Thomas & Betts RGM 405, RZ405 dimensions Mixing Cabinet Outside and Return Air

Page 20

OPTIONAL ACCESSORIES (cont'd)

18. Optional Filter Cabinet (return air only)

A filter cabinet designed for 2" pleated disposable or permanent metal filters is shipped separately for field assembly and installation. Depending on the option selected, filters are either shipped with the cabinet or are field-supplied.

To adapt to a variety of applications, the heater cabinet is designed so that the filter cabinet can attach on either the right side, the left side, or the rear of the heater. The larger filter cabinets (left two tables below) are uniquely designed so that the same cabinet can be field-assembled and installed with either a horizontal or vertical air inlet. The smaller filter cabinet in the table on the right is limited to Sizes 150 and 200 and is available with a horizontal inlet only. All cabinets have door panels for easy filter removal for changing or cleaning.

All of the filter cabinets have a duct flange for attaching the inlet air duct. For inlet duct dimensions, see Paragraph 8.

Follow the step-by-step instructions included with the filter cabinet package to assemble and attach it to the heater.

Figure 21 - Filter Cabinets with Filter Arrangements and Filter Sizes

Option CW4 with 2" Pleated Filters

Option CW7 with 2" Pleated Filters

Option CW5 with 2" Permanent Filters

Option CW12 with 2" Permanent Filters

Option CW6 for Field-Supplied Filters

Option CW11 for Field-Supplied Filters

• Attaches on Either Side of the Heater

• Attaches on the Rear of the Heater

• Vertical (Top) or Horizontal Inlet Opening

• Vertical (Top) or Horizontal Inlet

• "V" Filter Rack Arrangement

Opening

 

• "V" Filter Rack Arrangement

Figure 21A -

Figure 21B -

Assembled

Assembled with

with

Vertical Air

Inlet Opening

Horizontal

Air Inlet

 

 

Opening

Option CW8 with 2" Pleated Filters

Option CW9 with 2" Permanent Filters

Option CW10 for Field-Supplied Filters

Attaches on either Side or the Rear of a Size 150 or 200 Heater

Horizontal Inlet Opening

"V" Filter Rack Arrangement

Figure 21C -

Small Filter Cabinet for Sizes 150 and 200 only -- Horizontal Air Inlet Only

Sizes of Permanent or Pleated 2"

Filters for Options CW4, CW5, or CW6

Size

CFM

FPM

Filters

150

1800

281

(4) 16 x 16

 

 

 

 

 

2400

375

(4) 16 x 16

 

 

 

 

 

3000

469

(4) 16 x 16

200

2400

375

(4) 16 x 16

 

3000

469

(4) 16 x 16

250

3000

469

(4) 16 x 16

 

 

 

 

 

*4000

625

(4) 16 x 16

 

 

 

 

 

**5000

781

(4) 16 x 16

 

 

 

(4) 16 x 16

300

3000

469

(4) 16 x 16

 

 

 

 

 

*4000

625

(4) 16 x 16

 

 

 

 

 

**5000

781

(4) 16 x 16

 

 

 

(4) 16 x 16

350

4300

448

(6) 16 x 16

 

5000

521

(6) 16 x 16

 

 

 

 

 

*6000

625

(6) 16 x 16

400

4300

448

(6) 16 x 16

 

5000

521

(6) 16 x 16

 

 

 

 

 

*6000

625

(6) 16 x 16

Sizes of Permanent or Pleated 2" Filters for Options CW7, CW12, or CW11

Size

CFM

FPM

Filters

150

1800

281

(4) 16 x 16

 

 

 

 

 

2400

375

(4) 16 x 16

 

 

 

 

 

3000

469

(4) 16 x 16

200

2400

375

(4) 16 x 16

 

3000

469

(4) 16 x 16

250

3000

313

(6) 16 x 16

 

 

 

 

 

4000

417

(6) 16 x 16

 

 

 

 

 

5000

521

(6) 16 x 16

300

3000

313

(6) 16 x 16

 

4000

417

(6) 16 x 16

 

 

 

 

 

5000

521

(6) 16 x 16

350

4300

448

(6) 16 x 16

 

5000

521

(6) 16 x 16

 

 

 

 

 

*6000

625

(6) 16 x 16

400

4300

448

(6) 16 x 16

 

 

 

 

 

5000

521

(6) 16 x 16

 

 

 

 

 

*6000

625

(6) 16 x 16

Filters for Options CW8, CW9, CW10

Size CFM FPM

2" Filters

 

 

 

Pleated

Permanent

150

1800

375

(2) 12 x 32

(4) 12 x 16

 

2400

500

(2) 12 x 32

(4) 12 x 16

 

 

 

 

 

 

*3000

625

--

(4) 12 x 16

200

2400

500

(2) 12 x 32

(4) 12 x 16

 

 

 

 

 

 

*3000

625

--

(4) 12 x 16

NOTES:

*Requires 2" permanent filters.

**If using side inlets, two cabinets must be installed, one on each side.

19. Mixing Cabinet (Outside and Return Air)

The optional mixing box for the Reznor® Model CAUA heater is designed to provide the system with a supply air mixture of return air and outside air. Any percentage of outside air can be supplied to the unit as long as the air temperature entering the blower is 35°F or above. The mixing box is available in an assortment of configurations with a selection of actuators and controls. All mixing boxes are completely assembled at the factory for field attachment to the rear of a Model CAUA heater.

Follow the instructions packed with the mixing box to cut out the opening and attach the mixing box. If the mixing box has dampers, follow the

instructions for routing the damper motor wires, and connect the wires according to the wiring diagram. If there are both return air and outside air dampers, follow the directions to adjust the damper linkage.

All mixing box inlet air openings have duct flanges for attachment of ductwork. Ductwork must be attached to the outside air opening. Removable door panels provide for filter access from either end of the cabinet. If the box was ordered with optional filters, it is shipped with the filters installed.

Form 405, Page 20

Image 20
Contents Table of Contents Model CauaInstallation Codes Warranty ClearancesGeneral Contd Mounting the HeaterDimensions Dimensions inches + or 1/8Dimensions mm +or Air Opening DimensionsDecide which Venting System to Install Venting and Combustion AirCommercial Indus TrialConcentric Adapter Combustion Air InletVenter Outlet Venting and Combustion Air contd JointsSupport ClearanceFlash or caulk Inlet air pipeOn the outside WallSide View Installation Instructions for Option CC22b Install the rubber seal 559mm minimum Snow ClearanceExhaust TerminalVent Pipe and Joints Venter Flue OutletVent Pipe Diameter and Length Vent System SupportHorizontal Vent Terminal Clearances CondensationVent Terminal Pipe and Vent Cap Size 150 250 350 36 914mm 48 1219mm 21 533mm 34 864mm Duct Connections and DuctworkCut edges of the metal will be sharp Manifold or Orifice Pressure Settings Gas Piping and PressuresSizing a Gas Supply Line Supply PipingManifold Pressure Settings contd Gas Piping and Pressures contdBurner Condensate Drain Electrical Supply and ConnectionsCombustion Air Proving Switch Blower Motor and DriveDirect Drive Belt DriveAdjusting Blower Speed Blower Motor and Drive contdGas Valve Ignition SystemTypical Wiring Diagrams Typical Wiring Diagrams contd Low Voltage Wiring field-supplied Optional Cased Cooling Coil, Model ACUA, ACUB, or AcucBurner Condensate Drain Electrical ConnectionsMixing Cabinet Outside and Return Air Discharge Plenum Sizes 400 onlyInlet Base Sizes 350 and 400 only Optional Outside Air Return Air Mixing BoxCheck/Test/Start-Up Check Installation & Start-Up Check the installation prior to start-upStart-Up 250Check installation after start-up To Turn OFF GAS to the ApplianceManufacturer of HEATING, COOLING, and Ventilating Systems