Thomas & Betts UDAP General Troubleshooting, Venter motor, Will not start, Burner will, Not light

Page 35

Check the Lights on the DSI Integrated Control Module (Circuit Board)

IMPORTANT: When using a

The integrated circuit board monitors the operation of the heater and includes two LED signal lights that indicate normal operation and various abnormal conditions. If the heater fails to operate properly, check this signal to determine the cause and/ or to eliminate certain causes. See operating sequence in Paragraph 20.

Do not attempt to repair the DSI integrated control module; the only field replace- able component is the fuse.

multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or 9 pin connectors located on the ignition control. Do not remove connectors or terminals from the electrical components. Doing so can result in misinter- preted readings due to the ignition control board’s fault mode monitoring circuits.

Control Status - Green LED Codes

Steady ON .. Normal Operation, No call for heat

Fast Flash ... Normal Operation, Call for heat

1 Flash ........ System Lockout, Failed to

detect or sustain flame 2 Flashes .... Pressure Switch Did Not

Close within 30 Seconds of Venter Motor

3 Flashes .... High Limit or Flame

Rollout Switch Open

4 Flashes .... Pressure Switch is Closed

Before Venter Motor is Energized

Steady OFF Blown fuse, No Power, or Defective Board

Flame Status - Yellow LED Codes Steady ON .. Flame is sensed

Slow Flash . Weak flame (current below

1.0microamps ± 50%)

Fast Flash ... Undesired Flame (valve open and no call for heat)

General Troubleshooting

PROBLEM

PROBABLE CAUSE

REMEDY

 

 

 

Venter motor

1. No power to unit.

1. Turn on power; check supply fuses or main circuit breaker. Turn on

will not start

 

built-in disconnect switch (Model UDAS only); replace switch if not

 

 

operating.

 

2. No 24 volt power to integrated circuit board.

2. Turn up thermostat; check control transformer output.

 

3. Integrated circuit board fuse blown.

3. Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).

 

4. No power to venter motor.

4. Tighten connections at circuit board and/or motor terminals.

 

5. Integrated circuit board defective.

5. Replace intergrated circuit board.

 

6. Defective venter motor.

6. Replace venter motor. See Paragraph 31.

Burner will

1. Manual valve not open.

1. Open manual valve.

not light

2. Air in the gas line.

2. Bleed gas line (initial startup only).

 

3. Gas pressure too high or too low.

3. Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14" w.c.

 

 

for propane gas.

 

4. No Spark:

4.

 

a) Loose wire connections.

a) Be certain all wire connections are solid.

 

b) Transformer failure.

b) Be sure 24 volts is available.

 

c) Incorrect spark gap.

c) Maintain spark gap at 1/8".

 

d) Spark cable shorted to ground.

d) Replace worn or grounded spark cable.

 

e) Spark electrode shorted to ground.

e) Replace if ceramic spark electrode is cracked or grounded.

 

f) Burner not grounded.

f) Make certain integrated circuit board is grounded to ignitor.

 

g) Circuit board not grounded.

g) Make certain integrated circuit board is grounded to furnace chassis.

 

h.) Unit not properly grounded.

h.) Make certain unit is properly field grounded to earth ground and

 

 

properly phased (L1 to hot lead L2 to neutral).

 

i) Integrated circuit board fuse blown.

i) Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).

 

j.) Faulty intergrated circuit board.

j) If 24 volt is available to the integrated circuit board and all other causes

 

 

have been eliminated, replace board.

 

5. Lockout device interrupting control circuit

5. Reset lockout by interrupting control at the thermostat or main power.

 

by above causes.

 

 

6. Interlock door switch open (UDAS only).

6. Close access door or replace switch.

 

7. Combustion air proving switch

7.

 

not closing.

a) Make sure unit is properly vented.

 

 

b) Remove obstructions from vent.

 

 

c) Replace faulty tubing to pressure switch.

 

8. Faulty combustion air proving switch.

8. Replace combustion air proving switch.

 

9. Main valve not operating.

9.

 

a) Defective valve.

a) If 24 volt is measured at the valve connections and valve remains

 

 

closed, replace valve.

 

b) Loose wire connections

b) Check and tighten all wiring connections.

Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 35

Image 35
Contents Series Fan-Type Unit Heaters Table of ContentsVenting Manual by Model Installation CodesGeneral Hazard Levels of Warnings in this ManualMassachusetts Requirement Warranty Uncrating and PreparationSize DimensionsModel Udas Separated Combustion Fan Size 100 125 Technical DataClearances Instructions for Changing Pressure SwitchPressure Switch High Altitude OperationModel Udap and Model UDAP-CV Combustion Air applies to Model Udap and ModelLocation Recommendations Unit Heater LocationHeater Throw Model Udas Size 100 125 150 175 225 250 300 350 400 Unit Heater Location cont’dHanging the Heater Model Udap Size 100 125 150 175 225 250 300 350 400Locked to Connectors areRecommended maximum hanger rod length is 6 feet 1.8M Be sure Threaded swivelGas Connection Size Gas Piping and PressuresSizing Gas Supply Line Instructions Two -Stage Valve Manifold Pressure Settings by Altitude for CanadaGas Piping and Pressures cont’d Instructions for High Altitude DerateFeet Meters High Altitude Capacity ChangesThermostat and Connections Burner Electrical Supply and ConnectionsCombustion Air Proving Switch Pressure Switch Limit Control Pressure Switch SettingsCombustion Air Proving StatusLED Lights Door Switch Model Udas only Ignition SystemDip Switch Normal Heat Cycle Operating SequenceSW1 SW2 Time Ignition System cont’dContinuous Fan Operation Fault Modes Gas Valve Fan Motor Fault Modes cont’d LockoutOperating Sequence Wiring DiagramsWiring Diagrams cont’d SW1 Operating Instructions Operating Sequence Check Installation and StartupCheck the installation prior to startup Heater Startup Vent System Testing Procedure Model Udap Check installation after startupUse only factory-authorized parts Maintenance ScheduleStartup cont’d Burner Removal Instructions Refer to Figure Heat Exchanger Maintenance Burner MaintenanceBurner Orifice Burner Maintenance cont’dInspect and Clean the Burner Re-Install the Burner Instructions to Re-Install the Burner Refer to FigureDSI Fan Blades IgnitionSystem Cont’dUdas only Combustion Air Pressure SwitchDoor Switch Operating Gas ValveDisconnect Flame Rollout Switch Sizes 30-125 onlySwitch Air System TroubleshootingBurner will General TroubleshootingVenter motor Will not startCont’d Troubleshooting cont’d

UDAP, UDAS specifications

Thomas & Betts is a well-respected name in the electrical and industrial products sector, known for its innovation and quality. Among its impressive portfolio, the UDAS and UDAP series of connectors stand out for their reliable performance and advanced features. These connectors are specifically designed to meet the rigorous demands of electrical applications in various industries.

The UDAS (Universal Disconnect Appliance Switch) and UDAP (Universal Disconnect Appliance Plug) are engineered for high-capacity applications where safety, efficiency, and ease of use are paramount. One of the main features of these connectors is their ability to deliver increased electrical resistance and durability. They are constructed from high-quality materials that can withstand extreme environmental conditions, making them ideal for outdoor and harsh industrial applications.

Another key technology employed in the UDAS and UDAP series is the quick-connect mechanism. This innovative design allows users to connect and disconnect circuits swiftly without requiring excessive force or complex tools. This is particularly beneficial in settings where downtime must be minimized and efficiency is crucial. Additionally, the connectors are designed to provide a secure, locking fit to ensure consistent electrical contact, thereby enhancing operational safety.

The UDAS and UDAP connectors are manufactured to comply with several industry standards, ensuring that they meet or exceed the requirements for electrical safety and performance. Their user-centric design features help in reducing installation time and costs, making them a preferred choice among contractors and engineers.

Furthermore, these connectors are versatile, compatible with a wide range of electrical systems, and can be employed in applications such as HVAC, lighting, and power distribution. They also come in various sizes and configurations to accommodate diverse specifications, improving customization options for different projects.

In summary, the Thomas & Betts UDAS and UDAP series stands out for their robust design, quick-connect technology, and versatility across various industrial applications. Their durability and compliance with safety standards make them an excellent choice for professionals seeking reliable connectivity solutions in demanding environments. Investing in these connectors ensures optimal performance and safety in electrical installations, showcasing Thomas & Betts' commitment to excellence in electrical components.