Thomas & Betts RZ405, RGM 405 dimensions Condensation, Vent Terminal Pipe and Vent Cap

Page 11

5)Condensation

Any length of single-wall vent pipe exposed to cold air or run through an unheated area or an area with an ambient temperature of 45°F or less must be insulated along its entire length with a minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation. Where extreme conditions are anticipated, install a means of con- densate disposal.

6)Vent Terminal (Pipe and Vent Cap)

The vent system must be terminated with the type of vent cap approved for use with this heater. The vent cap must be the same size as the vent pipe. Use either a vent cap available from the

Figure 8 - Horizontal Vent Terminals

heater manufacturer (Option CC1) or a field-supplied cap. If the vent cap is field-supplied, use a Type L Breidert Air-x-hauster®or equivalent vent cap. (Type L Air-x-hauster®is a trademark of The G. C. Breidert Company.) Use of a vent cap supplied by the pipe manufacturer is not permitted; the vent cap must be the type approved for use with this heater. A different style vent cap could cause nuisance problems or unsafe conditions.

See the illustrations in Figures 9A and 9B for requirements of vertical and horizontal vent termination. The vent terminal pipe may be either single- wall or double-wall (Type B). If double-wall pipe is used in the vent termi- nal with a single-wall vent run, follow the instructions on page 10 to attach the vent cap and to connect the double-wall pipe to the single-wall vent pipe run.

Single-Wall

Single-Wall Vent

Run and Single-

Wall Terminal

Wall

Approved clearance thimble for single-wall vent pipe is required when flue pipe extends through combustible materials.

Roof or Building Overhang

AdjoiningBuilding

12”

3’(1M) minimum

6’ (2M)

(305mm)

 

 

 

minimum

 

 

 

 

 

minimum

Parapet or

 

 

 

Note position of vent cap openings.

Pitch flue pipe down toward outlet 1/4” per foot for condensate drainage. (NOTE: Applies to entire horizontal vent run.)

Vent Run

Roof or Building Overhang

 

and Double-

 

 

 

 

Wall

 

 

 

Terminal

 

 

 

minimum(152mm)6”

12”

(1M)3’ minimum

AdjoiningBuilding

(305mm)

minimum

 

 

 

6’ (2M)

 

 

 

minimumor

Wall

 

 

Parapet

 

Note position of

vent cap openings.

Approved clearance

Pitch flue pipe down toward

thimble for single-wall

outlet 1/4” per foot for con-

vent pipe is required

densate drainage.

when flue pipe extends

(NOTE: Applies to entire

through combustible

horizontal vent run.)

materials. Follow

 

the requirements

 

of the double-wall

 

pipe manufacturer.

 

Horizontal Vent Terminal Clearances

Follow instructions on page 10 to join single and double-wall pipe and to seal the connection.

A vent cap is required. Maintain a clearance of 12" from the wall to the vent terminal cap for stability under wind conditions.

Products of combustion can cause discolora- tion of some building finishes and deteriora- tion of masonry materials. Applying a clear silicone sealant that is normally used to pro- tect concrete driveways can protect masonry materials. If discoloration is an esthetic prob- lem, relocate the vent or install a vertical vent.

Structure

Minimum Clearances for Vent Termination

 

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1m)

3 ft

(0.9m)

above

Combustion air inlet of another appliance

 

 

 

 

6 ft (1.8m)

Door, window, or gravity air inlet

4

ft

(1.2m) horizontally

(any building opening)

4

ft (1.2m) below

 

1

ft (30cm) above

Electric meter, gas meter* and relief

4

ft

(1.2m)

*Do not terminate the vent

equipment

horizontally

directly above a gas meter

Gas regulator*

3

ft

(0.9m)

or service regulator.

Adjoining building or parapet

6

ft

(1.8m)

 

Adjacent public walkways

7

ft (2.1m)

above

Grade (ground level)

7

ft (2.1m)

above

Figure 9 - Vertical Vent Terminals

Single-Wall Vent

Run and Single-

Wall Terminal

Building

6’ (2M) minimum

 

Adjoining

Roof Flashing

 

or

Roof - pitched

from 0 to 45°

Parapet

Approved clearance thimble

 

for single-wall vent pipe is

 

required when flue pipe

 

extends through

 

combustible materials.

Vertical flue extension to be 6” (152mm) higher than anticipated snow depth but no less than 2 feet (610mm) above the roof.

Vertical pipe extension must be insulated.

Parapet or Adjoining Building

Single-Wall Vent

Run and Double-

Wall Terminal

6’ (2M) minimum

Roof Flashing

Roof - pitched from 0 to 45°

6” (152mm) minimum

Follow instructions on page 10 to join single and double-wall pipe and to seal the connection.

Vertical flue extension to be 6” (152mm) higher than anticipated snow depth but no less than

2 feet (610mm) above the roof.

Approved clearance thimble for single-wall vent pipe is required when flue pipe extends through combustible materials. Follow the requirements of the double-wall pipe manufacturer.

Mfg No. 164771, Page 11

Image 11
Contents Model Caua Table of ContentsMounting the Heater Installation CodesWarranty Clearances General ContdAir Opening Dimensions DimensionsDimensions inches + or 1/8 Dimensions mm +orIndus Trial Decide which Venting System to InstallVenting and Combustion Air CommercialConcentric Adapter Combustion Air InletVenter Outlet Clearance Venting and Combustion Air contdJoints SupportWall Flash or caulkInlet air pipe On the outsideSide View Installation Instructions for Option CC22b Install the rubber seal Terminal 559mm minimum SnowClearance ExhaustVent System Support Vent Pipe and JointsVenter Flue Outlet Vent Pipe Diameter and LengthHorizontal Vent Terminal Clearances CondensationVent Terminal Pipe and Vent Cap Size 150 250 350 36 914mm 48 1219mm 21 533mm 34 864mm Duct Connections and DuctworkCut edges of the metal will be sharp Supply Piping Manifold or Orifice Pressure SettingsGas Piping and Pressures Sizing a Gas Supply LineElectrical Supply and Connections Manifold Pressure Settings contdGas Piping and Pressures contd Burner Condensate DrainBelt Drive Combustion Air Proving SwitchBlower Motor and Drive Direct DriveIgnition System Adjusting Blower SpeedBlower Motor and Drive contd Gas ValveTypical Wiring Diagrams Typical Wiring Diagrams contd Electrical Connections Low Voltage Wiring field-suppliedOptional Cased Cooling Coil, Model ACUA, ACUB, or Acuc Burner Condensate DrainMixing Cabinet Outside and Return Air Optional Outside Air Return Air Mixing Box Discharge Plenum Sizes400 only Inlet Base Sizes 350 and 400 only250 Check/Test/Start-Up Check Installation & Start-UpCheck the installation prior to start-up Start-UpTo Turn OFF GAS to the Appliance Check installation after start-upManufacturer of HEATING, COOLING, and Ventilating Systems