Samsung AQ12TSBX, AQ24TSBXEUR manual Each wire is labeled with the corresponding terminal number

Page 29

2 . Open the front grille.

3 . Remove the screw securing the connector cover.

4 . Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals. (Refer to the picture below)

• Each wire is labeled with the corresponding terminal number.

5 . Pass the other end of the cable through the 65mm hole in the wall.

6 . Close the connector cover by tightening the screw carefully.

7 . Close the front grille.

8 . Remove the terminal board cover on the side of the outdoor unit. 9. Connect the cables to the terminals as seen in the picture.

• Each wire is labeled with the corresponding terminal number.

ENGLISH

Indoor unit

Outdoor unit

09/12/18

Indoor unit

Ground wire

(Green/Yellow)

Ground wire (Green/Yellow)

Outdoor unit

24

Indoor unit

Ground wire

 

(Green/Yellow)

Ground wire

Outdoor unit

(Green/Yellow)

 

• End of the wire must be circular.

• After connecting the cables, make sure terminal numbers on the indoor/outdoor unit matches.

Screws on terminal block must not be unscrewed with the torque less than 12kgf•cm.

10.Connect the grounding conductor to the grounding terminals.

11.Close the terminal board cover by tightening the screw carefully.

• In Russia and Europe, consult with the supply authority to determine the supply system impedance before

installation.

• Connect the wires firmly so that wires can not be pulled out easily. (If they are loose, it could cause burn-out of the wires.)

Connect the wires according to color codes, referring to the wiring diagram.

The power cable and the interconnection cable should be selected according to the specification in page 28.

29

Boracay EUR_AQ09T&U@_IBIM_32447A_EN-4.indd 29

2015/7/7 14:56:38

Image 29 Contents
Boracay EURAQ09T&U@IBIM32447AEN-4.indd 2015/7/7 Contents Important safety symbols and precautions Safety precautionsFollow directions Wall socketFor Using For Cleaning Operation ranges Checking before useChecking the name of the parts PowerMain parts  09/12/18/24T  Display  09/12/18/24TRemote controller buttons Checking the remote controllerBattery changing time Remote controller displayStoring the remote controller IndicatorBasic function Low Med High AutoAuto Low Med High Using the Turbo function Adjusting the air flow directionPress the Air swing button on the remote controller Vertical air flowPress the button on the remote controller When the air conditioner is on and in cool/heat modeMode Press the Time Up or Time Down button to set the timeAdditional options available in On timer mode Setting the On/Off timerPress the On Timer/Off Timer button From the moment you have set the timer Using the Smart Saver functionIf the air conditioner is on If the air conditioner is off Turn off automatically09/12/18/24T 09/12/18/24U Using the Auto Clean functionWhen the air conditioner is turned on Cleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger Opening the panelRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaPeriodical checks Maintaining the air conditionerTroubleshooting Connection Outdoor unit Heat exchanger during Heat mode in winterFlow movement changes. It is normal General information Installing the unit Choosing the installation locationPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyModel Where sulfide gas existsOutdoor Unit When the air outlet is towards the wall When installing more than 1 outdoor unit Figure Description Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Each wire is labeled with the corresponding terminal number Cut off the remaining foam insulation Smooth the cut edgesTorque Cutting or extending the pipe Purging the indoor unitUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCorrect Inclined Pipe 50 Pa. The joint must be accessible and serviceableCracked DitchDrain hose installation Connect a drain hose to the drain plug Purging the connected pipesEnsure that condensation draining is adequate Outer TorqueAdding Refrigerant Gas service port as seen in the pictureIf you use a pipe longer than 5m If you use a pipe shorter than 5m1975 Please fill in with indelible ink the factory refrigerant charge of the product Tightening torque Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test after opening valvesFixing the outdoor unit in place Then place the indoor unit on the installation plateFixing the indoor unit in place Final Check and Trial Operation Apply heat to the contraction tube to contract it How to connect your extended power cablesAfter tube contraction work is completed, wrap it with Insulation tape to finishMemo Questions or COMMENTS? Thank you for purchasing this Samsung product Air Conditioner
Related manuals
Manual 43 pages 7.84 Kb Manual 21 pages 37.46 Kb Manual 43 pages 50.34 Kb Manual 43 pages 54.35 Kb Manual 41 pages 57.34 Kb Manual 43 pages 47.11 Kb Manual 41 pages 21.89 Kb Manual 21 pages 33.89 Kb Manual 43 pages 20.03 Kb Manual 43 pages 57.8 Kb Manual 39 pages 24.04 Kb Manual 41 pages 16.8 Kb Manual 41 pages 21.55 Kb Manual 21 pages 17.82 Kb Manual 40 pages 16.42 Kb Manual 41 pages 7.22 Kb Manual 41 pages 49.92 Kb Manual 41 pages 32.45 Kb Manual 41 pages 26.36 Kb Manual 41 pages 36.71 Kb Manual 41 pages 46.99 Kb Manual 41 pages 14.18 Kb Manual 41 pages 8.52 Kb