Thomas & Betts UDAS, UDAP dimensions Unit Heater Location cont’d, Hanging the Heater

Page 10

10.Unit Heater Location (cont’d)

NOTE: Venting requirements may affect location. Consult the Venting Manual for this heater before making final determination.

Hazards of Chlorine - applies to location of Model UDAS heater with regard to combustion air inlet

For best results, the heater should be placed with certain rules in mind. In general, a unit should be located from 8 to 12 feet (2.4-3.7M) above the floor. Units should always be arranged to blow toward or along exposed wall surfaces, if possible. Where two or more units are installed in the same room, a general scheme of air circulation should be maintained for best results.

Suspended heaters are most effective when located as close to the working zone as possible, and this fact should be kept in mind when determining the mounting heights to be used. However, care should be exercised to avoid directing the dis- charged air directly on the room occupants.

Partitions, columns, counters, or other obstructions should be taken into consider- ation when locating the unit heater so that a minimum quantity of airflow will be deflected by such obstacles.

When units are located in the center of the space to be heated, the air should be discharged toward the exposed walls. In large areas, units should be located to discharge air along exposed walls with extra units provided to discharge air in toward the center of the area.

At those points where infiltration of cold air is excessive, such as at entrance doors and shipping doors, it is desirable to locate the unit so that it will discharge directly toward the source of cold air from a distance of 15 to 20 feet (4.6-6.1M).

CAUTION: Do not locate the heater where it may be exposed to water spray, rain, or dripping water.

The presence of chlorine vapors in the combustion air of gas-fired heating equip- ment presents a potential corrosion hazard. Chlorine found usually in the form of freon or degreaser vapors, when exposed to flame will precipitate from the com- pound, and go into solution with any condensation that is present in the heat ex- changer or associated parts. The result is hydrochloric acid which readily attacks all metals including 300 grade stainless steel. Care should be taken to separate these vapors from the combustion process. This may be done by wise location of the unit vent and combustion air terminals with regard to exhausters or prevailing wind directions. Chlorine is heavier than air. Keep these facts in mind when deter- mining installation location of the heater in relation to building exhaust systems.

11.Hanging the Heater

WARNINGS: Check the supporting structure to be used to verify that it has sufficient load carry- ing capacity to support the weight of the unit. Suspend the heater only from the threaded nut retainers or with a man- ufacturer provided kit. Do NOT suspend from the heater cabinet.

Before suspending the heater, check the supporting structure to be used to verify that it has sufficient load-carrying capacity to support the weight of the unit.

Model UDAP

Size

30

45

60

75

100

125

150

175, 200

225

250

300

350

400

lbs

54

59

67

72

96

101

172

187

203

215

269

294

306

kg

24

27

30

33

44

46

78

85

92

98

122

133

139

Model UDAS

 

 

 

 

 

 

 

 

 

 

 

Size

30

45

60

75

100

125

150

175, 200

225

250

300

350

400

lbs

55

60

68

73

97

102

173

188

204

216

270

295

307

kg

25

27

31

33

44

46

78

85

93

98

122

134

138

When the heater is lifted for suspension, support the bottom of the heater with plywood or other appropriately placed material. If the bottom is not supported, damage could occur. Before hanging, verify that all screws used for holding ship- ping brackets were re-installed in the cabinet.

The heater is equipped for either two-point or four-point suspension. A 3/8"-16 threaded nut retainer is located at each suspension point. See Dimensions in Para- graph 5 and the illustration in FIGURE 7A.

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 10

Image 10
Contents Table of Contents Series Fan-Type Unit HeatersHazard Levels of Warnings in this Manual Installation CodesGeneral Venting Manual by ModelWarranty Uncrating and Preparation Massachusetts RequirementDimensions SizeModel Udas Separated Combustion Fan Technical Data Size 100 125High Altitude Operation Instructions for Changing Pressure SwitchPressure Switch ClearancesCombustion Air applies to Model Udap and Model Model Udap and Model UDAP-CVHeater Throw Unit Heater LocationLocation Recommendations Model Udap Size 100 125 150 175 225 250 300 350 400 Unit Heater Location cont’dHanging the Heater Model Udas Size 100 125 150 175 225 250 300 350 400Be sure Threaded swivel Connectors areRecommended maximum hanger rod length is 6 feet 1.8M Locked toSizing Gas Supply Line Gas Piping and PressuresGas Connection Size Instructions Instructions for High Altitude Derate Manifold Pressure Settings by Altitude for CanadaGas Piping and Pressures cont’d Two -Stage ValveHigh Altitude Capacity Changes Feet MetersBurner Electrical Supply and Connections Thermostat and ConnectionsCombustion Air Proving Switch Pressure Switch Combustion Air Proving Pressure Switch SettingsLimit Control Normal Heat Cycle Operating Sequence Door Switch Model Udas only Ignition SystemDip Switch StatusLED LightsIgnition System cont’d SW1 SW2 TimeContinuous Fan Operation Fault Modes Fault Modes cont’d Lockout Gas Valve Fan MotorWiring Diagrams Operating SequenceWiring Diagrams cont’d SW1 Check the installation prior to startup Heater Startup Check Installation and StartupOperating Instructions Operating Sequence Check installation after startup Vent System Testing Procedure Model UdapStartup cont’d Maintenance ScheduleUse only factory-authorized parts Heat Exchanger Maintenance Burner Maintenance Burner Removal Instructions Refer to FigureInstructions to Re-Install the Burner Refer to Figure Burner Maintenance cont’dInspect and Clean the Burner Re-Install the Burner Burner OrificeDSI Cont’d IgnitionSystem Fan BladesOperating Gas Valve Combustion Air Pressure SwitchDoor Switch Udas onlyAir System Troubleshooting Flame Rollout Switch Sizes 30-125 onlySwitch DisconnectWill not start General TroubleshootingVenter motor Burner willTroubleshooting cont’d Cont’d

UDAP, UDAS specifications

Thomas & Betts is a well-respected name in the electrical and industrial products sector, known for its innovation and quality. Among its impressive portfolio, the UDAS and UDAP series of connectors stand out for their reliable performance and advanced features. These connectors are specifically designed to meet the rigorous demands of electrical applications in various industries.

The UDAS (Universal Disconnect Appliance Switch) and UDAP (Universal Disconnect Appliance Plug) are engineered for high-capacity applications where safety, efficiency, and ease of use are paramount. One of the main features of these connectors is their ability to deliver increased electrical resistance and durability. They are constructed from high-quality materials that can withstand extreme environmental conditions, making them ideal for outdoor and harsh industrial applications.

Another key technology employed in the UDAS and UDAP series is the quick-connect mechanism. This innovative design allows users to connect and disconnect circuits swiftly without requiring excessive force or complex tools. This is particularly beneficial in settings where downtime must be minimized and efficiency is crucial. Additionally, the connectors are designed to provide a secure, locking fit to ensure consistent electrical contact, thereby enhancing operational safety.

The UDAS and UDAP connectors are manufactured to comply with several industry standards, ensuring that they meet or exceed the requirements for electrical safety and performance. Their user-centric design features help in reducing installation time and costs, making them a preferred choice among contractors and engineers.

Furthermore, these connectors are versatile, compatible with a wide range of electrical systems, and can be employed in applications such as HVAC, lighting, and power distribution. They also come in various sizes and configurations to accommodate diverse specifications, improving customization options for different projects.

In summary, the Thomas & Betts UDAS and UDAP series stands out for their robust design, quick-connect technology, and versatility across various industrial applications. Their durability and compliance with safety standards make them an excellent choice for professionals seeking reliable connectivity solutions in demanding environments. Investing in these connectors ensures optimal performance and safety in electrical installations, showcasing Thomas & Betts' commitment to excellence in electrical components.