Thomas & Betts UDAS Combustion Air applies to Model Udap and Model, Model Udap and Model UDAP-CV

Page 8

9.Combustion Air - applies to Model UDAP and Model

UDAP-CV

(Note: For Model UDAS, see Venting Manual for combustion air requirements.)

This heater must be supplied with the air that enters into the combustion process and is then vented to the outdoors. Sufficient air must enter the equipment location to replace that exhausted through the heater vent system. In the past, the infiltra- tion of outside air assumed in heat loss calculations (one air change per hour) was assumed to be sufficient. However, current construction methods using more insu- lation, vapor barriers, tighter fitting and gasketed doors and windows, weather- stripping, and/or mechanical exhaust fans may now require the introduction of outside air through wall openings or ducts.

The requirements for combustion and ventilation air depend upon whether the unit is located in a confined or unconfined space. An "unconfined space" is defined as a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed appliance. Under ALL conditions, enough air must be provided to ensure there will not be a negative pressure condition within the equipment room or space.

WARNING: Model UDAP and UDAP-CV power-vented unit heaters are designed to take combustion air from the space in which the unit is installed and are not designed for connection to outside combustion air intake ducts. Connecting outside air ducts voids the warranty and could cause hazardous operation. See Hazard Levels, page 2.

Combustion Air Requirements for a Heater Located in a Confined Space - applies to

Do not install a unit in a confined space without providing wall openings leading to and from the space. Provide openings near the floor and ceiling for ventilation and air for combustion as shown in FIGURE 5, depending on the combustion air source as noted in Items 1, 2, and 3 below.

Add total BTUH of all appliances in the confined space and divide by figures below for square inch free area size of each (top and bottom) opening.

Model UDAP and Model UDAP-CV

FIGURE 5 - Definition of Confined Space and Required Openings for Combustion Air

Confined Space:

A space whose volume is less than 50 cubic feet per 1000 BTUH of the installed appliance input rating

(3)

(1)

(2)

Confined

Space

(3) (1) (2)

1.Air from inside the building -- openings 1 square inch free area per 1000 BTUH. Never less than 100 square inches free area for each opening. See (1) in FIGURE 5.

2.Air from outside through duct -- openings 1 square inch free area per 2000 BTUH. See (2) in FIGURE 5.

3.Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See (3) in FIGURE 5.

NOTE: For further details on supplying combustion air to a confined space, see the National Fuel Gas Code ANSI Z223.1a (latest edition).

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 8

Image 8
Contents Table of Contents Series Fan-Type Unit HeatersInstallation Codes GeneralHazard Levels of Warnings in this Manual Venting Manual by ModelWarranty Uncrating and Preparation Massachusetts RequirementDimensions SizeModel Udas Separated Combustion Fan Technical Data Size 100 125Instructions for Changing Pressure Switch Pressure SwitchHigh Altitude Operation ClearancesCombustion Air applies to Model Udap and Model Model Udap and Model UDAP-CVLocation Recommendations Unit Heater LocationHeater Throw Unit Heater Location cont’d Hanging the HeaterModel Udap Size 100 125 150 175 225 250 300 350 400 Model Udas Size 100 125 150 175 225 250 300 350 400Connectors are Recommended maximum hanger rod length is 6 feet 1.8MBe sure Threaded swivel Locked toGas Connection Size Gas Piping and PressuresSizing Gas Supply Line Instructions Manifold Pressure Settings by Altitude for Canada Gas Piping and Pressures cont’dInstructions for High Altitude Derate Two -Stage ValveHigh Altitude Capacity Changes Feet MetersBurner Electrical Supply and Connections Thermostat and ConnectionsCombustion Air Proving Switch Pressure Switch Limit Control Pressure Switch SettingsCombustion Air Proving Door Switch Model Udas only Ignition System Dip SwitchNormal Heat Cycle Operating Sequence StatusLED LightsIgnition System cont’d SW1 SW2 TimeContinuous Fan Operation Fault Modes Fault Modes cont’d Lockout Gas Valve Fan MotorWiring Diagrams Operating SequenceWiring Diagrams cont’d SW1 Operating Instructions Operating Sequence Check Installation and StartupCheck the installation prior to startup Heater Startup Check installation after startup Vent System Testing Procedure Model UdapUse only factory-authorized parts Maintenance ScheduleStartup cont’d Heat Exchanger Maintenance Burner Maintenance Burner Removal Instructions Refer to FigureBurner Maintenance cont’d Inspect and Clean the Burner Re-Install the BurnerInstructions to Re-Install the Burner Refer to Figure Burner OrificeDSI Ignition SystemCont’d Fan BladesCombustion Air Pressure Switch Door SwitchOperating Gas Valve Udas onlyFlame Rollout Switch Sizes 30-125 only SwitchAir System Troubleshooting DisconnectGeneral Troubleshooting Venter motorWill not start Burner willTroubleshooting cont’d Cont’d

UDAP, UDAS specifications

Thomas & Betts is a well-respected name in the electrical and industrial products sector, known for its innovation and quality. Among its impressive portfolio, the UDAS and UDAP series of connectors stand out for their reliable performance and advanced features. These connectors are specifically designed to meet the rigorous demands of electrical applications in various industries.

The UDAS (Universal Disconnect Appliance Switch) and UDAP (Universal Disconnect Appliance Plug) are engineered for high-capacity applications where safety, efficiency, and ease of use are paramount. One of the main features of these connectors is their ability to deliver increased electrical resistance and durability. They are constructed from high-quality materials that can withstand extreme environmental conditions, making them ideal for outdoor and harsh industrial applications.

Another key technology employed in the UDAS and UDAP series is the quick-connect mechanism. This innovative design allows users to connect and disconnect circuits swiftly without requiring excessive force or complex tools. This is particularly beneficial in settings where downtime must be minimized and efficiency is crucial. Additionally, the connectors are designed to provide a secure, locking fit to ensure consistent electrical contact, thereby enhancing operational safety.

The UDAS and UDAP connectors are manufactured to comply with several industry standards, ensuring that they meet or exceed the requirements for electrical safety and performance. Their user-centric design features help in reducing installation time and costs, making them a preferred choice among contractors and engineers.

Furthermore, these connectors are versatile, compatible with a wide range of electrical systems, and can be employed in applications such as HVAC, lighting, and power distribution. They also come in various sizes and configurations to accommodate diverse specifications, improving customization options for different projects.

In summary, the Thomas & Betts UDAS and UDAP series stands out for their robust design, quick-connect technology, and versatility across various industrial applications. Their durability and compliance with safety standards make them an excellent choice for professionals seeking reliable connectivity solutions in demanding environments. Investing in these connectors ensures optimal performance and safety in electrical installations, showcasing Thomas & Betts' commitment to excellence in electrical components.