat)
•indoor air quality sensor (if required)
•relative humidity sensor (if required)
•one SPST (for each stage of electric heat, not required for Carrier fan terminals)
•valve and actuator for hot water heat (if required)
•delta pressure airflow pickup
NOTE: When selecting an airflow pickup, it is the designer's responsibility to select a sensor that provides the desired output at the design airflow.
•wire
•polyethylene tubing (for pressure pickup)
•bushings (required when mounting SAT sensor in a duct
•primary air temperature sensor (if required)
SPACE TEMPERATURE SENSOR — Each zone control- ler requires a
•33ZCT55SPT, Space Temperature Sensor with Override Button
•33ZCT56SPT, Space Temperature Sensor with Override Button and Set Point Adjustment
PRIMARY AIR TEMPERATURE SENSOR — A field- supplied, primary air temperature (PAT) sensor (part number 33ZCSENPAT) is used on a zone controller which is function- ing as a Linkage Coordinator for a non CCN/Linkage compati- ble air source.
SUPPLY AIR TEMPERATURE (SAT) SENSOR — On
2