Samsung AQ12UGFNEUR, AQ18UGAN, AQ24TSBXEUR manual Correct Inclined, Cracked, Outer Diameter, Ditch

Page 32

Cutting or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 34~36.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must not be bent.

The drain hose must NOT slant upwards.

5cm

less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

The end of the drain hose must NOT be placed under water.

Ditch

Do not place the end of the drain hose in a hollow.

32

Boracay EUR_AQ09T&U@_IBIM_32447A_E.indd 32

2011-3-19 10:08:16

Image 32 Contents
Boracay EURAQ09T&U@IBIM32447AE.indd 2011-3-19 Contents Safety precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning Checking before use Operation rangesPower Checking the name of the partsMain parts  09/12/18/24T  Display  09/12/18/24TChecking the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller IndicatorBasic function Low Med High AutoAuto Low Med High Adjusting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowWhen the air conditioner is on and in cool/heat mode Press the button on the remote controllerMode Press the Time Up or Time Down button to set the timeAdditional options available in On timer mode Setting the On/Off timerPress the On Timer/Off Timer button Using the Smart Saver function Combining On Timer and Off Timer09/12/18/24T 09/12/18/24U Using the Auto Clean functionWhen the air conditioner is turned on Cleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Connection Outdoor unit Heat exchanger during Heat mode in winterFlow movement changes. It is normal General information Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyModel Where sulfide gas existsOutdoor Unit When installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Each wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flarePipe 50 Pa. The joint must be accessible and serviceable Correct InclinedCracked Outer DiameterDrain hose installation Ensure that condensation draining is adequate Purging the connected pipesConnect a drain hose to the drain plug Adding Refrigerant 1975 Please fill in with indelible ink the factory refrigerant charge of the product Performing the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesFixing the outdoor unit in place Then place the indoor unit on the installation plateFixing the indoor unit in place Final Check and Trial Operation How to connect your extended power cables Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with Insulation tape to finishMemo 42 27 7267864, € 0.07/min70 70 19 +381Air Conditioner
Related manuals
Manual 43 pages 7.84 Kb Manual 21 pages 37.46 Kb Manual 43 pages 50.34 Kb Manual 43 pages 54.35 Kb Manual 41 pages 57.34 Kb Manual 43 pages 47.11 Kb Manual 41 pages 21.89 Kb Manual 21 pages 33.89 Kb Manual 43 pages 20.03 Kb Manual 43 pages 57.8 Kb Manual 39 pages 24.04 Kb Manual 41 pages 16.8 Kb Manual 41 pages 21.55 Kb Manual 21 pages 17.82 Kb Manual 40 pages 16.42 Kb Manual 41 pages 7.22 Kb Manual 41 pages 49.92 Kb Manual 41 pages 32.45 Kb Manual 41 pages 26.36 Kb Manual 41 pages 36.71 Kb Manual 41 pages 46.99 Kb Manual 41 pages 14.18 Kb Manual 43 pages 51.4 Kb Manual 31 pages 36.44 Kb Manual 32 pages 17.61 Kb Manual 32 pages 60.27 Kb Manual 30 pages 51.71 Kb Manual 32 pages 35.17 Kb Manual 32 pages 6.86 Kb Manual 34 pages 7.54 Kb Manual 32 pages 51.3 Kb Manual 33 pages 17.1 Mb Manual 31 pages 55.87 Kb Manual 31 pages 51.06 Kb Manual 41 pages 8.52 Kb