F. Install Vertical Termination Cap

Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.

Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 10.13).

TERMINATION CAP

(1 of 3)

STORM

COLLAR

SCREWS

CAULK

Figure 10.13

G.Heat Shield Requirements for Horizontal Termination

WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness.

DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10.14.

Heat shields must overlap 1-1/2 in. (38 mm) mini- mum.

There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 10.20.

If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.

If the wall thickness is less than 4 in./102 mm (DVP), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.

Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).

The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.

Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.

Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.

Important Notice: Heat shields may not be field constructed.

H. Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.

1-1/2 (38 mm) minimum overlap of flue telescoping section is required.

Failure to maintain overlap may cause overheating and fire.

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at outside edges of cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149installation codes and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require in- stallation of a cap shield to prevent anything or anyone from touching the hot cap.

NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a flashing kit is available. When penetrating a brick wall, a brick extension kit is available for framing the brick.

Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall.

HEAT SHIELD OR

HEAT SHIELD

EXTENDED

1-1/2 IN. (38 MM) MIN.

HEAT SHIELD

OVERLAP

WALL SHIELD

 

FIRESTOP

 

SLIP SECTION

 

CAN BE EXTENDED

 

INNER VENT

SHEATHING

OUTER VENT

 

INTERIOR

EXTERIOR

VENT DEPTH FROM BACK OF APPLIANCE TO

 

OUTSIDE SURFACE OF EXTERIOR WALL

 

(SEE CHART BELOW)

 

Figure 10.14 Venting Through the Wall

Heatilator • HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12

43

Image 43
Contents HOT Surfaces ModelsWhat to do if you smell gas Do DiscardnotHomeowner Reference Information CongratulationsUser Guide Table of ContentsTroubleshooting Appliance SetupReference Materials Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches IPI Battery Tray/Battery InstallationBefore Lighting Fireplace Module ResetNine Hour Safety Shutdown Feature Control Module OperationGAS Valve Lighting Instructions IPIFinal inspection by What to do if YOU Smell GASIssue Solutions Frequently Asked QuestionsAfter Fireplace is Lit Remote Control Optional Maintenance and ServiceMaintenance Tasks-Homeowner Glass Cleaning Exterior of Installed Glass OnlyLogs Maintenance Tasks-Qualified Service TechnicianGlass Cleaning Exterior and Interior of Installed Glass Gasket Seal and Glass Assembly InspectionIPI Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components HEIR42 Framing and ClearancesSelecting Appliance Location HEIR36Constructing the Appliance Chase Minimum Framing DimensionsClearances Non-Combustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsNon-Combustible Zone Combustible Mantel Legs or Wall ProjectionsCombustible Mantel Allowance HEIR36, HEIR42 NON-COMBUSTIBLE Material HEIR50 Fireplace OpeningModel Hearth ExtensionVent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Clearance above electrical serviceVent Information and Diagrams One Elbow Top Vent Horizontal TerminationHEIR36 NG/LP, HEIR42 NG/LP HEIR50 NG/LP H1+ H2 Two ElbowsHEIR36 NG/LP, HEIR42 NG/LP, HEIR50 NG/LP Top Vent Horizontal Termination Three ElbowsFlue Restrictor Elbows Top Vent Vertical TerminationHt Max Top Vent Vertical Termination Three ElbowsHEIR42 PVK-80 and PVI-SLP InformationPVI-SLP HEIR36Non-Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe DVP Install the Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-ZoneGas Kit Flat Ceiling InstallationVent Preparation Appliance PreparationSide Nailing Tab in Shipping Position Securing and Leveling the ApplianceInstalling Non-Combustible Facing Material Installing Non-combustible Facing MaterialAssemble Pipe Sections Installing Vent Pipe DVP PipeAttach Vent to the Firebox Assembly Assemble Vent SectionsDisassemble Vent Sections Secure the Vent SectionsAssemble and Install Storm Collar Install Metal Roof FlashingInstall Horizontal Termination Cap Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination Gas Connection Gas InformationFuel Conversion Gas PressureElectrical Information Wiring RequirementsIntelliFire PlusTM Ignition System Wiring Optional Accessories RequirementsAccess Through Left Column Access Through Firebox Electrical Service and Repair Junction Box InstallationFinishing Template installation instructionFinishing Templates Finishing Template Bends Inoperable Fixed Doors Splatter GuardNon-Combustible Zone 10 Combustible Mantel Allowance HEIR36, HEIR42 Combustible Mantel ProjectionsModel HEIR36 Facing MaterialOperable Doors Dimension Inoperable Operable DoorDoors ArchAppliance Setup LOG#4 Install the Log Assembly Log Set Assembly LOGS-HEIR36LOG Placement Tabs LOG Placement Slot Notch for Models HEIR36H, HEIR36SContacts Back Burner Grate NotchLOG Contacts Notch Rests On Burner Grate Tine HEIR42 only Burned Edge PortionHEIR42 Shown Burned Portion Edge of LOG Used For Positioning For LOG #5Burned Portion LOG does not 2CONTACT Grate TineLOG Contacts Grate Tine Log Set Assembly LOGS-HEIR50 Models HEIR50T, HEIR50HBurned Edge LOG Contacts Side Refractory LOG Contacts Grate Tine Approximately HEIR36 HEIR42 HEIR50 TOP Retaining Rail Notch Glass Frame Notch Full Open Air Shutter SettingAir Shutter Settings Flame AppearanceSymptom Possible Cause Corrective Action TroubleshootingIntelliFire Plus Ignition System Troubleshooting Reference Materials Appliance Dimension Diagram1905 DVP-AS2 Vent Components DiagramsDVP-TRAP DVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2COOL-ADD RF6M RF12MBEK DVP-BEK2 DVP-TRAPFLDescription Part Number Optional Wire HarnessSLP-LPC Description Comments Part Number Service PartsLog Set Assembly At DepotStocked #19 Traditional Refractory #20 Herringbone RefractoryDescription Comments Part Number HEIR42T, HEIR42H HEIR42T, HEIR42H HEIR50T, HEIR50H Log Set Assembly#20 Traditional Refractory #21 Herringbone Refractory HEIR36, HEIR42, HEIR50 #11 Valve AssemblyMYSTIC-EMBERS Contact Information

HEIR50H, HEIR36T, HEIR36H, HEIR50T, HEIR42T specifications

The Heatiator range of heating appliances, including the HEIR36T, HEIR50T, HEIR42H, HEIR42T, and HEIR50H, represents a blend of cutting-edge technology and stylish design, tailored to meet various heating needs in residential spaces. Each model exhibits unique features, yet shares a commitment to efficiency and user-friendliness.

Starting with the HEIR36T, this model is compact yet powerful, making it ideal for smaller living areas. It boasts an efficient heating system that utilizes advanced ceramic heating elements, ensuring rapid warmth. The sleek design is complemented by a digital control panel, allowing users to easily adjust settings for optimal comfort.

In contrast, the HEIR50T caters to larger rooms, offering increased power and a higher heat output. Its robust construction is designed for durability, while energy-efficient technology minimizes operational costs. The HEIR50T comes equipped with a programmable thermostat, enabling users to set heating schedules to align with their lifestyle.

The HEIR42H stands out with its hybrid heating capability, combining traditional radiant heat with modern convection elements. This dual functionality allows for faster and more even heat distribution throughout the space. The HEIR42H is particularly popular for its versatility, suitable for use in various environments from homes to commercial spaces.

The HEIR42T model shares many of the benefits of the HEIR42H but focuses on a sleek, slim-line design that doesn’t compromise on performance. Ideal for minimalistic interiors, it offers the same advanced heating technology, ensuring efficient warmth without taking up excess space.

Lastly, the HEIR50H is designed for heavy-duty performance, making it the perfect choice for larger areas that require substantial heating power. It features enhanced insulation and expanded heating elements, ensuring that even the coldest rooms achieve a comfortable temperature quickly.

In summary, the Heatiator HEIR series exemplifies innovation in home heating solutions. With various models to choose from, customers can select the unit that best suits their space requirements while benefiting from technologies designed for efficiency and comfort. The digital controls, programmable settings, and modern designs make these heaters both functional and aesthetically pleasing, reinforcing Heatiator's commitment to quality and user satisfaction.